Short answer: bond X2, the leg you choose as grounded, to the enclosure's grounding system with a copper jumper, and let the enclosure's equipment grounding conductor carry faults back to the supply. For a 208 V control transformer feeding one panel, that is the whole job: no grounding electrode conductor, no ground rod, no wire to the nearest steel column. The NEC exception for control transformers removes all three. In the worked example below, a 1000 VA transformer on a 15 A primary fuse, the X2 bond and the equipment grounding conductor are both sized to the secondary conductor, and the EGC size comes from NEC Table 250.122.
Which leg is grounded, and where it bonds
The secondary of a control transformer is a separately derived system. The NEC's premises-wiring definition includes control-circuit wiring that runs from transformer windings out to relays, pilot lights and contactor coils. So the secondary is grounded the way any premises system is: one conductor grounded, identified, and bonded at a single point. Pick X2 as the grounded leg; that is the convention in panel work, and staying consistent is what lets a fuse on X1 protect the circuit.
Land X1 and X2 on terminal blocks beside the transformer. Everything leaving the X2 block is the grounded conductor: white insulation, on its own terminal group. Its only contact with metal is the bond you make at the ground bar, so put secondary fuses on X1 and leave X2 unfused. A fuse opening X2 would leave every load sitting at full voltage to ground behind a circuit that looks dead.
Why the grounding electrode question disappears
A control secondary supplying premises wiring is a grounded system, and the NEC gives the ground connection two routes.
The long route belongs to separately derived systems that feed more than one enclosure. It is a grounding electrode conductor to the nearest effectively grounded building steel or metal water pipe. The conductor is sized from the total area of the secondary conductors, and the NEC's table floors it at 8 AWG copper for secondary conductors 2 AWG and smaller. That is the route for a dry-type transformer feeding a downstream panelboard, and bonding a transformer secondary inside a UL 508A panel lays it out.
The short route is the one a panel transformer takes. The NEC exception for control circuits applies when a separately derived system supplies only the loads inside a single enclosure. Bond the grounded secondary conductor to the enclosure or the transformer frame. Ground the enclosure with its equipment grounding conductor, and the grounding electrode conductor goes away. Copper clears faults; earth never does, because NEC 250.4(A)(5) defines the effective ground-fault current path as the conductors and states the earth is not part of it.
A rod beside the panel, if one is already there, is an auxiliary electrode under NEC 250.54: it may be connected to the EGC and it never replaces it. Panels listed to UL 508A are built this way at the bench — the transformer's grounded leg lands on the grounding terminal, not on steel. If the secondary feeds loads outside the panel on its own conduit, the exception stops applying and the long route does.
What you need
- A grounded enclosure: the supply EGC lands on the ground bar first, through a fitting that bonds to the wall — where the grounding conductor enters and bonds covers the entry hardware.
- A ground terminal bar on the backplate, mounted with star washers into clean metal. Painted carbon steel needs the coating scraped off the contact surfaces (NEC 250.12); bare 304 or 316L stainless has none to remove.
- Copper jumpers: one from X2 to the bar, at least as large as the X2 lead, and one across the door hinge sized like the panel EGC — door bonding jumpers covers size and routing.
- Terminal blocks with a separate grounded-conductor group, plus fuses for the primary and for X1.
- If the box is still an order form: the custom enclosure builder sets material, size and every cutout, and custom stainless enclosures with factory cutouts delivers the openings built in rather than drilled on site. The finished panel carries its enclosure type marking (NEC 409.110); our stainless boxes are rated NEMA 4X / IP66 by the manufacturer, not UL listed.
Wire it in, step by step
- Lock out and tag the feeder to the panel, and verify absence of voltage at the transformer primary terminals before touching anything.
- Land the supply equipment grounding conductor on the ground bar, sized from the primary overcurrent device with NEC Table 250.122. Common pairs: 14 AWG copper for a 15 A device, 12 AWG for 20 A, 10 AWG for 30 A, 8 AWG for 60 A.
- Land the 208 V primary on its two terminals behind the primary fuse or breaker.
- Land X1 and X2 on terminal blocks and label them; white leads to the loads go on the X2 group only.
- Make the bond: one copper jumper from the X2 terminal to the ground bar, no smaller than the X2 lead. Bare copper under a star washer is fine; an insulated jumper of 6 AWG or smaller is green or green with yellow stripes (NEC 250.119).
- Bond the rest of the metal — backplate, raceway entries and the transformer frame — to the bar (NEC 250.96(A)), and fit the door jumper from the list above.
