Short answer: about 120 VAC between the two secondary legs, with roughly 60 VAC from each leg to ground, is a healthy floating control transformer secondary. The to-ground reading is an artifact of the meter, not a supply fault. Neither leg is a neutral until the design bonds one. Measure leg to leg at the transformer, land the legs on the PLC's L and N terminals, and bond one leg only where the panel design calls for a grounded secondary.
Why each leg reads half the supply to ground
A control transformer with no bond on its secondary has no reference to the enclosure or the earth. Your meter completes a path anyway. Its 10 MΩ input, in series with a few hundred picofarads of stray capacitance from the secondary to the grounded box, forms a divider across the secondary. Each terminal hovers near the midpoint, which is why the split reads so consistently from panel to panel.
Put numbers on it. Assume 265 pF of stray coupling between the secondary and the grounded enclosure, an example value rather than a datasheet figure, and a meter input of 10 MΩ. At 60 Hz that coupling is 1/(2π × 60 × 265 pF) ≈ 10 MΩ. The divider then sits at half: 120 V × 10 MΩ ÷ 20 MΩ ≈ 60 VAC per leg. The current behind that display is about 6 µA. A 15 W test lamp bridged the same way stays dark, because a filament that size needs about 0.125 A and the coupling supplies millionths of that. Bridge one leg to the enclosure with a 2 kΩ resistor and the reading collapses to about 0.02 V. That collapse, rather than the number on the display, is what proves the secondary floats.
What each reading points to
- About 60 VAC to ground on both legs, nameplate voltage leg to leg — a floating secondary. The supply is usable; the to-ground numbers are meter artifacts.
- One leg at full voltage to ground, the other near zero — a bonded secondary. Find the existing bond before adding a second one.
- The 60/60-to-ground split but a leg-to-leg reading below nameplate — a supply fault: blown secondary fuse, mis-set primary tap or an opening lug. Fix the supply before wiring the PLC.
- Readings that drift or jump as you move the leads — a damaged lead or an opening connection. Remeasure on a known-live circuit to prove the leads first.
Causes, most likely first
- The secondary is unbonded by design. Most control panels run the secondary floating on purpose, so the 60/60-to-ground split is the normal case and nothing is failing.
- The design wanted a grounded conductor and nobody bonded it. The PLC still runs, but a single ground fault produces no trip; the fault sits on the steel until a second one lands.
- A supply fault is hiding behind the split. A blown secondary fuse, a mis-set primary tap or a burned lug also produce odd readings; the tell is a leg-to-leg number that misses the nameplate.
- An old bond survives from a previous design. A pilot lamp, filter or surge part wired from one leg to ground quietly references that leg and turns the split into a full-and-zero pattern.
How to confirm the cause
- De-energize the primary, lock it out and confirm absence of voltage before opening a lug.
- Measure leg to leg at the transformer's secondary terminals, not at the PLC. A healthy secondary reads its nameplate voltage there.
- Compare that reading with the PLC input label. Datasheets for compact PLC AC inputs commonly specify 100-240 VAC, so the nameplate secondary should sit inside that window with margin to spare.
- Trust the meter only after a check: use one rated CAT III at 600 V or better, and prove the leads on a known-live circuit.
- Repeat the to-ground measurement with 2 kΩ bridged from leg to enclosure. A drop to millivolts confirms a floating secondary; a reading that holds near full voltage means a bond already exists.
- Trace both secondary conductors end to end, looking for a bond the drawing never showed.
The fix, case by case
Floating by design, leg to leg at nameplate. Energize and land the two secondary conductors on the PLC's L and N terminals as its manual shows. The protective ground terminal goes to the ground bus; that connection is chassis safety, not a circuit reference. The PLC sees the same supply across its terminals either way, and floating secondaries run controls in plants everywhere. Accept the trade-off knowingly: with no reference, one ground fault trips nothing, so fit a ground-detection lamp where the panel is critical. For a compact box where the transformer shares the back panel with a supply and a relay, putting a 120 VAC power supply and relay inside a small enclosure covers the layout side.
