Single-ended wiring gives each channel one signal conductor against one shared common: 17 conductors for a 16-channel card. Differential wiring gives each channel its own pair: 32 conductors plus shields on the same card, and on some cards only 8 usable channels. Pick the mode before you order anything with terminals in it. The mode sets your wire count, your DIN rail length, your duct fill and your gland holes, and it decides how much box you need on the wall.
What is the difference between single-ended and differential analog inputs?
A single-ended channel measures one signal conductor against a common reference shared by every channel, while a differential channel measures between its own two conductors — 17 field wires for a 16-channel card one way, 32 the other. On a single-ended card you land each signal on its own terminal and tie every return to one common terminal, so the card sees each signal against that common. The negative terminal of a differential channel is a measurement connection, not a protective earth, and it never carries another channel's current.
IEC 61131-3 lets you declare an analog channel as a data type in your program, which makes the channel feel like software. The measurement still happens between two metal points, and the wiring mode decides which two. The choice is electrical first — a differential pair rejects interference that lands on both conductors equally — and physical second: the pair doubles your field conductors, your terminals and most of your gland entries.
How many terminals does each channel need?
One signal terminal per channel plus a single shared common for single-ended, against a dedicated pair of terminals per channel for differential: on a 16-channel card that is 18 terminal positions against 33, counting the shield landing. The count at the card matches the count at your terminal rail, which is why the mode belongs on the enclosure drawing rather than in the electrician's head.
| What you count | Single-ended, 16 channels | Differential, 16 channels |
|---|---|---|
| Signal conductors | 16 | 32 (16 pairs) |
| Shared common | 1 | none |
| Shields to land | 1 overall | 16 pair shields + 1 overall, on a bar |
| Rail at 0.2 in [5.08 mm] pitch | 18 terminals = 91 mm [3.6 in] | 33 terminals = 168 mm [6.6 in] |
| Gland entries for 12 mm OD cable | 1 x M20 | 2 x M20 |
The shield row is where builders lose count. A multipair instrument cable wraps a shield around each pair and another around the whole cable, so a 16-pair differential run can put 17 shield ends at your bar. Land them on a shield bar rather than on 17 individual terminals, and label the bar so the next person reads it as one system.
Count the card's own terminals from its channel-allocation diagram, not from the terminal strip. The diagram tells you whether a differential channel owns its pair or borrows two single-ended terminals. For grouping terminals on the plate, analog signal conditioning layout shows the same count on a built panel.
Does differential wiring halve the channel count?
On some cards, yes: a differential channel is built from two single-ended inputs, so a 16-input card delivers 8 differential channels, while cards with dedicated terminal pairs keep all 16. Both architectures are on the market, and the card's channel-allocation diagram says which one you hold. If the job needs 16 differential channels and your card combines inputs, order the 32-terminal member of that card family and size the enclosure to its rail length.
The enclosure feels the difference before the card does. Sixteen differential channels at 33 terminal positions want roughly twice the rail of the single-ended version plus a second gland entry, in the same cabinet.
How much noise does differential wiring reject?
Differential wiring cancels the noise that both conductors of a pair pick up equally, up to the printed common-mode limit of the input — one documented 0-100 V input module specifies 750 V DC or peak AC. Interference from a contactor coil or a drive's output cable tends to land on both conductors almost equally, because they run together, and the subtraction removes that common part. Interference that appears between the two conductors still reads as signal, which is why the pair stays twisted for its whole run.
Single-ended channels pay for their economy in the common. Sixteen 4-20 mA loops at full scale push 16 x 0.02 A = 0.32 A back through that one conductor. Twenty metres of 1.0 mm² copper is 0.0172 x 20 / 1.0 = 0.34 Ω, so the field end of the common sits 0.32 x 0.34 = 0.11 V away from the card end. Every channel sharing that common reads the offset: 1.1 % of a 0-10 V span, 2.2 % of a 0-5 V span, and it moves as loops load and unload.
Two fixes keep single-ended honest without rewiring the plant. Split the returns across two or three common terminals so no conductor carries all sixteen loops, or double the common's cross-section, which halves the drop to 0.05 V. When your channels arrive from another enclosure with its own reference, grounding between enclosures with single-ended signals covers where that reference belongs.
Is a differential input also an isolated input?
No. Differential tells you where the channel measures; isolation tells you what it is galvanically separated from. Isolated cards print a dielectric test value, commonly 500 V AC held for one minute, and every isolated input is differential — not the other way round. A card can be fully differential and still tie all sixteen channels to one reference bus, so two transmitters on two separate supplies can push their references further apart than the inputs tolerate.
This is where differential current inputs earn their keep: they accept sensors powered from their own supplies, away from the noise a panel supply picks up when coils and solenoids switch. Budget the loop the same either way. A 24 V supply minus 5 V across a 250 Ω sense resistor at 20 mA leaves 19 V for transmitter and wiring, and a transmitter that needs 12 V minimum keeps 7 V of margin. Differential wiring adds no loop voltage; the pair only changes where the measurement sits.
How do I size the enclosure for 16 analog channels?
For 16 differential channels, plan 168 mm [6.6 in] of terminal rail, about 226 mm² [0.35 in²] of duct fill and two M20 gland entries; the same 16 channels single-ended take 91 mm [3.6 in] of rail and one gland. Work it in that order — terminals, duct, glands, depth — with the arithmetic shown below. Treat the cable ODs and the duct as worked-example assumptions and swap in your own numbers before you cut steel.
