Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Arc flash labels for a six-door control panel with one main breaker

With no partition inside, a six-door panel is one arc flash volume and every door carries the line-side 32 cal/cm². A full-height metal barrier around the main-breaker section is what earns door 1 at 32 and doors 2–6 at 0.5, and the 2 s upstream clearing time — not the door count — is what leaves the line side 64× the load side.

NEMA4 Enclosure engineering team · Published November 14, 2026 · 7 min read

Short answer: a six-door free-standing cabinet with no internal partitions is one arc flash volume, and every door carries the line-side value — 32 cal/cm² at 7.6 kA bolted fault with 2 s upstream clearing. You earn split labels two ways: a full-height metal barrier that makes the main-breaker section its own compartment, or a written engineering case recorded in the study and covered in training. The 0.5 cal/cm² load-side figure is real, and it describes one point inside a volume that the 32 also occupies. Here is how the inputs check out, where the secondary-arc argument stands, and where the decision lands.

One volume, one label

An arc flash study calculates a point: one bus, one arcing current, one clearing device, one working distance. A cabinet is a volume, and IEEE 1584 treats it as one — the 2018 edition takes the enclosure's height, width and depth as calculation inputs. That is why shallow enclosures calculate lower incident energy, and why how IEEE 1584 handles MCC buckets turns on the steel between them.

Six doors on one open interior change access, never volume: an arc behind door 4 shares its air with doors 1 through 6, and the door count is bookkeeping. The same one-interior logic settles multiple circuits in one junction box — one shared space, one worst case, one value on the metal.

Check the study inputs against the nameplate

Every label downstream inherits the study's inputs, so settle the numbers before arguing about doors. Run them on the study's own figures as the worked example: a 500 kVA, 480:380 V three-phase transformer feeding an 800 A main, with 32 cal/cm² line side at 7.6 kA and 2 s.

  • Full-load current. 500,000 VA ÷ (1.732 × 380 V) = 759.7 A, call it 760 A. The 800 A main sits 5 % above full load (800 ÷ 760 = 1.05): a main, right-sized.
  • Bolted fault. 7,600 A is 10 × full load, which points to about 10 % impedance from source to lugs. A 500 kVA nameplate at 5 % impedance would drive 760 ÷ 0.05 = 15,200 A into a bolted fault on an infinite primary. If your nameplate reads 5 %, the secondary cable is making up the difference, or the study undercounts. One of those two is worth a morning before the labels go on.
  • Clearing time. The 2 s is a cap the study applied, and at fixed arcing current energy tracks time in a straight line: 1 s of clearing turns 32 into 16 cal/cm². Confirm the upstream device's real curve, and confirm the 0.5 load-side value came from the main's actual trip settings rather than a library default.
  • Working distance. IEEE 1584 sets 18 in [455 mm] as the low-voltage panel working distance, and the label value is that value at that distance. The distance exponent sits near 1, so a face at 12 in takes roughly 50 % more energy.

Why the line side is 32 and the load side is 0.5

The main breaker cannot clear an arc on its own line terminals — that fault is upstream of it, and only the device on the 480 V side clears it, inside the 2 s cap. A load-side arc is the main's to clear on its instantaneous curve, in a few cycles: call it 30 ms at 60 Hz. Two seconds against 30 ms is 67:1; the energy gap is 64:1 (32 ÷ 0.5 = 64). The arithmetic agreeing with itself is what a healthy study looks like. This is why the line side of a main stays live whatever the handle says, and the upstream clearing speed is the number to go fix.

The secondary-arc question, weighed

Panelboard practice labels at the line side of the main because a low-energy branch arc can eject ionized gas and conducting debris into line-side parts and start a second arc at the higher energy. No test series or documented field event is commonly cited for that mechanism at this scale — it is conservatism, and conservatism is a defensible reason. The counter-case carries weight in a 12 ft [3.7 m] lineup: a 0.5 cal/cm² event two to six doors from the main lugs is a weak candidate for initiating an arc across them. That is judgment, so write it, date it and sign it. Until a partition makes the argument physical, the shared-volume answer is the default: 32 on every door.

What earns two labels on one cabinet

Walk the enclosure once with the doors open — de-energized, locked out, tags on — and match what you see to a row.

What you find What it means What goes on the doors
Open interior, no barriers One volume; six doors, one value 32 cal/cm² on all six
Line-side cables or bus pass doors 2–6 on the way to the main Those doors put line-side energy at working distance 32 on every door the line side is reachable from, or reroute the cables into the main's compartment
Full-height metal partition around the main-breaker section, penetrations closed Two compartments, each holding its own event Door 1 at 32; doors 2–6 at 0.5; the partition named in the study
No partition, split labels wanted anyway A paper argument standing in for steel Written rationale, program-owner signature, recorded training

The partition earns the split when it is metal, full height, closed at every penetration, and honestly expected to keep an arc in its own compartment. Anything less is a suggestion, and plasma ignores suggestions.

