How to show terminal block symbols on a wiring diagram

Draw each DIN rail terminal as an open circle carrying a strip-and-position label: TB1:9 through TB1:14 names six terminals on strip 1. Use that same label in three coordinated drawings — schematic, terminal overview and panel layout — because rail adjacency says nothing about what is bridged. A 12-sensor strip works out to 36 labels on 12 triple-level terminals with two 12-way jumpers.

NEMA4 Enclosure engineering team · Published November 14, 2026 · 5 min read

Short answer: draw every DIN rail terminal as an open circle carrying a strip-and-position label — TB1:9 through TB1:14 names six terminals on strip 1 — and use that same label on three drawings: the schematic, the terminal overview and the panel layout. The circle comes from IEC 60617, and every major CAE package draws it this way; the label is what turns it into an address. The diagrams from your image search show few terminals because they are schematics, whose job is circuit operation, and a terminal changes nothing electrically. What you are documenting — which rail, which position, which cable — lives on the termination drawings, so build those and cross-reference all three.

Why your image search comes back empty

A schematic answers one question: which points share an electrical node. A feed-through terminal continues that node, so it shrinks to a small circle or drops out of an operating drawing entirely. That is deliberate, and nothing is wrong with your CAD or your rail.

Ownership changes the questions. You now want to know where the brown conductor from sensor 7 physically lands, on which side of which strip, and in which cable it arrived. Those answers belong to a termination drawing, not to the schematic — what belongs on the schematic and what belongs at the terminal layer is a split worth fixing before the first fault, not during one.

The circle and the label that does the work

IEC 60617 is the international symbol library for electrotechnical diagrams, written so one symbol serves schematics, terminal-connection diagrams and cable diagrams at whatever detail you need. Its terminal is the open circle. US-format drawings lean on ANSI/IEEE 315 for the same job with their own graphics; pick the set your shop already draws and stay inside it.

Two small marks get confused at print size. A junction dot says the conductors drawn through it connect — that is how multi-way connections are shown. An open circle says a physical termination exists here, one you can reach with a screwdriver. Label every circle with strip, then position: TB1:9 is strip 1, position 9. TB1:9 through TB1:14 is six consecutive positions. Packages punctuate the pair differently — colon, dot, dash — so print the legend once and hold it across every sheet you issue.

One label, three drawings

No single view carries function, termination and position without becoming unreadable, so run three coordinated drawings plus a cable schedule on bigger jobs.

Drawing What it carries What it leaves to the others
Schematic Circuit function, node membership, device cross-references Rail order and cable routes
Terminal overview Positions in rail order, every level, both connection sides, cable IDs, destinations, jumper bars Circuit function
Panel layout Which rail holds each strip, where strips, duct and devices sit Electrical continuity
Cable schedule Gland entry, cable type, core count, from-to Everything inside the box

Number the positions in rail order on the overview, and let the schematic follow function instead; a schematic drawn to imitate the rail reads badly and ages worse. The backplate and DIN rail layout guide covers where the strips and duct physically go on the plate. Give one strip one job — 24 V DC field devices on one, line-voltage loads on another — and the labels then carry that separation for you.

One housing, three circuits

Position count and circuit count are different numbers. A triple-level terminal stacks three connection levels into a housing about 5 to 6 mm [0.2 to 0.24 in] wide in terminal makers' data for the 2.5 mm² [14 AWG] class, and each level is its own node unless the maker bridges levels internally. The maker's internal connection diagram is the only honest source for that, so read it before you draw.

Suffix every level: TB1:5.1, TB1:5.2, TB1:5.3. On sensor terminals the mapping the datasheets use is level 1 to L+ (brown), level 2 to the signal (black), level 3 to 0 V (blue). While the datasheet is open, check wire range and current: a 2.5 mm² [14 AWG] class screw terminal commonly accepts 0.5 to 4 mm² [20 to 12 AWG] and is rated 24 A at 40 C ambient in the maker's IEC 60947-7-1 data, so a 0.5 mm² [20 AWG] sensor cable sits well inside it.

Jumpers are drawn, never implied

Adjacent housings are isolated mouldings until a jumper bar joins them, and a shared strip number proves nothing about continuity. Draw the bar as a horizontal line across the bridged positions on the overview, and name its span in text: "jumper TB1:1–TB1:8, L+".

