Short answer: choose the disconnect by where the circuit begins, not by the 15 W load. At 120 V that load draws 0.125 A, so almost any listed switch is big enough electrically. On a utility pole you are opening the service: run the transformer secondary at 240 V (two hot legs and a neutral) through the meter into a disconnect marked suitable for use as service equipment, and give the tap its own single-pole breaker in a small NEMA 3R load center. On an equipment pole fed by an already protected circuit, an outdoor-rated switch in a NEMA 3R or 4X enclosure does the job. The sections below give both decisions, the enclosure types and materials that survive a pole, and the height and access numbers an inspector measures.
Utility pole or equipment pole: decide this first
Name the source before you pick any hardware. If the conductors at the pole come from the utility transformer secondary, they are service conductors at 240 V: two hot legs and a neutral, passing through the meter. The device that opens that pair is service equipment. It must carry the marking suitable for use as service equipment (SUSE), which comes from a listing evaluation of the switching device itself. The service disconnect opens the entire service, both hot legs together; a general-duty switch, however weatherproof, is not that device.
The two jobs stay separate: the service disconnect does not protect the tap. The tap needs its own single-pole breaker, and the cabinet that carries both is a small load center in NEMA 3R, with a 240 V two-pole main above and one single-pole breaker below for the branch circuit. Keep the disconnect at or near the meter, because the run between them is unprotected service conductor; the 6 ft distance from the meter is where long runs start drawing questions.
If the pole sits downstream of an existing installation, the circuit arrives already protected, and your local switch only isolates the load for service. Select it for the protected circuit's rating and spend the rest of the effort on the enclosure. Tapping power for an outdoor floodlight: which circuit and box walks through choosing the circuit and the box, and when a 120 V enclosure needs its own disconnect covers the second-disconnect question.
| Utility service pole | Equipment pole, downstream | |
|---|---|---|
| Conductors at the cabinet | 240 V service: two hot legs and a neutral, via the meter | Branch circuit, protected upstream |
| Disconnect | SUSE-marked, opens the whole service | Rated for the protected circuit |
| Branch protection | Separate single-pole breaker in a NEMA 3R load center | Already upstream |
| Enclosure | NEMA 3R load-center cabinet | NEMA 3R; Type 4X near salt or spray |
Sizing the 15 W tap
Inputs:
- Load: 15 W at 120 VAC, the nameplate values for this pole instrument.
- Power factor: 1.0 assumed for a small resistive or electronic load; replace it with the nameplate current when the nameplate prints one.
- Baseline circuit: 14 AWG copper on a 15 A single-pole breaker, the standard branch circuit in North America.
The rule in words: current in amperes equals power in watts divided by voltage in volts.
15 W ÷ 120 V = 0.125 A.
The load draws 0.125 A, which sits 120 times below the 15 A breaker (15 A ÷ 0.125 A = 120). Build the tap as that standard 15 A circuit on 14 AWG copper: the breaker protects the conductors, and a 15 W device cannot challenge it. The point where you step above the standard circuit is around 12 A of continuous load, 96 times what this device draws (12 A ÷ 0.125 A = 96). So the 15 W figure decides nothing about the disconnect; the same tap breaker serves both cases above. The service main above it is chosen for the service conductors and the utility's metering arrangement — 100 A and 200 A are the typical small-service sizes — never for this load.
Give the breaker and disconnect a short-circuit current rating at or above what the utility can deliver at the pole; 10 kA is the common interrupting rating for small 120/240 V breakers. Disconnect sizing by load, feeder and SCCR works the full sizing chain for a control cabinet.
The enclosure type: 3R is the floor on a pole
Outdoors, Type 3R is the baseline: it stands up to rain, sleet and snow, and outdoor load centers come built to it. Type 4 adds hose-directed water, so order it when water can arrive as a stream — washdown hoses, irrigation sprayers, driving coastal rain. Type 4X adds corrosion resistance on top of Type 4; the UL 50E evaluation behind it (Table 5-1D) includes another 200 hours of salt spray against an AISI 304 stainless specimen, alongside Types 3X, 3RX, 3SX and 6P.
