Match the pitch and the contact count first, then make the rest of the plug earn its place. The blocks on compact PLCs almost always run a 3.81 mm [0.150 in] contact pitch, so confirm yours with a caliper before you order anything. The contact count is fixed by the connector position, commonly 8 or 15, and it can change from one module to the next on the same CPU. Pitch and count are only the screen, though: the maker's block also carries a molded keying tab that snaps into the carrier and a latch that holds the plug under vibration. An aftermarket block with the right pitch and count can slide on, pass a bench test, and still walk loose in a running panel. Measure, compare against the maker's dimensioned drawing, and fit the maker's own block wherever the panel runs; the steps below put the checks in order.
What has to match
A replacement block has to satisfy two interfaces at once. The electrical interface lines every plug contact up with its pin at the right spacing. The mechanical interface sets orientation, seating depth and retention, and it is where lookalike plugs fail. Rows of these plugs sit on the backplate beside DIN rail and wire duct, and a body even a millimetre wider can foul its neighbor; keep the row clearances the backplate layout guide gives.
| Feature | What to compare | What passes |
|---|---|---|
| Pitch | Caliper across every interval of the row | 3.81 mm [0.150 in] between contact centers |
| Contact count | Count the pins on that header position | The same count, position by position |
| Housing profile | Width, height and insertion depth against the maker drawing | Full seating under normal hand force |
| Keying tab | Tab location on the drawing | Tab present, same place, engages the carrier |
| Latch | Side latches or center screw, per the drawing | Positive click on insertion, clean release |
| Ratings | Datasheet voltage, current and wire range | Covers the circuit with margin |
| Duty | Vibration and washdown at that panel | Latched construction, not friction alone |
Commercial connector families exist at the same pitch, some molding a star key into the plug face. A star key is not the carrier tab: the PLC's molded tab snaps into the carrier and sets both position and retention. Two more checks sit outside the table. A substitute block's ratings feed the panel's fault rating, so read what sets the short-circuit rating in a control panel before a different block goes in. And connector keying is purely mechanical; it has nothing to do with electronic keying, the compatibility check controller software applies when an I/O module changes.
What you need
Nothing exotic, and most of it lives in a panel drawer already:
- A digital caliper reading to 0.01 mm [0.0005 in]; pitch decides the order.
- The full model designation off the module label, written down.
- The maker's dimensioned drawing or datasheet for the block; a catalog photo hides the dimensions that decide.
- Straight-on photos of the mating face, both sides of the old block, and the carrier it snaps into.
- The wiring schematic with channel assignments; when to use terminal blocks in a panel covers what belongs on that drawing.
- A release tool or small screwdriver to match the latch design, and fresh wire labels.
Replacing the block, step by step
- Write the full model designation off the module label and note which connector position lost its block; count and keying can differ between positions on the same CPU.
- Take the block's part number from that model's parts list in the maker's documentation; that block is the reference every candidate gets measured against.
- Count the contacts on the header itself, pin by pin; the slots in a lost plug's shell are not a count.
- Measure the pitch across the full row and divide by the number of intervals; the worked example below runs the arithmetic.
- Photograph the mating face straight-on and from both sides, then compare keys, tabs, partitions and latch surfaces against the drawing.
- Compare body width, height and insertion depth with the drawing. A bare hobby-grade PCB socket measures about 10.5 × 9.2 mm [0.41 × 0.36 in], while PLC plugs add latch wings and wire entry, so compare numbers rather than looks.
- Read the candidate datasheet for rated voltage, current, wire range and strip length. IEC 60947-7-1 covers screw-type and screwless blocks up to 1000 V AC (to 1000 Hz) or 1500 V DC, and the short-time withstand current test in IEC 60947-7-1/-2 gives the fault-current figure.
- Isolate the PLC and verify absence of voltage, then dry-fit the empty plug: correct orientation, full seating, a positive click, and clean release with the intended tool.
- Move the wires across one at a time, re-terminating each to the datasheet strip length, and check every label against the schematic; strip length loosens more wires than bad blocks do, as why wires back out of screw-clamp terminals shows.
- Dress the loom back into the duct, keeping the row spacing and finger-duct clearance between terminal rows.
- Seat the block, confirm the click, restore power, and switch each output on and off while watching each input come back.
Measuring pitch on an 8-contact block
The inputs: an 8-contact plug, the size carried by the common I/O positions; the pitch documented for these compact-PLC connectors, 3.81 mm [0.150 in] between contact centers; and a caliper reading to 0.01 mm. Count your contacts first, because the arithmetic only works with the real number.