Size the bar by the sum of its branches. A bar feeding ten 1 A solenoid coils carries 10 A, and that sum goes against the jumper's rated current on the same datasheet page as the terminal's rating. Sensor milliamps rarely matter; coils, heaters and valve banks do.

Twelve sensors on one strip: 36 labels, two jumpers

Inputs, all replaceable with your own values: twelve three-wire 24 V DC sensors at 30 mA each from the datasheet, 0.5 mm² [20 AWG] field cable, triple-level terminals 6 mm [0.24 in] wide per housing, strip named TB2. The rule: one terminal per sensor, level .1 to L+, .2 to signal, .3 to 0 V, with the L+ and 0 V levels bridged along the strip and the signal levels isolated.

The arithmetic:

  • Field conductors: 12 sensors × 3 wires = 36 terminations.
  • Housings: 36 terminations ÷ 3 levels = 12 terminals, TB2:1 through TB2:12 — counting points, not blocks, with the levels doing part of the work.
  • Labels: 12 positions × 3 levels = 36 designations, TB2:1.1 through TB2:12.3.
  • Rail length: 12 × 6 mm = 72 mm [2.8 in] before end brackets.
  • Jumper load: 12 × 30 mA = 0.36 A on each of two 12-way bars.

Decision: 0.36 A against a 24 A terminal rating leaves the electrics comfortable, so documentation quality drives the choices here. Draw both jumper bars across TB2:1.1–TB2:12.1 and TB2:1.3–TB2:12.3. Reserve 10 to 20 % spare positions per strip, the figure most control-panel specs ask for — two here, TB2:13 and TB2:14 with blank levels — which 72 mm of strip leaves room for on any cut rail length. Past about 20 positions a strip gets hard to trace and feed, so start TB3 on its own feed instead of stretching one strip across the box. For a box that is all terminals, the junction box terminal drawing and what it must show extends this same list to the field side.

From the overview to the enclosure order

The overview doubles as order data. Twelve field cables mean twelve gland entries, and their diameters and spacing follow the cutout, gland and window guide; the rails and cutouts themselves go into the enclosure builder as build options, so the box arrives drilled for the strip you documented.

Then hold the set together. When a bridge moves or a conductor lands on a new position, revise schematic, overview and layout under one revision number, because two of the three agreeing is how a fault gets chased to the wrong terminal. Land one conductor per label as printed — putting two wires on one terminal is a separate decision — and the panel will still match its paper years from now.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
6 × 6 × 4 in304 stainless6 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
8 × 6 × 4 in304 stainless8 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10 × 8 × 4 in304 stainless10 x 8 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Is there a standard symbol for a terminal block?

Yes. IEC 60617 collects the graphical symbols for electrotechnical diagrams, and its terminal is the open circle you see in CAE schematics; ANSI/IEEE 315 covers the equivalent US symbol set. The circle only says that a termination exists — the strip-and-position label beside it, TB1:9 for terminal 9 on strip 1, is what takes a technician to the right housing on the rail.

Why do wiring diagrams online show no terminal blocks?

Because those drawings are schematics, whose job is circuit function: which points sit on the same node. A terminal continues a node, so it shrinks to a circle or disappears, and operation-focused drawings leave it out on purpose. Termination detail lives on a separate terminal overview listing positions, levels, both cable sides and jumper bars. One view cannot carry function and routing at once, so draw both and cross-reference them.

How do you label a three-level terminal block?

Give each conductive level its own suffix: TB1:5.1, TB1:5.2 and TB1:5.3 for the three levels of one housing. Check the maker's internal connection diagram first, because some levels are bridged inside the housing and some stay isolated. One housing then carries up to three separate circuits, and the drawing still tells them apart.

Do neighbouring terminals connect to each other automatically?

Only through a jumper bar, and the overview has to draw it. Side-by-side housings are isolated mouldings until a bridge joins them. Size the bar by the sum of its branches: a 12-way jumper feeding twelve 30 mA sensors carries 0.36 A, far inside a 24 A terminal rating, while the same check on solenoid loads is what actually protects the strip.

How many spare terminals should the drawing reserve?

Figure 10 to 20 % spare positions per strip, the number most control-panel specs ask for: two spares on a 12-position strip, three on a 16. Number them on the overview with blank levels — TB2:13 and TB2:14 — so a later addition costs a jumper bar and a label, not a redrawn strip.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start a junction box from 6 × 6 × 4 inRequest a custom quote

Stainless junction boxes: sizes for this job