The design calls for a grounded secondary. Bond one secondary conductor, once, at the transformer. Either leg is electrically correct on a plain single-phase secondary; the bonded one becomes the grounded circuit conductor, so identify it as such (white or gray is the NEC's identification at these sizes) and land every control return on it. The bonded leg takes the PLC's N terminal. A first ground fault then drives current through the effective ground-fault current path the NEC calls for, and the secondary fuse clears on the first fault instead of waiting for a second. For where that bond belongs, grounding a control transformer secondary: electrode or bond and where to bond a separately derived transformer neutral give the decision. The listing side is covered in bonding a separately derived transformer inside a UL 508A panel.
Leg to leg misses the nameplate. Repair the supply first: replace the blown fuse, set the primary tap to the measured primary voltage, remake the burned lug. To-ground readings mean nothing until leg to leg matches the nameplate.
Keep the enclosure out of the circuit
Every reading above uses the enclosure as its reference, so the box's bonding has to be real. Bond the enclosure and the back panel into the grounding system; the NEC requires metal parts serving as grounding conductors to be bonded so they can safely carry fault current (NEC 250.96(A)). Remove paint, lacquer and enamel from threads and contact surfaces at bonding connections (NEC 250.12). Keep load current off the steel: NEC 250.6 aims to keep neutral current off metal parts, so the grounded control conductor lands on its own terminal and the equipment grounds land on the ground bus. If the back panel raises the one-bar-or-two question, two ground bars in one enclosure: is the back panel enough settles it. The fundamentals behind these steps are in the enclosure grounding and bonding guide.
When the layout leaves no room for the grounded-conductor terminal beside the ground bus, order the box for it. A custom stainless enclosure takes your width, height, depth and cutouts, and it is delivered in 10 business days, counted from your approval of the drawing; start at custom enclosures. Write the arrangement on the panel drawing — "secondary floating" or "bonded at the transformer" — and label it inside the door. The next shift then reads the design instead of chasing the to-ground number.
The decision
Measure leg to leg at the secondary terminals; everything follows from that number.
- Nameplate voltage leg to leg, floating by design: land the legs on L and N, keep the enclosure bonding intact, leave the secondary unbonded. The 60/60-to-ground split is only your meter.
- Nameplate voltage leg to leg, drawings call for a grounded conductor: bond one leg at the transformer, identify it as the grounded conductor, and land the returns on it.
- Leg to leg below nameplate: fix the fuse, the tap or the lug before connecting the PLC.
To-ground readings decide nothing; the leg-to-leg reading at the transformer decides everything.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is there any harm in powering a PLC from a floating 120 VAC secondary?
There is no electrical harm, provided the leg-to-leg voltage matches the PLC's input window. Datasheets for compact PLC AC inputs commonly specify 100-240 VAC, and the transformer's nameplate secondary lands well inside it. The supply works the same whether or not one leg is bonded. The cost of a floating secondary is quiet: a single ground fault trips nothing until a second fault shorts the legs, so fit a ground-detection lamp on critical panels.
Which leg of a control transformer secondary becomes the neutral?
On a plain single-phase secondary, either one, and the panel drawings decide which the design chose. The leg you bond at the transformer becomes the grounded circuit conductor; identify it and land the control returns on it. Grounding a leg to improve a meter reading is backwards: the bond is a system decision that turns a first ground fault into a fuse-clearing short, and it goes in one place only.
Why does the to-ground reading collapse on a low-impedance meter range?
The 60 VAC-per-leg figure lives in the measuring path, not in the transformer. A digital meter's 10 MΩ input against roughly equal stray coupling divides the secondary to half, and a low-impedance range of a few hundred kilohms collapses that divider to millivolts. A 15 W test lamp wired leg to enclosure stays dark for the same reason: 6 µA of coupled current cannot light a filament.
Can I bond the secondary leg at the PLC instead of at the transformer?
Bond at the transformer, in one place. A second bond at the PLC puts load current onto the enclosure and every ground wire in the box, and the earth is never part of the effective ground-fault current path under NEC 250.4(A)(5). One bond at the secondary terminals keeps the return on the conductor you ran and leaves the enclosure steel for fault duty only.