Z axis DRO counts but no motion: probe points in the cabinet

A counting DRO with a stationary Z axis points at the step/direction path between controller and drive, not at the G-code: probe the 5 V step and direction pins against the controller's own signal common, jog slowly and watch the averaged mid-rail reading near 2.5 V, then pull the harness and loop the pin into an LED and a 330 Ω resistor. Alive unloaded means the fault is downstream; dead unloaded means the controller output stage.

NEMA4 Enclosure engineering team · Published November 25, 2026 · 9 min read

Short answer: a Z axis that shows counting numbers on screen but will not move is a wiring or output-stage fault between the controller and the drive, not a program problem. On a step-and-direction machine the readout counts commanded position computed in software, so it climbs even when the Z output pin sits at 0 V. Work the fault from the cabinet side: probe the 5 V step and direction pins against the controller's own signal common, jog slowly and read the averaged voltage, then pull the harness and loop the pin into an LED and a 330 Ω resistor. A pin that blinks is alive and the fault sits downstream; a dark pin is a dead output stage. Switch off and verify absence of voltage before moving any conductor in a terminal block.

Why does the DRO count while the Z axis stands still?

Because on a step-and-direction machine the readout counts commanded position computed in software: a climbing number with a dead Z output terminal proves the planner is issuing the move, and points the fault at the step/direction path between the controller and the drive.

The screen never told you that pulses left the box, and the rest of the symptom set narrows the location:

  • X and Y jog normally while Z is dead: the fault lives on the Z channel, because a shared logic supply fault or a software fault would stop all three axes at once.
  • DRO counts while you jog: the motion planner runs, but it is never proof that a pulse reached the pin.
  • The Z drive runs when fed from the Y output: the motor, mechanics, drive and drive cable are all good, so the fault sits upstream of the drive input terminals.
  • A dead Z output pin while X and Y pins toggle: the Z port itself or the conductor between that terminal and the drive.
  • The axis died over an overnight shutdown with nothing else changed: suspect wiring, connector or output stage before any setting.

The swap is the strongest of the five observations. Put the harness back on Z, jog again, and note that the fault stays with the physical port across two cable positions: that is hardware, and everything that follows is confirmation.

Where do you put the meter's black lead?

On the controller's own signal common, the common terminal of the axis output group: a step output is a voltage between its pin and its common, so measuring to chassis or to the drive's own common reads floating millivolts that mimic a dead pin.

Park the black lead on that common for the whole session. Before trusting any reading taken at the drive end, prove the two commons are bonded: supplies off, ohms range, controller common to drive common. A sound bond reads under about 1 Ω. A reading of 10 Ω or more, or an open circuit, means the common path is lifted. A lifted common makes a healthy output look dead. The ground loop checks for a cabinet walk through that survey, and on a three-axis box it costs about five minutes.

Measure the drive's opto logic feed at the drive's input connector too, not at the supply's own terminals. Most opto-isolated inputs need an external feed from the controller's logic rail before they can see anything, so a missing feed there leaves the drive deaf while the controller looks fine.

What should a step line read on a DMM while jogging?

An averaged value between the rails: a healthy step pin driven with pulses reads somewhere between the low rail and the high rail on a DC volts range, the number moves with the jog rate, and a dead pin sits at one rail or wanders on a floating input.

A DMM averages whatever arrives, so the reading is duty cycle times the high rail. Use a continuous slow jog, never a bump, and give the meter a second to settle:

  • Parked: the step pin sits at one rail, and the direction pin sits at whichever level the last jog set.
  • Continuous jog: the step pin averages mid-rail, and the reading tracks the jog speed.
  • Reverse the jog: the direction pin toggles between the two rails while the step average stays mid-rail.

Worked example: jog Z with a 5 V step line at 40% duty, and the meter reads 0.40 × 5 V = 2.0 V. Double the jog feed so the duty rises to 60%, and the reading scales to 3.0 V. If X shows 2.0 V then 3.0 V while Z holds 0.00 V at both rates, the Z pin is producing nothing. If Z moves the same way the duty moves, pulses exist and the hunt moves downstream. That averaging behaviour is the whole trick, and it is the same practice described for testing low-voltage logic rails with a DMM.

A meter cannot show pulse width. Drive datasheets commonly ask for step pulses of 2.5 µs or wider, so wiring that averages correctly yet still misses steps needs an oscilloscope, not a second meter.

Are the outputs differential or single-ended?

Read the controller's wiring sheet before you trust any single reading: a differential pair is measured between STEP+ and STEP-, and each leg idles near half the rail, so a pair at the logic level shows about 2.5 V on either leg to common whether or not pulses flow.

A single-ended output runs one conductor per signal against the shared common, which is what most retrofitted machines use. A differential pair drives two conductors in opposite phase and doubles the swing the drive sees: it swings from below the common to above it, twice the single-ended swing. That is why noisy shops prefer it. Measure the pair between its legs; one leg to common sits at the midpoint and tells you nothing. Where a differential drive must take a single-ended signal, the drive's common-anode or common-cathode input arrangement decides where the return lands, and the wiring sheet shows it.

How do you prove a dead output with the harness off?

Pull the Z step conductor off the controller terminal and loop the bare pin into an LED and a series resistor down to the controller's signal common: a pin that blinks the LED while you jog is alive and the fault sits downstream; a dark LED is a failed output stage.

This is the decisive test: it loads the pin with almost nothing and removes every downstream suspect at once. Size the resistor for the rail in the machine. For a 5 V rail and a red LED dropping about 2 V, R = (5 - 2) V ÷ 0.010 A = 300 Ω. Fit the standard 330 Ω value. The loop then runs at 3 V ÷ 330 Ω = 9.1 mA, bright enough to see and inside the 5 to 20 mA a typical opto input wants. Jog Z slowly and watch the LED, then repeat on the direction pin with short single jogs. Mind the polarity; a reversed LED stays dark and mimics a dead pin, so flip it once before you believe the result.

Read it like this. Blinking unloaded but dead with the harness reconnected puts the fault in the harness, the drive input or its opto feed. Dark unloaded ends any argument about software: the controller's Z output stage has failed, and the readings collected so far are the service evidence.

What kills a step output overnight?

In order of likelihood: a conductor or terminal fault on the Z path, a lifted common or a missing opto feed, a shorted field wire dragging the pin to the low rail, a zeroed axis parameter, and only then a failed output driver inside the controller.

No single symptom separates them, so run each check and apply its fix:

Rank Cause What you find The fix
1st Backed-out screw, stray strand or wire clamped on insulation at the Z terminal 0 V at the terminal; continuity comes and goes as you flex the conductor Re-terminate with about 6 mm of bare copper under the screw, then re-run the loopback
2nd Broken conductor at a flex point in the drag chain or at the gland End-to-end continuity fails while you flex the cable at a strain relief Replace the conductor and rebuild the strain relief; the vibration-resistant wiring article covers harnesses that survive movement
3rd Lifted common or missing opto logic feed More than 10 Ω between controller common and drive common, or no feed at the drive's input connector Re-land the common; restore the opto feed at the drive
4th Field wire shorted to a neighbour or to ground The pin recovers the moment the field wire is unplugged Repair the chafed or pinched wire, then prove the pin survived with the LED test
5th Axis parameter zeroed or corrupted Steps per unit or maximum feed reads 0 where X and Y show their numbers, say 2,000 steps/mm Re-enter the values and store them; the DRO counted all along because the planner ran
6th Output driver failed inside the controller Dark LED unloaded, the meter pinned at the low rail at every jog rate, fault stays on the Z port across two cable swaps Send the meter and range with every probe reading for service; one dead channel does not load the other two

An output that recovers with the field wire off has usually survived the short, but prove it with the loopback before you trust it again.

How do you keep the Z axis from dying again?

Most of these faults come from handling and kickback, so fixture the Z harness the way the rest of the cabinet is fixed: ferrules on every conductor, strain relief at both ends, a service loop of 4 in [100 mm] before the gland, and the shield landed at one end only.

Twist each step and direction signal with its own signal return conductor, and hold the bundle about 4 in [100 mm] away from AC power and motor cables. That separation is what drive installation manuals ask for in cabinet wiring; cross at right angles where runs must meet. Land the cable shield on the panel earth bar at one end only, as the panel earth and shield earth article lays out. Bring control power up before drive power and let it fall last, and fit suppression on any coil that shares the harness, because most overnight output deaths trace to kickback through a shared loom. When you order the entries rather than drilling them, the cutouts, glands and HMI windows guide shows how to give each cable class its own gland field.

When does the enclosure or the wiring layout need a change?

Re-specify when the Z harness breaks at the same point a second time: move the splices and terminal blocks inside the cabinet, give the signal entry its own gland field away from the motor power entry, and place the controller so its axis terminals reach the harness without tension.

A second break at one gland or drag-chain entry is a layout fault, not bad luck. The controller enclosure cable entry article covers giving machine wiring its own sealed, strain-relieved path, which is what stops conductor fatigue at the wall. Splices and probe points belong on terminal blocks you can reach with a meter, not buried in a loom. For signal wiring that lands away from the main cabinet, the instrument junction box selection article matches the box to the terminations. The stainless junction box range covers the wall-mount sizes.

If the controller, three drives and a relay have outgrown the plate, the stepper drive and controller in one enclosure article shows the arrangement that keeps signal and power apart. Custom stainless enclosures let you set the depth, the gland field and every cutout instead of re-drilling a stock box. In a washdown or dusty shop, keep the electronics in a cabinet rated NEMA 4X / IP66 by the manufacturer; not UL listed. The sealed box protects the wiring you service inside it.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can a multimeter really show step pulses?

For presence, yes; for quality, no. A DMM on DC volts averages the pulse train, so a step line at 50% duty reads near mid-rail, about 2.5 V on the typical logic level, and the reading rises and falls with the jog rate. It cannot show pulse width or amplitude, so a drive that misses steps while the average reads correctly needs an oscilloscope; drive datasheets commonly ask for pulses 2.5 µs wide or wider.

How much current does an opto-isolated drive input draw?

Most opto-isolated step and direction inputs accept 5 to 24 V signaling and draw roughly 5 to 20 mA through the resistor built into the drive; the drive's wiring sheet prints its own number. That window also sizes the loopback LED: with a 5 V rail and a 2 V LED drop, 330 Ω gives 9.1 mA, comfortably inside it.

Can step and direction wiring run beside motor cables in the cabinet?

Keep them apart: roughly 4 in [100 mm] of separation from AC power and motor cables is what drive installation manuals ask for in cabinet wiring, with right-angle crossings where runs must meet. Twist each signal with its own signal return conductor, and land the shield on the panel earth bar at one end only.

What should you write down before sending the controller out for service?

Record the meter and range used, then the DC volts at each probe point: Z step and Z direction to the controller's signal common, harness on and again unloaded, plus the same readings on X and Y at the same jog rate. A page showing 2.0 V on X against 0.00 V on Z pins the dead channel and shortens the repair.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on control panels and drive cabinets

All articles

Buying guides

The guides behind this answer

All guides