- Dry inland pole, rain and snow only: Type 3R.
- Spray, hose or driving rain anywhere near: Type 4.
- Salt air, brine, fertilizer or chemical drift: Type 4X, and 316L stainless for the cabinet.
Two rating notes matter on a pole. In US installations, NEC 110.28 points at the enclosure type: its Table 110.28 lists the type that suits each location, and an IP code cannot stand in for that type number. And the lowest-rated part sets the assembly: an unrated hub, breather or drain drops the cabinet to that part's rating, so every penetration takes a fitting rated for the Type. The NEMA 3R vs NEMA 4 guide details the water tests, and the NEMA 4X vs IP66 guide shows where 4X earns its mark.
A weather rating answers water and sun, not flammable atmospheres. Poles near fuel storage or solvent areas need classified-location gear built to NEMA 7 or 9, which we do not build; NEMA 7 vs NEMA 4X: hazard rating is not weatherproof explains that difference.
Material, sun and weight
Pick the material from the atmosphere. 304 stainless suits inland poles; 316L earns its keep near salt air, brine and chlorides. Stainless ignores ultraviolet light, so a bare stainless cabinet neither fades nor chalks after seasons of direct sun. Powder-coated carbon steel is the budget choice inland, and its finish chalks over the years; polycarbonate needs a UV-stabilized grade before it sees open sun at all.
Weight is a real constraint on a pole, and aluminum cabinets cut the hanging load where the pole or the climb argues for it. Our own 304 and 316L wall-mount boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed — the right housing for the downstream-equipment case, while the service cabinet and its devices come as listed equipment from the load-center maker.
Humid climates add one more item: condensation, which no water rating covers, beats rain as the water you will actually see inside. A breather with a small heater keeps a sealed cabinet dry; the outdoor electrical enclosures guide sizes both and covers the sun as the largest heat load on an outdoor box.
Height, access and working space
Mount the cabinet to the numbers the code prints. NEC 240.24(A) requires overcurrent devices to be readily accessible, with the center of the grip of the operating handle, in its highest position, no more than 2.0 m (6 ft 7 in) above the floor or working platform. On a cabinet worked from a ladder or bucket, measure from the platform you stand on: a highest handle at 1.8 m clears the limit, one at 2.1 m fails it.
NEC 110.26(A) sets the working space in front of equipment likely to be serviced while energized: at least 3 ft (900 mm) deep for 0-150 V to ground in Condition 1, at least 30 in wide or the equipment width, and room for the door to open at least 90 degrees. Face the breaker side toward your access route and keep that space clear.
The metering position belongs to the utility. They set the socket and the point of attachment, so agree the cabinet's finished position with them before you drill the pole.
Entries, bonding and the live line side
Band or bolt through the back with stainless hardware, and bring every conduit in from the bottom or the rear so water sheds instead of pooling on a hub. Pole mounting a weatherproof enclosure without leaks covers brackets and standoffs, and getting power into a pole-mounted enclosure covers the entry choices.
Seal the penetrations and let the cabinet drain. Type 3R and Type 4 cabinets manage water by design, and NEC 314.15 permits drainage openings of 3 mm (1/8 in) to 6 mm (1/4 in) in boxes listed for damp or wet locations. At bonding points, NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces, so scrape the coating at every bond on a painted cabinet or use fittings designed to bite through. Size the equipment grounding conductor from the overcurrent device ahead of it using NEC Table 250.122, and land grounds on the ground bus, not the neutral; the grounding and bonding guide shows the full fault path.
Once the conductors land, remember what stays hot: the line side of the service disconnect is live with the switch off, so lock out and test for absence of voltage before touching a lug. Why the line side of a separate disconnect stays live explains that arrangement.