The rule: pitch equals the span across the outermost contact centers divided by the number of intervals, and 8 contacts make 7 intervals. Measuring a single interval puts the whole answer on one jaw placement; spreading the measurement over the full row divides any placement error by 7.
The arithmetic: a correct row spans 7 × 3.81 mm = 26.67 mm [7 × 0.150 in = 1.05 in]. A caliper reading of 26.64 mm gives 26.64 ÷ 7 = 3.81 mm, and the pitch matches. A reading of 24.50 mm gives 24.50 ÷ 7 = 3.50 mm, a different pitch family. The families sit far enough apart that a caliper cannot confuse them: 3.81 mm and 3.50 mm differ by 0.31 mm per interval, which is 2.17 mm across the full row. A 5.08 mm [0.200 in] family would span 35.56 mm [1.40 in] and be obvious at a glance.
Result: pitch 3.81 mm [0.150 in], matching the documented connector. The decision rule: divide your reading by the number of intervals. A result equal to the documented pitch passes the screen; 3.50 mm [0.138 in] or 5.08 mm [0.200 in] means a plug from another family that misaligns every contact beyond the first, and it goes back.
Checks when the new block is in
A block that looks right on the bench still has to pass five checks, in this order:
- Contact alignment. Every plug contact sits centered over its pin across the full width; a cumulative offset at the far end means the pitch is wrong even with the count right.
- Seating. The housing reaches its seated line under normal hand force, with no rocking and no molded feature bearing against the wrong surface.
- Retention. A firm pull on the wiring loom shifts the plug not at all. Friction alone is what you get when the latch or carrier tab is missing, and the same logic that keeps ceiling-receptacle plugs captured applies here.
- Point-to-point continuity. With power still isolated, expect continuity from every field wire to its assigned terminal and an open circuit to every neighbor, schematic in hand.
- Live I/O. Each commanded output reaches its field device and each input reads true; any flicker sends you back to the dry-fit for another look at contact engagement.
Mistakes that leave you with a loose plug
The plug that seats but never clicks is the trap worth naming twice, because it passes every bench test and fails in service. The usual ways a replacement goes wrong:
- Retention by friction alone. Without the latch or a captured carrier tab, machine vibration and the shaking a washdown panel takes walk the plug out over weeks; latching is exactly what plug-in connector families add for vibration resistance.
- A filed or scraped keying tab. The tab is the keying and half the retention; a modified block is fine for a locked-out bench trial, then goes back in the drawer tagged as a test part.
- Ordering from a photograph. Photos flatten the 0.31 mm that separates pitch families; only a dimensioned drawing carries insertion depth and tab position.
- A block moved from another model. Same pitch, different tab: count and keying are set per position, so salvage clears the table above or it clears the panel.
- A lower-rated substitute. Rated current and short-time withstand feed the panel's fault ratings, and a smaller block can quietly set the limit for everything upstream.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will a 5.08 mm pitch plug fit a 3.81 mm PLC header?
The rows cannot line up. The pitch difference is 1.27 mm per contact, so contact 2 already sits 1.27 mm off its pin, and by contact 8 the two rows are 8.89 mm apart (7 × 1.27 mm). Even a two-contact span misses badly enough to bend pins. Pitch has to match the header exactly, contact row to contact row.
Are pluggable terminal blocks on a PLC covered by a standard?
Yes. IEC 60947-7-1 covers terminal blocks with screw-type and screwless clamping units, with rated voltages up to 1000 V AC (up to 1000 Hz) or 1500 V DC. It also specifies the short-time withstand current test behind the fault-current figure on a block's datasheet; compare that figure with the panel's fault rating before you substitute.
Can I file the keying tab off a generic plug to make it fit?
It will slide on, and that is all you gain. The tab carries the keying that keeps a block out of the wrong position and half the retention that holds it in the right one, so a filed plug relies on contact friction alone. Keep a modified block on the bench, tagged as a test part, and fit the maker's block in the panel; the click test settles the question in two seconds.
Where do I find the part number for a lost terminal block?
Read the full model designation from the module label, then take the block's part number from that model's parts list in the maker's documentation; connector positions can differ in count and keying on the same PLC, so match the part to the position. With the paperwork gone, a block salvaged from a scrap unit of the same model is the next best source, and it still passes the same dimension and retention checks.