Terminals. Differential: 32 signal terminals plus one shield-bar position = 33 positions x 0.2 in [5.08 mm] pitch = 168 mm [6.6 in]; add 25 mm [1 in] for end anchors, separators and labelling and plan 193 mm [7.6 in]. Single-ended on the same job: 18 x 5.08 mm = 91 mm [3.6 in], or 116 mm [4.6 in] with fittings. The backplate and DIN rail layout guide covers rail spacing around ducts and devices.
Duct. Assume a 25 x 40 mm duct with about 1000 mm² [1.55 in²] of interior section, and read the true interior from your duct's data. The fill cap this site uses is 50 % of that interior — the value NFPA 79-2012 section 13.5.2 sets for percentage fill of ducts, because round cables leave air between them. Usable: 500 mm². Two 8-pair cables of 12 mm OD are 2 x π/4 x 12² = 2 x 113 = 226 mm², 23 % of the duct. Single-ended needs one 12 mm cable at 113 mm², 11 %. Both fit the small duct; the rail and the second gland are what grow the box.
Glands. Pick an M20 gland whose printed insert seals your 12 mm cable OD; typical M20 inserts cover about 4-13 mm. Differential takes two entries, single-ended one, and both want factory cutouts rather than field holes.
Depth. A 12 mm instrument cable typically asks 6-8 times its OD in bend radius, so keep about 4 in [100 mm] of clear depth between the gland plate and the terminal rail. The nine stainless junction box sizes each list their panel, DIN capacity and depth; compare 193 mm against them, and instrument junction box selection steps the same count for field boxes.
Where should the cable shield be terminated?
Land every shield once, at the panel end: pair shields and the overall shield go to a shield bar or shield terminals bonded to the mounting plate, and the field end stays insulated and taped back. The bar belongs to the enclosure bonding scheme, not to the power ground bus; grounding and bonding in the enclosure covers the plate-to-door bonding that keeps it quiet. Shields are the third system on your rail after signals and commons, so give the bar its own labelled row.
When a drive shares the cabinet, clamp the cable shield 360 degrees at the gland plate, keep 6 in [150 mm] between the analog duct and the drive's output cable, and cross at right angles where you cannot run apart. VFD speed signal wiring shows the same discipline on a live speed loop, and configuring encoder cable shields and spare conductors goes deeper on pairing shields with spares. Open the disconnect and confirm the field side is dead before you re-terminate: a remote 24 V loop supply energizes the transmitters even with the panel off.
What should the enclosure order say?
Put the numbers on the drawing: wiring mode per channel, terminal count, rail length, duct size, gland holes and the shield bar, with 6 in [150 mm] of separation from power wiring marked on the layout. The box follows the count.
| Line on the order | Single-ended, 16 channels | Differential, 16 channels |
|---|---|---|
| Field cable | 1 x 18-conductor, 12 mm OD | 2 x 8-pair, 12 mm OD each |
| Gland holes | 1 x M20 | 2 x M20 |
| DIN rail to reserve | 116 mm [4.6 in] + 10 % spare | 193 mm [7.6 in] + 10 % spare |
| Shield landing | 1 shield terminal | 1 shield bar, 17 ends |
| Duct runs | 1 | 1-2 |
Stainless junction boxes are rated NEMA 4X / IP66 by the manufacturer and not UL listed, and every size lists the DIN capacity you compare against 193 mm. On custom stainless cutouts you set the material, the width, height and depth, and every opening, and the box is delivered in 10 business days counted from your approval of the drawing — the cutouts and glands guide lists the hole sizes that match standard fittings.
The decision by case: one panel supply, one reference, a tight terminal budget — single-ended with the returns split across two or three commons. Sensors on their own supplies, long runs beside power, or a drive in the same cabinet — differential, ordered as the 32-terminal card, with the box sized to 193 mm of rail.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a differential current input read a 4-20 mA loop?
Yes. The loop stays one series path through supply, transmitter and input; differential only changes where the measurement lands. It works for both a 2-wire loop-powered transmitter and a 4-wire transmitter on its own supply, but the 4-wire case is where you check the common-mode limit, because both conductors can sit well above panel ground. Differential wiring adds no loop voltage.
How many field wires does a 16-channel analog card need?
17 single-ended (16 signals plus one shared common) against 32 differential (one pair per channel), plus shields — and the count scales fast: a 32-channel card is 33 conductors single-ended against 64 differential, which is usually the point to split the field side into a remote junction box. Fix the mode before you size rail, duct and glands.
Why do single-ended readings shift when every loop runs at 20 mA?
The returns share one conductor. Sixteen loops at 20 mA push 0.32 A through it, and 20 m of 1.0 mm² copper is about 0.34 Ω, so the common lifts 0.11 V, which is 1.1 % of a 0-10 V span on every channel sharing it. Split the returns across two or three common terminals, or double the common's cross-section to halve the lift to 0.05 V.
Is a differential analog input isolated from ground?
No. Differential says where the channel measures; isolation says what it is galvanically separated from, and every isolated input is differential but not the reverse. Look for two separate figures on the datasheet: channel-to-ground and channel-to-channel. A card isolated to ground but with a shared reference between channels still lets two transmitters on separate supplies fight, and that channel-to-channel figure is the one field wiring depends on.
Where do cable shields land in the enclosure?
Once, at the panel end. Pair shields and the overall shield land on a shield bar or shield terminals bonded to the mounting plate, and the field end stays insulated. With a drive in the cabinet, add a 360-degree clamp at the gland plate and keep 6 in [150 mm] between the analog duct and the drive's output cable.