Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Arc flash labels for a panel with multiple 480V feeds

Tying both feeds to one bus models a 40 kA path that never exists. Run each 480 V feed to its own line-side point at its highest available fault current, twice — with the real clearing time, then with the device omitted so IEEE 1584's 2-second cap governs — and label the enclosure with the worst case, 64 cal/cm² in the worked example, plus the note that one disconnect leaves it energized.

NEMA4 Enclosure engineering team · Published November 14, 2026 · 7 min read

Short answer: keep the feeds separate and bound the panel instead of modeling it. IEEE 1584's equations were fitted to single-source tests on one bus, and no edition covers a custom panel with two independent 480 V line sides. You run each feed to its own line-side point at the highest available fault current. Calculate every point twice: once with the real clearing time, once with the overcurrent device omitted so the standard's 2-second cap governs. The worst case goes on the label, with a note that opening one disconnect leaves the box energized. Incident energy scales with current x time, so the 2-second run is what bounds the day the fuse or breaker fails to clear the way its curve says. The study outputs below are hypothetical worked-example numbers: swap in your own before you label.

Why the one-bus run gives a number you cannot defend

Your study software will happily land both feeds on one bus node and print an incident energy. With 22 kA on one feed and 18 kA on the other, the summed case pushes 40 kA through a single arc. The panel has no such path — two lug sets, two conductor impedances, two clearing devices — and the run pairs the strongest current with whichever device the single-bus model happens to use. It can overshoot or undershoot the real event, and nothing in the output tells you which.

The equations behind that number are an empirical fit to tests with one arcing source, one set of electrode gaps and one enclosure geometry. A custom panel breaks all three at once. Terminal blocks, fuse blocks, starters, relays and a control transformer crowd the backplate, taps of mixed wire sizes put a different available current at every terminal, and the box may hold a second voltage in its control section. Where the panel has compartments, choosing which box to model is its own question — one the IEEE 1584 enclosure size with compartments article works through.

Because you cannot rule out an arc starting on one circuit and involving its neighbour, the unit you label is the enclosure, not the circuit. When the geometry genuinely puts two sources into one arc — parallel conductors landing on the same lug block — adding their contributions is the right arithmetic, and the multiple circuits in one junction box case covers it. A panel with separate line sides is the case that arithmetic does not describe, so you bound it instead.

What to have on the bench first

  • Every source that can put voltage in the box: its voltage, its upstream device type and rating, and the available fault current at the panel's line-side lugs from the system study.
  • Whether the two sources can be live together — interlock, transfer arrangement, or nothing between them. "Normally off" counts as nothing.
  • The one-line and the panel drawings as built, with device part numbers as they sit in the field.
  • The working distance you will print: 18 in [455 mm] is the low-voltage panelboard convention.

The procedure, step by step

  1. List every source that can energize the enclosure: both 480 V feeds, plus any control-power or utility feed landing in it.
  2. Record the upstream clearing device and the available fault current for each, and mark whether the pair can be energized at the same time.
  3. Take each feed as its own study point at the line-side lugs, run at that feed's highest available fault current, never an average of the two.
  4. Calculate the point with the real device curve and record incident energy, clearing time and arc-flash boundary.
  5. Calculate the same point again with the device omitted from the model, so duration falls to IEEE 1584's 2-second cap, and record the same three numbers.
  6. Set the enclosure's label value to the worst of every run — 64 cal/cm² in the example below — carrying the working distance and boundary from that same run.
  7. Write the uncertainty statement into the study report: in-panel taps and impedance, possible propagation between circuits, device clearing treated as unreliable.
  8. Label the box with both sources named, at the door and at each remote disconnect.

Worked example: two 480 V feeds in one box

Take a 36 x 30 x 10 in [914 x 762 x 254 mm] enclosure with two independent 480 V, 3-phase feeds. Feed A arrives through a 400 A current-limiting fuse with 22 kA available at the lugs. Feed B arrives through a 200 A circuit breaker on its short-time band with 18 kA available. The working distance is 18 in [455 mm], and the incident-energy values below are illustrative study outputs; the arithmetic between them is what you repeat.

Feed Available at lugs Upstream device Run with device Run with device omitted
A 22 kA 400 A current-limiting fuse 0.05 s → 1 cal/cm² 2.0 s → 40 cal/cm²
B 18 kA 200 A breaker, short-time band 0.25 s → 8 cal/cm² 2.0 s → 64 cal/cm²

At a fixed arcing current, incident energy is proportional to duration, so the omitted run is the with-device run scaled by the time ratio: Feed A, 1 x (2.00 / 0.05) = 40 cal/cm²; Feed B, 8 x (2.00 / 0.25) = 64 cal/cm². The label takes Feed B's omitted run, 64 cal/cm² at 18 in, and the boundary that same run prints.