Doors shut: where the boundary applies

Two readings exist on the closed door, and they split on equipment class. The working one: the boundary governs work with exposed parts, or interaction that could start an arc. A screwed-shut door with a label on it is neither; a pushbutton operated through the door is the second. High-energy switchgear and arc-rated equipment are where the editions have moved, so anchor your program to the NFPA 70E edition your site enforces and say so in the procedure.

On the numbers, the load-side boundary is short: with 0.5 cal/cm² at 18 in [455 mm], the 1.2 cal/cm² second-degree-burn line falls between the arc and your face. The line-side boundary is nothing like short, and that is the trouble. What a door cutout changes for arc flash covers the cases where a worker interacts through the door.

What goes on each label

NFPA 70E asks for three things on the label: nominal system voltage, the arc flash boundary, and the incident energy at its working distance or the PPE category. In the category table, Category 4 spans 25 to 40 cal/cm², so 32 is a Category 4 door; 0.5 sits below Category 1's 4 cal/cm² floor, so that door carries an energy value, not a category. Put the upstream device and the study date on the label as well, because a value with no date is where drift hides.

Label every door when the values differ across one lineup — a worker who reads four doors at the same number takes the fifth on faith. A 10-section MCC with six buckets a section has 60 doors, and one label per third of a lineup holds up only while the values stay uniform. Door 1's label should state that the line-side lugs stay energized with the main off; a disconnect under lockout still needs its arc flash label, and so does this one. Putting several labels on one enclosure sets out the same marking discipline for mixed equipment.

Cut the line-side number where it starts

32 cal/cm² buys Category 4 suits and slow, reluctant diagnostics on the doors where nearly all the energized work happens. Fix it where it starts, cheapest first:

  • Maintenance switch or arc-reduction setting on the upstream trip unit, active for the work window. At 0.5 s instead of 2 s the line side calculates 32 × 0.5 ÷ 2 = 8.0 cal/cm², at Category 2's ceiling.
  • Faster or current-limiting protection on the 480 V side, sized so the arcing current lands in the current-limiting range of the curve.
  • A compartment for the main. Steel you can point at beats an argument you have to explain, and it takes working with live circuits ahead of the main off the daily path.

Rerun the study after any of these. A trip-setting change that halves your incident energy also invalidates the old numbers still on the wall.

The decision

The decision, case by case:

  • No partition, none planned: 32 cal/cm² on all six doors, worked to as written.
  • Partition around the main-breaker section: door 1 at 32, doors 2–6 at 0.5, the partition named in the study, both boundaries on the labels.
  • Split labels without steel: written rationale, program-owner signature, recorded training — with the honest expectation that the partition would have cost less than defending the paper.
  • Clearing time improved upstream: rerun, relabel, date everything.

If the fix is a rebuilt enclosure, the compartment split belongs on the drawing before anything is cut: the enclosure selector narrows the body by usable size and DIN count, and how to size an electrical enclosure carries the volume math. Our NEMA 4X stainless enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed — a water and corrosion rating, silent on arc containment. They are built to order and delivered in 10 business days, counted for custom work from your approval of the drawing.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can each door of one enclosure carry its own arc flash label?

Yes, when a metal partition splits the cabinet into real compartments, or when you write the reasoning into the study and train every worker on it. Six doors over one open volume take the worst value: with 32 cal/cm² line side and 0.5 on the load side the gap is 64×, and an arc in any section shares the air with all of them.

Is 32 cal/cm² a Category 4 door?

In NFPA 70E's category table, Category 4 spans 25 to 40 cal/cm², so 32 sits inside it. The 0.5 cal/cm² load-side value falls below Category 1's 4 cal/cm² floor, so that door carries an incident-energy value and a boundary, not a category number.

Does the arc flash boundary apply with the doors shut?

It governs work with exposed parts, or interaction that could start an arc — so a closed, fastened door is out of play and a door-mounted pushbutton is in. On the numbers: 0.5 cal/cm² at the 18 in [455 mm] working distance puts the 1.2 cal/cm² boundary closer than your face. High-energy switchgear is where editions differ; anchor to the one your site enforces.

What breaks first when labels and the study drift apart?

A door that kept its value from the previous revision. Match every label to the current study — energy, boundary, working distance, upstream device, date — and rerun after any change to trip settings, the transformer or the feeder. A door still reading 32 after a settings change took the arc to 8.0 cal/cm² is carrying a 4× error.

How much does faster upstream clearing cut the line-side number?

At fixed arcing current, energy tracks time in a straight line. Clearing in 0.5 s instead of 2 s takes 32 to 8.0 cal/cm², the Category 2 ceiling; 0.1 s takes it to 1.6 cal/cm², under Category 1's 4 cal/cm² floor. An arc-energy-reducing maintenance setting on the upstream trip unit is usually the cheapest fix you own.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides