Slide each device toward the centre of the box and drive a 6-32 machine screw through the round holes at the ends of the strap into the two inner 6-32 holes; 1 in [25 mm] screws usually seat on the first try. The bent tabs on a decorator strap look like mounting points, but they are drywall spacers, so snap them off and forget them. The two outer holes in the box belong to the weatherproof in-use cover, which bolts on last over both devices. The box itself is right for the job: a 2-gang, 32 cu in weatherproof PVC device box with a 3/4 in [19 mm] hub takes an outlet and a switch with room to spare. What follows is the whole job, from open box to closed cover.
Why won't the outlet line up in a 2-gang weatherproof box?
Because the box is drilled for devices sitting inboard of centre, not centred between the hole pairs: ganged straps overlap at the middle, so their screw holes line up with the two inner bosses and with nothing else. The bosses are the raised, threaded posts the 6-32 screws run into.
Hold a decorator device up the way you would to a single-gang box, centred on its half of the opening, and its strap holes land in the gaps between bosses. That is the trap, and it catches most first ganged weatherproof installs. Two devices share the middle of the box: each strap shifts toward the centre line until the two straps meet, and the box maker molds the bosses to match that position. The inner pair sits closer together than a single-gang layout suggests, which is why the spacing looks tight when you first hold the parts up. The outer holes have a separate job: they sit where the in-use cover's screws want them, and nothing about their spacing matches a device strap.
Which holes in the box hold the devices?
The two inner ones: the pair of 6-32 bosses nearest the centre of the box takes the device screws, and the outer pair is there for the in-use cover, so nothing shares a screw.
On this style of 2-gang PVC box, each strap lands on the inner boss on its side of the centre line, and the neighbouring device takes the mirror-image one. That is the arrangement the box was molded for, and it holds a decorator device square, because the strap hole and the boss are made for each other and the cover later captures everything from outside. The threads are 6-32, the same machine thread a metal device box uses, so the screws already in your pouch fit. Slide a device outboard toward the outer holes and the mismatch shows at once, since those bosses are spaced for the cover gasket, not for a strap.
What are the tabs on the device strap for?
Drywall, nothing else: the bent ears on a decorator strap are made to lie on the face of unfinished board and hold the device at finished-wall depth while the room is completed, and a weatherproof box has no use for them.
The ears carry holes, which is what makes them look like mounting hardware. Inside a wall those holes see no screw either; the ears only set depth against the board face. Break them off before you offer the device to the box. Grip each ear with pliers and bend it back and forth at the score line; one or two flexes and it snaps clean. Left on, an ear can stand the strap off its boss, catch the cover gasket, or crowd the conductor fold behind the device. Three good reasons for a five-second job.
What screws do the bosses take?
The same 6-32 machine screws a metal box takes, and length is the only choice left: hardware runs 6-32 in 1/2 in [13 mm], 5/8 in [16 mm] and 1 in [25 mm], and a weatherproof box usually wants the 1 in.
The bosses sit deep in the box, behind the cover's gasket flange, so a screw crosses more distance here than in a flush wall box. Start with 1 in; if it bottoms in the boss or stands the strap off, drop to 5/8 in. Drive until the strap lies flat on its boss and stop there, because past that point you are chewing plastic thread rather than clamping anything. Electrician screw kits sell 6-32 flat- and oval-head machine screws together, which saves sorting at the bench. In salt air or a permanently wet spot, stainless 6-32, sold in 5/8 in packs of 50, keeps the heads from seizing to the cover screws years later.
How do you mount the outlet and the switch, step by step?
Prove the circuit dead first, then land the ground on the box's ground screw, terminate both devices, break the tabs, drive 1 in 6-32 screws through both straps into the inner bosses, and bolt the in-use cover to the outer pair.
If the box itself is still loose on the wall, fix that before the devices go in; mounting a weatherproof box without losing its rating covers the fasteners and the wall-side seal.
- Kill the feeder and prove absence of voltage at the box with a tester you have just tried on a live source, since outdoor circuits get fed from surprising places.
- Run the conductors in through the 3/4 in hub and its conduit. Close any second, unused hub opening with a listed plug made for that hub; sealing unused conduit holes in an outdoor metal box runs through the same logic on the metal side.
- Land the equipment grounding conductor on the box's ground screw, then pigtail from that screw to the ground terminal of each device. A PVC box gives you no metal to bond through, so the wire carries the whole job, and enclosure grounding and bonding lays out the sizing.
- Terminate hot and neutral on the GFCI's LINE terminals and the switch leg on the switch. A GFCI body is deeper than a plain receptacle, so fold its conductors in the space behind it rather than beside the switch.
- Break the drywall ears off both straps.
- Slide each device toward the centre until a strap hole sits over the inner boss on its side, start a 1 in 6-32 screw in each, and leave both a turn loose until the two devices sit square to each other.
