Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

One outdoor box for 120 V and 240 V outlets: how to build it

Yes — one stainless pedestal box holds both, fed from the 10/3 UF-B: a two-pole feeder, two 20 A branch breakers, a barrier and labeled faceplates. Keep 24 in [600 mm] of cover on the buried cable. A 20 A feeder runs an 11 A pump plus a 5 A charger exactly at its 16 A limit, so take 30 A for headroom.

NEMA4 Enclosure engineering team · Published November 14, 2026 · 8 min read

Yes, and the build is simpler than the panel hunt suggests: one outdoor pedestal box carrying a 20 A, 120 V GFCI receptacle and a 20 A, 240 V twist-lock, both fed from a 10/3 UF-B run. The NEC allows power circuits of different voltages in one enclosure when every conductor's insulation covers the highest voltage present, and 600 V cable against this box clears that with room to spare. What you order is a stainless box with factory cutouts, a barrier, a breaker compartment and two weatherproof covers. Rate it Type 4X where spray or a hose can reach it — ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed. Below is the split, the feeder arithmetic and the drawing to send.

Can one outdoor box hold both a 120 V and a 240 V outlet?

Yes, when the conductors meet one condition and you mark what each receptacle delivers: the NEC lets power circuits up to 1,000 V share an enclosure when every conductor's insulation is rated for the highest circuit voltage in that box.

The 10/3 UF-B meets it already. Its insulation is rated 600 V, the highest voltage present is the 240 V circuit, and that leaves a 2.5-times margin. The mixing question closes on insulation ratings, not on the two receptacles sharing a box.

Make the split visible to the next person. A barrier between the breaker section and the receptacle section keeps the two terminations apart. Faceplate labels naming the voltage on each device say what it delivers before anyone plugs in. The enclosure carries its type number for the location. NEC 110.28 requires that marking on enclosures for the locations its table lists, and in US installations an IP code alone will not satisfy it. Where the code lists the types shows the pairing, and the mixed-voltage junction box checklist is the door-open walk-through of a box like this.

What rating should the enclosure carry outdoors?

Type 3R is the floor for rain and sleet; take Type 4X / IP66 once a hose, a lawn sprinkler or lake spray can reach the box, and beside a lake that is the normal case.

3R sheds rain and drains the bottom; 4X adds hose-directed water and corrosion resistance, so boat splash and washdown sites get 4X. The material follows the water: 304 stainless inland, 316L where the lake is brackish or salt air reaches the post. The 3R versus 4 comparison sets out the test differences behind the two numbers.

The assembly runs at its weakest part, so the covers and the cable entry set the real rating. On a 3R build, a 3 mm [1/8 in] weep at the low point is the classic field drain: NEC 314.15 permits drainage openings of 3 mm to 6 mm [1/8 to 1/4 in] in boxes and conduit bodies listed for damp or wet locations. On a 4X box, keep the bottom sealed — one field-drilled weep drops the assembly back to 3R.

How do you split one 10/3 UF-B into two circuits?

Land the black and red on a small two-pole breaker or fused disconnect in the pedestal, then take one pole with the white for the GFCI receptacle and both poles for the twist-lock.

The 10/3 is already the right shape — a multiwire feed of two hots, one neutral and one ground. White lands on an isolated neutral terminal and the bare conductor on the ground bus, so load current stays off the enclosure metal; the grounding and bonding guide covers those terminations. Downstream of the main, a 20 A single-pole breaker feeds the GFCI branch and a 20 A two-pole feeds the twist-lock.

Tie the two branches so they switch off together — a handle-tie or a factory two-pole — so opening one leaves the shared neutral carrying nothing from the other. Each receptacle then sits behind its own overcurrent device, which is what makes one box behave like the two circuits it is.

Does the 240 V outlet need GFCI protection too?

Give the whole pedestal a 2-pole GFCI breaker and the question closes: one device trips at 4 to 6 mA on either leg, watches the twist-lock and everything downstream, and resets at the post instead of at the house panel.