Feed A's fast 0.05 s deserves its suspicion. A current-limiting fuse clears in under half a cycle — about 8 ms of the 16.7 ms a 60 Hz cycle takes — only while arcing current stays above its threshold, and the taps and conductor impedance inside a custom panel pull that current down. UL 248-8 lets a time-delay Class J fuse carry 500% of rating for at least 10 s, so a 400 A fuse holds 2,000 A for 10 s before it clears. Forensic files include panels that burned for several seconds while upstream current-limiting fuses watched. The 2-second run, not the fast one, is the number that survives that day.

Both omitted runs land at or above 40 cal/cm², where NFPA 70E's PPE categories stop and the equipment is called dangerous. At that level clothing is not the control — distance, procedure and the fixes below are.

What the label says

The door label carries the worst-case incident energy, the working distance and boundary from that run, the study date, and source wording plain enough to act on: "Two 480 V sources. Opening disconnect A leaves source B energized." Add one line to the label package — bounding analysis, device clearing not modeled — and keep the full statement in the study report.

Where each label goes, at every door and every remote disconnect, is covered in multiple arc flash labels on one enclosure; the single-main-breaker pattern is the one the six-door panel with one main breaker article follows. Before hands go in, prove absence of voltage at the lugs from every source. The disconnect you can see from the door is one of two, the same reason a separate disconnect enclosure keeps its line side live.

Checks that prove the study matches the panel

  • Walk the panel with the drawings: every energized source on the floor appears in the study, and every source in the study is named on the label.
  • Pull the fuse part numbers and read the breaker settings as built. A fuse class or trip setting that differs from the model wrecks the fast run; the 2-second bound stands regardless, which is the second reason it sets the label. Underrated feeder breakers in the panel add a clearing problem of their own.
  • Read the label against the runs. If the number on the door is not the maximum of the cases you ran, one case is missing — find it before anyone opens the door.

When the bound is ugly: fixes that change the number

A 64 cal/cm² label is a working answer, not a design. Three moves take it down, in order of effect:

Fix What it does to the study
One main disconnect ahead of both feeds The box becomes a single source at its line side: a standard IEEE 1584 run, one label
Split the sources into two enclosures Each box gets its own single-feed study, and propagation leaves the picture
Arc-energy-reducing setting upstream Maintenance-mode trip settings cut duration, and energy falls with it one-for-one

Splitting into two boxes is the cleanest fix for a panel that grew a second feed. Two stainless enclosures rated NEMA 4X / IP66 by the manufacturer — not UL listed — each carrying one line side and its devices. Size them with the enclosure selector or the stainless NEMA 4X enclosures range; they are delivered in 10 business days, counted from your approval of the drawings. If the panel carries a UL 508A label, structural changes go through what field modifications to UL 508A panels allow before you cut anything.

Decide by case, then. One combined disconnect ahead of everything, and the box studies as a single source. A true interlock that keeps the feeds from ever being live together, and you still run every feed, with the label at the worst single feed. Two feeds that can be live together with propagation you cannot rule out, and you run the two-run bound of the example: worst case on the door, uncertainty note in the report. A bound nobody can work under, and you split the boxes or fix the clearing upstream, then study it again.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
36 × 30 × 10 in304 stainless36 x 30 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

If I model both 480 V feeds terminating on one bus, is that incident energy real?

No. The software sums 22 kA and 18 kA into one 40 kA arc, but the panel has two line sides and two clearing devices, so that current never flows through a single path. The figure can sit above or below the real event. Keep the one-bus run as a comparison case in the report, and label from the worst of the per-feed runs.

What happens if the upstream current-limiting fuse does not clear?

The arc keeps burning and the energy climbs with every second. Forensic cases exist where upstream current-limiting fuses never cleared and the panel burned for several seconds, putting the energy in the hundreds of cal/cm². That is why the omitted-device run sets the label: with the device gone, IEEE 1584 caps duration at 2 s, which turns Feed A's 1 cal/cm² at 0.05 s into 40 cal/cm².

Can I leave a feed out of the study because it is normally off?

No. The normally off feed is the one that backfeeds a fault or gets switched on for a test, and in the worked example it is the second feed that sets the 64 cal/cm² label. It stays in the study and it stays named on the door.

Does the 2-second cap apply where the worker cannot step clear?

It assumes they can. IEEE 1584 sets the 2-second cap on the assumption the person can move away from the arc in that time, and it also assumes 2 s when no device exists or the clearing time is unknown. In a closet or tight corner, keep the real device curve in the study and treat the point as beyond the 40 cal/cm² ceiling of the PPE categories.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 36 × 30 × 10 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides