Short answer: keep the lineup's incident energy on every wireway label, and decide the PPE by task, not by trough. NFPA 70E runs its arc flash risk assessment on what your hands are doing and on the condition of the equipment. Lifting the vertical wireway cover to look, with the starter terminals behind secured plastic shields, keeps you outside the arc flash hazard. Pushing fish tape into the same trough, pulling cable past bare terminal strips, or finding metal dust and brittle insulation puts you back at the full label value — in the worked example below, 8 cal/cm² at 18 in. The trough does not get a softer number; the task gets a different answer.
What NFPA 70E asks you to weigh
NFPA 70E requires an arc flash risk assessment wherever work happens on energized equipment, and that assessment weighs two separate things: how severe an arc would be, and how likely your task is to start one. The label answers only the first. Its number is incident energy at a stated working distance, typically 18 in [455 mm] at low voltage, from a study that modeled the enclosure you are opening — the same modeling that gives smaller buckets different results, as covered in how IEEE 1584 handles MCC bucket dimensions.
NFPA 70E draws the arc flash boundary where incident energy falls to 1.2 cal/cm² [5 J/cm²], the onset of a second-degree burn on bare skin. Inside that boundary you wear arc-rated PPE for an interacting task; outside it, the energy has dropped below the injury threshold. Likelihood is the other half of the assessment. An arc needs something to initiate it, and in a wireway that initiator is almost always your hands: a fish tape, a dragged cable, a tool slipped past the opening.
The three checks that clear a wireway task
A task in an MCC wireway sits outside the arc flash hazard when three checks all pass. Run them in this order and write them on the work order.
- Nothing crosses the plane of the opening. You remove the cover, look, and close it. No fish tape, no wire being pulled, no tools or fasteners going past the opening.
- No energized conductor is exposed. Terminal strips sit behind secured covers or shields, and those shields are present, fastened and uncracked.
- The equipment is in normal condition. Covers open freely, insulation is supple, and there is no scorching, corrosion, water or unrepaired fault damage.
With nothing exposed, the shock side closes too. NFPA 70E sets the limited approach boundary at 3 ft 6 in [1.0 m] and the restricted approach boundary at 1 ft [0.3 m] from an energized 480 V conductor, and a clear trough contains no such conductor to approach. That is the whole logic of assessing the work before choosing PPE, and it applies to a wireway exactly as it applies to a junction box.
Two trough layouts, two different answers
| Where you are working | What is inside | What it decides |
|---|---|---|
| Older line, vertical trough beside the buckets | Starter terminal strips land in the trough, bare once the cover is off | Every task including the look works at the label value; schedule terminal work with the bucket de-energized |
| Newer line, vertical trough | Plastic shields isolate the starters from the trough | Cover-off visual passes the three checks; pulling wire past the shield openings works at the label value |
| Top and bottom horizontal troughs | Shared by the whole lineup, with bus-side openings and blind holes | Walk the three checks on the specific task before you classify it |
The older layout puts bare terminals in the trough, so the second check fails the moment the cover comes off, and the whole trough behaves as live terminal work. The shielded layout keeps the trough clear, so visual access qualifies while anything inserted still works at the label value. The horizontal troughs serve every section in the lineup, so carry the worst bucket's energy there until your study prints a different number.
What returns you to the full label value
Any one of these findings revises the task back to the label value, or to a shutdown:
- fish tape that can stick, dive into a blind hole or wander back toward the bus;
- a conductor pulled past bare terminal strips or through a shield opening;
- insulation that has run hot and gone stiff enough to crumble at a touch;
- water, mud, oil or conductive dirt inside the trough;
- metal powder or flakes from grinding or cutting anywhere near the lineup;
- a shield missing, cracked or unfastened;
- covers that stick, discolor or smell of overheating.
Half the list is contamination, and contamination is an enclosure problem before it is a PPE problem. The shared space that aggregates several buckets' circuits — the situation in arc flash with multiple circuits in one junction box — also collects whatever the plant air carries. A sealed, gasketed trough keeps the list short.
Shields buy exposure control, not energy credit
The plastic shields around the starters earn you the second check: with them in place the trough has no exposed conductors, and a cover-off look passes all three. They earn you nothing on the number. Nothing in NFPA 70E or IEEE 1584 subtracts incident energy for a plastic barrier, so the posted value stands for every interacting task, and a shield is never a reason to step PPE down. Treat the shields as a per-task check — present, fastened, undamaged — because one missing shield turns a clear trough back into a bare-terminal trough.
Worked example: a 480 V MCC wireway posted at 8 cal/cm²
The inputs: a 480 V lineup, 277 V to ground, whose arc flash study posts 8 cal/cm² at an 18 in [455 mm] working distance for the vertical wireway — an example value, so replace it with whatever your study prints. The trough beside the buckets has bare terminal strips in the older row and checked plastic shields in the newer row. The rule: for any task that can initiate an arc or reaches an exposed conductor, the arc rating of your clothing system must meet or exceed the posted incident energy, and 8 cal/cm² is the minimum rating of NFPA 70E's PPE Category 2.
Task A, visual on the shielded row: cover off, look, cover on. All three checks pass, so the task sits outside the arc flash hazard and needs no arc-rated clothing. With nothing exposed, the 1 ft [0.3 m] restricted approach boundary holds nothing.
Task B, pulling a control cable through the older row: the cable rides past bare terminals, so it works at the label value. Required rating 8 cal/cm²; a Category 2 kit provides 8 cal/cm², and the margin is 8 − 8 = 0 cal/cm². A 25 cal/cm² suit, the Category 3 minimum, buys 25 ÷ 8 ≈ 3 times that margin at the cost of reach and dexterity at the strips.
Decision: run Task B with the affected buckets de-energized where the process allows. Where it must stay live, wear at least the label value and keep the cable clear of the strips. Above 40 cal/cm², the top of Category 4, write the wireway into your de-energize-only policy. De-energized means locked out and proven dead before hands go in.
Writing the policy so it holds up
Put the lineup's value on every wireway opening and let the work order carry the task decision. Where the study calculated different energies for different sections, label each one — the conditions match when one enclosure needs several arc flash labels.
The work order names the trough, the task, the shield condition, the contamination findings and who ran the three checks. A decision written for a visual task expires the moment the task changes, so the crew fishing wire the next day starts a fresh one. And while your bucket is open with the sections around it still live, the rules in PPE with live circuits ahead of the main govern the door you left open.
Specifying the next lineup and the boxes around it
Order new lines with the starter terminals behind barriers so the wireway stays clear, and keep field splices in their own boxes rather than in the shared trough. Label every field box with the incident energy of the circuits inside it, and keep it sealed: a gasketed box holds water and conductive dust off the list that escalates tasks to full PPE. Our stainless junction boxes and NEMA 4X wall-mount enclosures are rated NEMA 4X / IP66 by the manufacturer and not UL listed — NEMA does not test or endorse enclosures — and they take your cutouts and terminal plan as a custom build delivered in 10 business days from your approval of the drawing. Where the plant demands listed equipment, start from what a UL 50E listing covers.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Should the wireway get its own arc flash label, or use the MCC's?
Label it with the lineup's value: the study modeled the whole enclosure, wireway included, at one working distance such as 18 in [455 mm]. Put a separate label on a section only when the study actually calculated a different incident energy for it, the same rule that governs multiple circuits sharing one junction box.
Can I take the wireway cover off for a look without arc-rated clothing?
Yes, when all three checks pass: nothing goes past the plane of the opening, no energized conductor is exposed, and the shields or covers are in place and undamaged. With nothing exposed there is nothing inside the 1 ft [0.3 m] restricted approach boundary at 480 V to approach. Write the three findings on the work order so the decision survives an audit.
Is pushing fish tape through an energized MCC wireway acceptable in lighter PPE?
Treat it at the full label value or de-energize the section first. A tape that sticks and dives into a blind opening toward the bus is exactly the interaction that starts an arc, and the assessment keys on that interaction. For the 8 cal/cm² example that means an 8 cal/cm² minimum arc rating, with locked-out work the better answer.
Do the plastic shields around the starters reduce the posted incident energy?
They remove exposed conductors from the wireway, which is what earns the no-hazard call for visual access, and they carry no calculated reduction of the posted incident energy. Check each shield before you lean on it: present, fastened, uncracked. One missing shield and the trough is a bare-terminal trough again, so reassess that task at the label value.