- Fit the secondary fuse on X1, 10 A in the worked example, and none on X2.
- Mark the panel beside the bond: 'Control circuit — X2 grounded here.'
Worked example: 1000 VA, 208/120 V
A two-wire 1000 VA transformer, 208 V in and 120 V out, feeding relays and pilot lights in one stainless panel:
- Primary full-load current: 1000 VA ÷ 208 V = 4.8 A. Manufacturer datasheets list control-transformer inrush at 10 to 25 times rated current, so the primary fuse is 15 A, the common pick above a 4.8 A running current.
- Secondary full-load current: 1000 VA ÷ 120 V = 8.3 A.
- EGC and secondary conductors: 14 AWG copper, good for 25 A at 75 °C under the NEC's ampacity table, which covers both the 15 A device and the 8.3 A load.
- Secondary fuse: 10 A on X1 — above the 8.3 A running current, below the 25 A conductor rating.
- X2 bond: a jumper of that same size to the ground bar.
- Door jumper: green or a braided strap, matching the EGC.
Every conductor in the secondary path is one size, each protective device sits above the 8.3 A running current and below the 25 A conductor limit, and a fault anywhere on the secondary returns through X2's bond and the EGC to the source — all copper, no soil.
Checks when done
- With the panel still locked out, lift the load conductors off the X1 and X2 blocks and pull the secondary fuse. Measure X2 to the enclosure: a sound bond reads below 0.1 Ω on a digital meter, usually a few hundredths.
- Measure X1 to the enclosure the same way: open. Continuity here means a conductor pinched to the wall or a load left connected.
- Re-energize and measure at the terminal blocks: full secondary voltage across X1 and X2, 0 V from X2 to the enclosure, the same voltage from X1 to the enclosure.
- Tug each jumper and recheck the ground-bar terminations at their marked torque, star washers biting clean metal.
- For the 24 V version of the same panel, grounding a small 120/24 V control panel step by step walks the identical checks at 24 V.
Mistakes that break the ground path
- Treating a rod or building steel as the secondary's ground. Both are auxiliary at best (NEC 250.54); the clearing path is the EGC.
- Sizing the EGC from the transformer kVA instead of the primary device. NEC Table 250.122 keys to the overcurrent device: 10 AWG copper at 30 A, 8 AWG at 60 A.
- A second bond on X2 downstream of the main one. Current then shares the white conductor and the metal, which NEC 250.6 exists to keep apart.
- Coating left under the ground-bar screws. Painted steel needs contact surfaces scraped clean (NEC 250.12); gasket or anodize hides the same fault.
- Fusing X2 in a legacy panel that grounds X1. The fuse belongs on the ungrounded leg, so move it to X2 and re-label the panel.
The decision in one line: ground X2 at the enclosure with a copper jumper, size the EGC from the primary overcurrent device, and leave the electrode out of the order.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a control transformer inside a panel need a grounding electrode conductor?
No, when the secondary feeds only the circuits inside that enclosure. The NEC exception for control transformers lets you bond X2 to the grounded enclosure instead, and the enclosure's EGC carries the fault back to the supply. In the 1 kVA worked example the bond and the EGC are both sized to the secondary conductor from NEC Table 250.122 at a 15 A primary device. An auxiliary electrode under NEC 250.54 is optional and never replaces the EGC.
Which leg of a control transformer gets grounded?
Ground X2 and keep X1 hot. From the X2 terminal outward the circuit is the grounded conductor, landed on white leads, touching metal only at the bond. Fuses go on X1 only: a 10 A fuse covers the 8.3 A full-load current of a 1 kVA transformer while the secondary conductors carry 25 A at 75 °C, so the device opens long before the copper is at risk.
Can I bond the secondary to building steel or a ground rod instead?
You can connect either as an auxiliary electrode (NEC 250.54), but neither clears a fault: the earth is excluded from the effective ground-fault current path under NEC 250.4(A)(5), so the EGC does the clearing. Size it per NEC Table 250.122, the same table that sets the panel EGC — 10 AWG copper at a 30 A device — and the fault clears in copper in milliseconds.
What size copper jumpers does the bond need?
Match each jumper to the conductor it parallels: the X2 bond is the same size as the X2 lead, and a door jumper is sized like the panel EGC. Insulated jumpers of 6 AWG and smaller are green or green with yellow stripes (NEC 250.119); bare copper is fine under a star washer on clean metal (NEC 250.12). The NEC's electrode table floors a secondary bond at 8 AWG copper only when an electrode conductor is actually required.