A GFCI receptacle guards only its own branch; it has no way to watch the higher-voltage circuit, so that side takes its protection at the breaker. Recent NEC editions extend outdoor GFCI to 250 V receptacles, and the edition your inspector enforces sets the details — a 2-pole GFCI breaker satisfies either answer. Beside a lake, with damp cord ends and wet grass, that trip level earns its keep.

Plan the covers with the protection. Any receptacle that runs with a cord attached — a battery tender, a pump — needs a while-in-use cover, and the single-outdoor-outlet cover article shows what that buys you. The single-outlet version of this whole build is in turning an outdoor light junction box into a GFCI outlet.

How much load can the feeder carry with both outlets in use?

Add the loads leg by leg, because one hot leg carries the twist-lock load plus the GFCI branch load: with an 11 A pump and a 5 A charger, that leg sits at 16 A — the exact continuous limit of a 20 A breaker.

Treat 11 A and 5 A as the worked example's stand-ins, an 11 A pump nameplate and a 5 A battery tender, and put your own numbers in their place:

  • The pump draws 11 A at 240 V across L1 and L2.
  • The tender draws 5 A at 120 V from L1 to neutral.
  • L1 carries 11 + 5 = 16 A; L2 carries 11 A; the neutral carries the difference, 16 - 11 = 5 A.
  • A load counts as continuous past 3 hours, and a breaker holds 80% of that: 20 x 0.8 = 16 A. The feeder is at its line, with nothing left over.
  • Swap the tender for a 12 A wet-vac and L1 sees 11 + 12 = 23 A; the feeder trips mid-job.
  • The fix is a 30 A two-pole feeder on the 10/3 — 10 AWG copper is 35 A at 75 C — with the 20 A branch breakers at the pedestal so each receptacle stays a 20 A circuit.
What the pedestal runs Feeder breaker The arithmetic
1.5 hp pump, 9 A, plus a 5 A charger 20 A two-pole 9 + 5 = 14 A on one leg, under the 16 A limit
2 hp pump, 11 A, plus a 5 A charger 30 A two-pole 11 + 5 = 16 A sits exactly at the 20 A limit
2 hp pump, 11 A, plus a 12 A wet-vac 30 A two-pole 11 + 12 = 23 A clears a 20 A feeder outright

What size box do you need, and how does it mount?

For two receptacles, two branch breakers and the splices, a box around 12 x 10 x 6 in [305 x 255 x 150 mm] is comfortable, and depth decides it: a GFCI device behind a while-in-use cover wants close to 3 in [75 mm].

Check fill with the standard unit counts: 2.5 cu in per 10 AWG conductor, doubled for each device yoke. Four feeder conductors — two hots, the neutral, the ground counted once — total 10 cu in. Two yokes add 10 cu in, and four 12 AWG pigtails add 9 cu in, so about 29 cu in is spoken for, and a pedestal this size has several hundred. NEC 312.8 caps how much of an enclosure housing overcurrent devices may fill with conductors and splices, so land the splices in the receptacle section and keep the breaker section for straight runs. Bending space, set by wire size under NEC 312.6, is a non-event at 10 AWG — the cover depth outranks it. The full walk-through is in how to size an electrical enclosure.

Mount on a 4 x 4 in [100 x 100 mm] treated post or a concrete pier with stainless fasteners, and set the breaker handles near 48 in [1.2 m] — well under the 2.0 m [6 ft 7 in] ceiling NEC 240.24(A) sets for the highest handle. Leave 3 ft [0.9 m] of clear standing room in front per NEC 110.26(A); the system is 120 V to ground, the 0-to-150 V case. Heat never sizes this box: the loads pass through it rather than live in it.

How does the buried cable get into the pedestal?

Come up through the bottom on a sealed hub, and give the run its cover: UF-B direct-buried wants 24 in [600 mm] of cover, and the same cable inside PVC conduit drops that to 18 in [450 mm].