- Tighten both until the straps lie flat, dress the conductors away from the cover gasket, seat the cover, and drive its screws into the two outer holes.
Does a 32 cu in box have room for that wiring?
Yes, with margin: counting the NEC way, at 2.25 cu in per 12 AWG conductor, the grounding conductors once, and each device double, three current-carrying conductors, one ground and two devices in a 32 cu in box total 18.0 cu in, leaving 14.0 cu in spare.
The count for one 20 A outdoor circuit in 12 AWG copper:
- three current-carrying conductors, the feed hot, the neutral and the switched leg: 3 x 2.25 cu in = 6.75 cu in
- equipment grounding conductor, counted once: 2.25 cu in
- two devices, each worth two conductor volumes: 2 x 2 x 2.25 cu in = 9.00 cu in
- total 18.00 cu in against the box's 32 cu in
That leaves 14.00 cu in, about six more 12 AWG conductors (6 x 2.25 = 13.5 cu in). The conduit entry through the hub adds nothing to the count. Move the circuit to 10 AWG at 2.50 cu in per conductor and the same arrangement rises to 20.00 cu in, still inside. If a future splice lands in this box, every added conductor costs its 2.25 cu in, and six of them use up the whole margin. That number is what to watch, not the device count.
Where do the in-use cover screws go?
In the two outer holes: the weatherproof-while-in-use cover mounts on the outer pair while the devices hold the inner pair, so cover and devices each keep their own screws and neither loosens the other.
The NEC's outdoor rule for 15 and 20 A receptacles calls for an enclosure that stays weatherproof with a plug inserted, which means the in-use, or bubble, cover, listed for wet locations. Bolt it down over a clean, even gasket and it also shields the assembly from water running down the wall. A weatherproof in-use cover for a single outdoor outlet shows the single-gang version of the same hardware. If your starting point is an old outdoor light box instead of a fresh device box, turning an outdoor light junction box into a GFCI outlet covers that path end to end.
How do you check the job when it's done?
Five checks prove it: both devices sit square with snug screws, the cover gasket shows an even print all round, a plug latches with the cover closed, the GFCI trips and resets from its own buttons, and the hub and any plugged opening stay dry.
- Square and snug: each strap lies flat on its boss, screw heads flush, and nothing rocks when you press a plug home.
- Gasket print: latch the cover, open it again and read the compression mark. An unbroken ring means it sealed; a gap means re-seat it.
- Plug fit: a landscape timer or transformer plug latches and stays put with the cover closed and latched.
- GFCI function: with power on, press TEST and confirm the receptacle is dead, then RESET and confirm it returns.
- Weather-tight behind: the hub ring is tight on the conduit, and every unused hub opening carries its listed plug.
When does this spot want a stainless box instead?
When the location is hosed down daily or sits in salt air: PVC weathers there, and a stainless junction box rated NEMA 4X / IP66 by the manufacturer (not UL listed) keeps splices and small devices dry where washdown and chlorides are routine.
Stainless junction boxes come in wall-mount sizes for splices, terminal blocks and a few devices, built to your cutouts and delivered in 10 business days. The outdoor enclosures guide covers the sun load, the condensation risk and the 304-versus-316L choice for the exact spot. The receptacle itself still wants its listed in-use cover wherever a plug stays in outdoors, since the stainless box protects what lands inside it and the cover protects the outlet face.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can you use the wallplate screw hole in the strap as a mounting hole?
It will hold nothing. The small threaded hole in the middle of many straps is for the wallplate screw, and there is no 6-32 boss behind it in a weatherproof box, so the device would hang loose on one fastener. Mount only through the round holes at the two ends of the strap.
Do you have to break the tabs off before mounting the devices?
Yes. The bent ears exist to rest on drywall and set device depth while a wall is being finished; in a weatherproof box they only stand the strap off its boss or catch the cover gasket. Grip each ear with pliers and bend it at the score line. One or two flexes snaps it clean.
What screw length works in a 2-gang weatherproof PVC box?
Start at 1 in [25 mm]. Hardware runs 6-32 machine screws in 1/2, 5/8 and 1 in lengths, and the bosses of a weatherproof box sit well back, so the long one usually seats the strap flat. Drop to 5/8 in [16 mm] if the 1 in bottoms out, and use stainless 6-32 where the box lives in salt air.
Will a GFCI and a switch fit in one 32 cu in box?
Yes, with margin. Counting the NEC box-fill way for 12 AWG, at 2.25 cu in per conductor, grounds once and each device double, two devices, three current-carrying conductors and one ground total 18.0 cu in of the 32 cu in, leaving 14.0 cu in. The GFCI body is deeper than a plain receptacle, so fold its conductors behind the switch.