A dry-location set-screw connector will not do this job. In a wet location, both the flexible cable or conduit and the connector at the box must be listed for wet locations. Pick a wet-listed connector that matches the cable type and the knockout, enter the box from the bottom, and keep the water that finds its way into flex out of the enclosure.
Why a dry-location connector fails outdoors
Standard AC cable connectors are marked for dry locations. Their threads and clamp are bare metal against the box wall, with no gasket and no seal around the cable. Rain running down the flex sits in the fitting and wicks into the box.
The listing follows the location, not the conductors. A flex carrying only a bare equipment grounding conductor still needs wet-listed cable and a wet-listed connector if the run is in a wet location. The NEC treats a location exposed to rain as wet regardless of what the circuit carries, and an inspector will judge the installation by the markings on the products, not by what is inside them.
There is also a practical reason. Flexible metal conduit breathes: daily temperature swings push humid air in and pull it back out, and condensation forms inside the spiral. If the connector at the box does not manage that water, it ends up on your terminals.
What to use instead
Two paths work, depending on what you are running:
- Wet-rated flexible cable with a wet-listed connector. Jacketed MC cable listed for wet locations, often with a PVC or nylon overall jacket, is the common choice. Pair it with a connector listed for wet locations for that cable type; some are sold as deck or outdoor connectors for exactly this surface-mounted, exposed use.
- Liquid-tight flexible conduit with liquid-tight fittings. Liquid-tight flexible metal conduit with a wet-listed liquid-tight connector gives a sealed entry and better mechanical protection on an exposed wall.
Match three things before you buy: the connector to the cable type, the connector's thread to the knockout size, and the connector's clamping range to the cable's overall diameter. Jacketed and liquid-tight cables are thicker than bare flex, and a clamp that is too large will not seal. The same matching logic applies to cable glands; see the custom cutouts and gland entries page for how entry points are specified.
What you need
- Cable or conduit listed for wet locations, cut to length
- Connectors listed for wet locations, one per end
- The right knockout size, typically 1/2 in for 3/8 in flex connectors
- Box, gasketed cover, and mounting hardware rated for the location
- Cable clips or straps rated for outdoor use
- Tools: punch or step drill if a knockout must be added, screwdrivers, wrench for the locknut
Steps
-
Confirm the location and the listings. Exposure to rain makes the run a wet location. Check the print on the cable jacket and the connector body or data sheet for a wet-location listing. If either lacks it, stop and buy the listed part.
-
Plan the route and the entry point. Run the flex on the protected side of features that concentrate water, keep the run supported at the spacing the cable's instructions require, and bring it into the bottom of the box. A bottom entry on a wall-mounted enclosure is the single biggest moisture decision you will make.
-
Prepare the knockout. Use an existing knockout at the bottom, or punch a new one. Remove all swarf and burrs so the connector's gasket seats on clean flat metal. Painted or coated contact surfaces that serve grounding need the coating removed from the joint, per the enclosure grounding and bonding practice set out in NEC 250.12.
-
Install the connector at the box. Slide the locknut over the connector, pass the body through the knockout from outside, and tighten the locknut from inside. If the box has a removable panel, install it before the backplate goes back. Hand-tight plus a firm wrench turn is usually right; overtightening distorts thin stainless walls.
-
Terminate the cable. Secure the cable in the connector's clamp so it cannot pull or rotate, and leave enough slack outside to form a drip loop below the connector before the cable rises to it. Water running down the cable drips off the loop instead of into the fitting.
-
Dress the inside. Keep the grounded conductor and any spare cable low in the box, clear of where water would pool if the seal ever leaked, and land the equipment grounding conductor on the ground terminal. In US boxes, NEC 314.15 permits drainage openings of 3 mm (1/8 in) to 6 mm (1/4 in) in boxes listed for damp or wet locations; leave any listed drain holes open rather than plugging them.
-
Close and test. Fit the gasketed cover, compress the gasket evenly, and hose the assembly briefly from above. Check inside after an hour. A drop of water at the entry is a fitting problem; find it now, not next winter.
Checks when you are done
- Cable jacket print and connector marking both show a wet-location listing
- Connector locknut tight, gasket or clamp sealed, cable cannot rotate or pull out
- Drip loop formed below the entry, entry on the bottom face
- Cover gasket evenly compressed, no pinch points
- Grounding connection tight on a clean, coating-free surface
Mistakes that cost you the rating
- Reusing a dry-location set-screw connector because the thread fits the knockout
- Running unjacketed flexible metal conduit outdoors, where it is a damp-location product at best
- Entering through the side or top, where rain sits on the fitting
- Skipping the drip loop, so the cable feeds water straight into the connector
- Punching a new hole above the working zone or leaving burrs under the connector gasket
- Plugging a listed drain hole to "keep water out" and trapping what gets in anyway
Every penetration and every fitting is a weak link: the weakest one sets what the installation really is, which is the same weakest-link rule that governs enclosure ratings.
If the box has no knockout where you need one
Small cast or stamped boxes live with their knockouts. If you are specifying the box rather than working with what exists, choose one you can have cut where the job needs it. A hinged gasketed box such as the 8 x 6 x 4 in 316L wall-mount enclosure, rated NEMA 4X / IP66 by the manufacturer; not UL listed, can be ordered with the entry placed at the bottom center, which beats modifying a sealed box in the field. For more on what cutting and fitting do to a rating, see the custom stainless cutouts section.
Keeping water out of an outdoor box is a system: wet-listed cable, wet-listed connectors, bottom entry, drip loops, drains, and a gasket you can inspect. If corrosion on the terminals is what prompted the job, water is finding other entry paths too, and the wall-mount enclosure range shows gasketed boxes built to keep them shut.
Enclosures for this job
Catalog sizes that suit the job this article answers, picked from its subject; open one for its full specifications.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 8 × 6 × 4 in | 316L stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I use a standard set-screw AC connector outdoors if only a ground wire runs through the flex?
No. The listing of the cable and the connector follows the location, not what runs inside. In a wet location both the flexible cable or conduit and the connector must be listed for wet locations. A dry-location set-screw connector can trap water against the box wall and let moisture into the enclosure, so it does not keep the installation compliant even on an equipment grounding conductor only.
What is a wet-location flex connector?
It is a connector listed for wet locations, usually with a gasketed or sealed fitting body and a locking ring, sold for connecting wet-rated flexible cable or conduit to a box knockout. Suppliers call some styles deck connectors because they suit exterior surface runs. Match the connector to the cable type and the knockout size, and follow the manufacturer's installation instructions.
Does water get inside flexible metal conduit outdoors?
Yes. Unjacketed flexible metal conduit is not sealed; temperature changes breathe humid air in and out, and condensation forms inside. That is why unjacketed types are limited to damp locations. In wet locations use a type listed for wet use, such as jacketed MC, enter the box from the bottom, and form a drip loop so water runs off the outside rather than into the connector.
What knockout size fits a 3/8 in flex connector?
Most connectors for 3/8 in flexible cable or conduit thread into a 1/2 in knockout, the common size on small junction boxes. Check the connector's data sheet before cutting or punching anything. If your box has no knockout where you need it, a custom-cut entry in the right place is the cleaner path than forcing a connector into the wrong spot.