What to put on the order
| Item | Utility service pole | Equipment pole, downstream |
|---|---|---|
| Disconnect | SUSE-marked, two-pole, opens the whole 240 V service | Outdoor-rated switch rated for the protected circuit |
| Main | Sized to the service conductors; 100 A and 200 A are the typical small sizes | None at this pole |
| Branch protection | Single-pole 15 A breaker on 14 AWG copper for the 0.125 A tap | Upstream; record its rating |
| Fault rating | 10 kA or more, matched to the utility's available fault current | Matched to the protected circuit |
| Enclosure | NEMA 3R load-center cabinet; disconnect near the meter | Type 3R; Type 4X near salt or spray |
| Material | 304 stainless inland, 316L near salt | Same, or aluminum to cut hanging weight |
| Height and access | Handles at or below 2.0 m (6 ft 7 in) from the platform; 3 ft (900 mm) deep and 30 in wide working space | Same numbers |
The decision, case by case. Utility service pole: a SUSE-marked two-pole disconnect at the meter, a NEMA 3R load center with a single-pole 15 A breaker feeding the 0.125 A tap on 14 AWG, handles within 2.0 m of the platform, working space 3 ft deep by 30 in wide. Equipment pole: an outdoor-rated switch in a Type 3R cabinet — Type 4X in 316L where salt or spray reaches — with protection left upstream and the switch chosen for that circuit's rating. When you order a custom cabinet, specify bottom entries, rated fittings at every penetration and the drain the Type expects; 304 or 316L boxes in your dimensions are delivered in 10 business days, counted from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is there a one-box arrangement for the utility pole?
Yes: meter-main load centers put the meter socket, the SUSE-marked main and the branch breakers in one NEMA 3R cabinet, so the tap's single-pole breaker sits directly beside the service disconnect. The main is sized to the service, not to the load; 100 A and 200 A are the typical small-service sizes. Confirm the utility accepts meter-main gear at your site before ordering, because some utilities want their own socket.
Does a ground rod at the pole replace the equipment grounding conductor?
A ground rod next to a pole-mounted enclosure is an auxiliary electrode under NEC 250.54: you may connect it to the equipment grounding conductor, and the conductor itself stays in the circuit. Size that conductor from the overcurrent device ahead of it using NEC Table 250.122, and land it on the ground bus. The rod helps with lightning and surge currents; fault current clears through the conductor.
Does the NEMA 4X rating make a switch suitable as service equipment?
Service suitability is a marking on the switching device, not the box. Pair a SUSE-marked breaker with the NEMA 3R load center for the utility case, and keep Type 4X wall-mount enclosures for the downstream-equipment case; our 304 and 316L boxes are rated NEMA 4X / IP66 by the manufacturer and are not UL listed. Enclosure type answers water, ice and corrosion; the SUSE evaluation answers the service connection.
What breaker size protects the 15 W tap?
A 15 A single-pole breaker on 14 AWG copper is the standard answer. The 0.125 A load sits 120 times below the trip, and the 12 A continuous ceiling on that breaker (80% of 15 A) sits 96 times above the load. If the equipment nameplate states a current or an inrush, check the breaker's time-current curve against it; a 15 W device rarely moves the needle.
Can I switch only one hot leg of the 240 V service?
Open all ungrounded service conductors together: a 240 V split service takes a two-pole main, and the tap gets its own single-pole breaker below it. A single-pole switch in the 240 V pair leaves one hot leg live at the pole, and even the two-pole main leaves the line-side lugs hot when it is off, so lock out and test before work.
Does the enclosure type cover sun damage?
Water, ice and corrosion are what the type rating tests; the 200 hours of salt spray behind Type 4X says nothing about ultraviolet exposure. Pick UV resistance from the material instead: 304 and 316L stainless ignore UV, powder-coated steel chalks after seasons in direct sun, and only UV-stabilized polycarbonate suits an open-sun pole.