Bottom entry leaves the walls and the gasket line unbroken, which is how the box keeps its rating — every field-added hole becomes the weakest part. Sleeve the UF-B up inside the post in PVC with a bushed entry, or land conduit on a hub sized for it; the cutouts and glands guide covers the hardware. Probe the existing trench before you set the post: a section sitting shallower than 24 in [600 mm] gets conduit or more cover, and tracer tape in the backfill marks the run for the next dig. The fusing view of a buried distribution box is in underground junction box power distribution.

What should the order say?

Send a drawing with the material, the three outside dimensions, every cutout diameter and the entry hub, and the box is delivered in 10 business days — counted from your approval of that drawing, anywhere in the world.

Pick the two device covers before the drawing and order the cutouts to their templates: a while-in-use cover on the GFCI face, a weatherproof spring-door cover on the twist-lock. An RV panel answers a different mix — a 30 A RV receptacle beside a 20 A GFCI, mostly surface-mount for overhead feed — so it never carried a 240 V slot. The spec for a custom body then reads:

Line on the drawing What to write
Material 304 stainless, #4 finish; 316L for brackish water or salt air
Size About 12 x 10 x 6 in [305 x 255 x 150 mm] for two devices, two breakers, splices
Rating NEMA 4X / IP66, manufacturer rating
Device cutouts One to the while-in-use cover template, one to the twist-lock cover template
Interior Barrier splitting breaker section from receptacle section; DIN rail; ground and neutral bars
Cable entry Bottom hub for 3/4 in [20 mm] conduit, or a gland for direct 10/3 UF-B
Mounting Tabs or feet for a 4 x 4 in [100 x 100 mm] post

Custom enclosures take the material, the width, height and depth and every cutout, built from one piece; the outdoor bodies are on the outdoor enclosures page. Ours are manufacturer-rated, not UL listed. If the inspector wants a listed assembly, buy the listed pedestal and keep this layout for what goes inside it.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Do the 120 V and 240 V circuits have to go in separate boxes?

No. The NEC allows both in one enclosure when every conductor's insulation covers the highest voltage present — 600 V UF-B clears it with a 2.5-times margin. Put a barrier between the two sections and label each faceplate with its voltage, so anyone opening the door reads what each device delivers before plugging in.

Will a 20 A feeder run a 2 hp pump and a 120 V load together?

Barely. An 11 A pump plus a 5 A charger puts 16 A on one hot leg — the exact 80% continuous limit of a 20 A breaker (20 x 0.8 = 16). Add a 12 A wet-vac and that leg sees 23 A and trips. A 30 A two-pole feeder on the 10 AWG copper, with 20 A branches at the pedestal, covers it.

Can an RV panel replace this pedestal?

Not for this mix. RV panels pair a 30 A RV receptacle with a 20 A GFCI, or come as 50/30/20 A combinations, mostly surface-mount for overhead feed — none has a 240 V twist-lock slot. A box built to your cutout list is delivered in 10 business days from drawing approval; take the listed pedestal only if the inspector requires a listed assembly.

Does the 240 V twist-lock need GFCI protection too?

Yes, and the breaker is where it lives: a 2-pole GFCI device trips at 4 to 6 mA on either leg and covers the twist-lock circuit and everything downstream. A GFCI receptacle guards only its own 120 V branch and cannot watch the higher-voltage load. Reset it at the pedestal and you save the walk to the house panel.

How deep does the UF-B trench have to be?

24 in [600 mm] of cover direct-buried, and 18 in [450 mm] once the cable runs in PVC conduit. Lay tracer tape in the backfill so the run is marked for the next dig.

Is Type 3R enough, or do I need 4X beside a lake?

Take 4X. 3R sheds rain; lake spray, a hose or a lawn sprinkler is hose-directed water, which is 4X territory. NEC 110.28 has the type marked on the enclosure for the location, and an IP code alone will not satisfy that table. On a 4X box keep every entry sealed — one field-drilled 3 mm weep drops the assembly to 3R.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

Outdoor enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides