Yes, bring the wire out of the seal fitting and land it at the enclosure wall through a cable gland. In a non-classified area the NEC never forces the conduit to continue to its termination; once the conductor leaves the raceway, the wire is the circuit. Three moves make the job right. Secure and bond the raceway to the enclosure, terminate at a listed gland sized to the cable, and keep every entry a factory hole with its gasket land intact.
The numbers that steer the job: a 3/4 in NPT gland clamps 0.3-0.5 in (8-13 mm) of cable OD, and that thread takes a 1-1/8 in (29 mm) hole. The sizing math, the steps in order and the checks follow.
What the code asks when the raceway stops at a seal
The NEC requires a raceway entering equipment to be secured to that equipment. Equipment built with an open bottom carries the provision for conduits stubbing up from a slab without individual fittings. A solid bottom is meant to be entered through fittings fastened to the wall: hubs, glands or connectors. A bank of stub-ups under a solid bottom therefore raises a fastening question before a wiring one, and the gland answers both.
Metallic raceway also has to be bonded. NEC 250.96(A) requires metal parts serving as equipment grounding conductors, raceways and enclosures included, to be bonded so they carry the fault current likely to be imposed on them. The earth is not part of that path; NEC 250.4(A)(5) keeps the effective ground-fault current path metallic end to end. The guide to enclosure grounding and bonding walks the full chain, and the jumper size comes from NEC Table 250.122, read against the overcurrent device ahead of the run.
Then ask what the seals were bought for. A conduit seal stops gas and pressure from migrating along a raceway in a classified area; in plain shop air the NEC asks for none. If any part of the underground run crosses a classified area, the seal belongs at that boundary, and rigid metal conduit carries the wire from seal to enclosure the way the RMC between seal fitting and enclosure article lays out. For gland selection inside classified runs, the Class 1 Division 1 conduit and cable gland selection article is the companion. Where the run never crosses one, the seal is a fitting, and the wire that leaves it can terminate at the wall.
One detail sits before the steps: a conductor leaving a seal has no jacket if the seal sits on individual wires. Protect the exposed span with a sleeve or a short piece of flexible conduit, and let the gland take the strain at the wall.
What you need
Everything here has one job: carry the wire, support it, and leave the gasketed wall unbroken.
- Cable glands, one per cable, listed for the job, with the seal insert chosen for the jacket OD.
- Thread sealant for NPT glands; an O-ring or flat sealing washer for straight-thread glands, seated on a flat land. The G thread vs NPT article sorts out which adapter suits which wall.
- A gland plate or multi-hole sealing plate when the bank brings several cables, or when the seal delivers individual conductors instead of a jacketed cable.
- A bonding jumper and hardware for metallic raceway; the earth continuity through a gland plate article sizes the link when the plate carries it.
- A sleeve or short piece of liquid-tight flex for the span between seal outlet and gland.
- A hole saw and deburring tool only where the entries were not ordered with the box; the stainless hole-cutting article shows the saw work.
Hole sizes follow standard knockout practice, the fitting pairings UL 50 Table 71-1A tabulates; the cutouts and glands guide shows how they land on a stainless wall.
| Gland thread | Hole in the wall | Cable OD the insert clamps |
|---|---|---|
| 1/2 in NPT | 7/8 in (22 mm) | small control cables; the insert chart sets the range |
| 3/4 in NPT | 1-1/8 in (29 mm) | 0.3-0.5 in (8-13 mm) |
| 1 in NPT | 1-3/8 in (35 mm) | larger jackets; the insert chart sets the range |
Molded plastic and aluminum walls carry their own conventions, covered in the M20 gland hole-size article; a stainless bottom is simply cut to the table. Drilling a 7/8 in hole in a stainless panel for a 1/2 in NPT fitting is the classic entry job. Check the gland's own limits too: one published tray-cable gland line lists the gland body for -25 to +40 C ambient, with only the insulating bushing rated hotter. A cold-storage or unheated outdoor bottom deserves that datasheet read.
Sizing the gland and the hole for a 0.44 in cable
The case: five jacketed control cables leave a bank of seals under a solid bottom, each jacket reading 0.44 in (11.2 mm) OD, a plausible figure for a 12-conductor tray cable. Read the real value off the cable print before ordering anything. The inputs and their sources: the gland maker's insert chart, which for a 3/4 in NPT gland clamps 0.3-0.5 in (7.6-12.7 mm) of OD, and the knockout pairing that gives a 3/4 in NPT fitting a 1-1/8 in (29 mm) hole.
The rule: pick the smallest gland whose insert range covers the jacket; the thread size then fixes the hole. An oversized gland leaks around a loose insert, and an undersized insert cuts the jacket.
The arithmetic: 0.3 in x 25.4 = 7.6 mm and 0.5 in x 25.4 = 12.7 mm, so the insert range runs 7.6 to 12.7 mm. The jacket at 0.44 in x 25.4 = 11.2 mm sits inside, with 0.5 - 0.44 = 0.06 in (1.5 mm) of margin below the top of the range. The layout check: five holes at 1.125 in take 5 x 1.125 = 5.625 in, four gaps at 1 in (25 mm) of gasketed land add 4.0 in, and the bank needs 5.625 + 4.0 = 9.6 in (244 mm) of clear flange.
The result: five 3/4 in NPT glands with inserts for an 11.2 mm jacket, five factory-cut 1-1/8 in (29 mm) holes, and a 1 in land between the edges. The thresholds: under 0.3 in of OD, a 1/2 in NPT gland in a 7/8 in (22 mm) hole is the smaller answer; over 0.5 in, step to a 1 in NPT gland in a 1-3/8 in (35 mm) hole and read its insert chart for the range. The cutout designer checks the spacing against the real flange before anything is cut.
The steps, in order
- Settle the seal's job. Confirm the run stays non-classified. A run that crosses a classified area keeps its seal at the boundary and rigid conduit from there to the wall; the wall entry itself still follows the steps below.
- Lock the circuits out and verify the conductors dead before anyone opens the bottom.
- Secure and bond the raceway. Fasten each raceway or land it on a fitting made for the cabinet, and bond metallic raceway to the enclosure with a jumper sized from NEC Table 250.122. Nonconductive coatings come off the contact: NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding connections.
- Make the entries factory-clean. Order the holes cut with the box when the schedule allows. A field entry holds the rating when it is cut, deburred and sealed to the field-drilled conduit entry method.
- Fit the glands. Run sealant on NPT threads and wrench them home in metal. On a straight-thread gland, seat the washer on the flat land and compress it square.
- Bring the wire over and land it. Sleeve the conductor out of the seal, support the run so nothing hangs on the seal or the gland, and let the insert grip the jacket full round; the cable strain relief article covers the support hardware. Individual conductors go through a multi-hole sealing plate sized per wire. At the terminals, NEC 312.6 sets the bending space: 2.5 in for 2 AWG with one wire per terminal.
Checks when the wiring is done
- Pull each cable at the gland by hand: the jacket creeps nowhere, and the insert holds it full round.
- Megger the new runs at 500 V DC. IEC 60364-6 sets 1 MΩ as the floor for circuits up to 500 V, and a dry control circuit reads far above it.
- Confirm the bonding jumper lands on bare metal; the fault path stays metallic end to end, with the earth out of it.
- Walk the rating: every hole cut to the table above, gasket seated all round, unused openings closed with rated plugs. The article on what a panel keeps after you cut it and mount devices gives the full accounting.
- A hole drilled in the wrong spot has a sealing fix of its own, shown in the wrongly drilled hole article.
- Compare the gland datasheet's ambient range with the site; the published -25 to +40 C line rules out a freezer-room bottom.
Mistakes that cost the rating
- One slot cut for the whole bank. A slot destroys the gasketed land between entries; individual gasketed holes keep the rating.
- A gland with no published Type rating. Catalog lines carry footnotes such as "not NEMA 4 or 4X rated" on some variants, and that footnote, not the thread size, sets what the entry holds.
- Sealed threads around a floating jacket. Sealant on the threads does nothing for a cable the insert never gripped.
- A weep hole for condensation. NEC 314.15 permits approved drainage openings of 1/8 to 1/4 in (3-6 mm) in boxes and conduit bodies listed for damp or wet locations; on a washdown bottom, fit a drain plug rated for the enclosure type, and the assembly then sits at that plug's own rating.
- Loose conductors through a single-cable gland. The insert clamps a jacket; individual wires need the multi-hole plate from the steps.
Ordering the bottom with the entries already in it
Order the holes with the box and the job shrinks to layout. Count the penetrations first: a wall carries only so many holes before the lands get thin, and the penetrations article sets the count.
Then send the layout: custom enclosures take your material, size and every cutout from one piece, and are delivered in 10 business days, counted from your approval of the drawing. Pick 304 for indoor washdown and most outdoor sites, 316L for salt air, brine and chemical areas; the stainless range runs from 6 x 4 x 4 in up to 60 x 36 x 16 in (H x W x D). Our boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. A UL listed enclosure has been evaluated by UL to UL 50E, which is the listing some specifications ask for; on a bottom-entry panel, the entry work above is the first thing an inspector opens.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can the wire leave the conduit at the seal fitting and enter through a cable gland?
Yes, in a non-classified area. The NEC requires raceways secured to the equipment they enter and metallic raceways bonded, but it does not force conduit to continue to a termination inside the box. Terminate at a listed gland sized to the cable, protect the conductor between seal and gland, and keep each entry a factory-cut gasketed hole.
Does a cable gland keep the enclosure at its NEMA 4X rating?
The gland's published rating decides. Some gland lines carry a footnote marking the body as not NEMA 4 or 4X rated, and a lower-rated part pulls the whole assembly down to its level. Choose a gland published for Type 4X service, seat its sealing washer, and check its ambient too: one published line lists the gland body from -25 to +40 C. Our boxes are manufacturer-rated NEMA 4X / IP66, not UL listed.
What gland and hole fit a 0.44 in OD cable?
A 3/4 in NPT gland: the insert clamps 0.3-0.5 in (8-13 mm) OD, and 0.44 in (11.2 mm) sits 0.06 in inside the top of that range. The hole follows the thread at 1-1/8 in (29 mm), factory-cut. Under 0.3 in of OD, drop to a 1/2 in NPT gland in a 7/8 in (22 mm) hole.
Does the metallic conduit still need bonding when the wire exits at the seal?
Yes, and the gland makes the jumper mandatory rather than optional: the gland's insert grips an insulating jacket, so the plastic gland body breaks the metallic path the conduit relied on. Fit a bonding jumper from the raceway to the enclosure, sized from NEC Table 250.122 by the overcurrent device ahead of the run, and land it on bare metal; NEC 250.12 requires paint and enamel off the contact surfaces. A metal-bodied gland with a listed bonding ring can serve, if its datasheet shows it.