Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

One VFD two motors: sizing and overload protection

One drive runs two motors when its continuous output-current rating covers the two nameplate currents added: 15.2 A + 15.2 A = 30.4 A for two 5 hp, 230 V motors. Give each motor its own overload set to its nameplate current, wire both contacts in series into the drive's run permissive, and swap two leads at one motor for opposite rotation. Size the enclosure from the drive's heat loss, not its horsepower.

NEMA4 Enclosure engineering team · Published November 10, 2026 · 8 min read

Short answer: add the two motor nameplate currents and buy the drive on that sum. Two 5 hp, 230 V motors draw 15.2 A each, the value in the NEC full-load-current tables. The drive's continuous output-current rating must read 30.4 A or more. A 32 A plate carries both motors at full load; a 27 A plate trips. Each motor then gets its own overload set to its nameplate current, with its contact wired in series into the drive's run permissive. Swapping two leads at one motor makes it turn opposite the other. The enclosure comes from heat, not horsepower. The worked example below lands at 40 × 32 × 20 in [1016 × 813 × 508 mm] of stainless for a drive losing 180 W in a 25 °C room. The datasheet's own heat-loss figure replaces the example value.

Judge the drive by amps, not horsepower

A horsepower badge describes one motor at one load point. Two motors turn the check into arithmetic on currents. The NEC allows one circuit to feed several motors on that basis: each motor carries its own overload protection, and the supply side is sized for the combined load. So the first check happens at the drive's plate, not in a catalog.

The NEC full-load-current tables for three-phase induction motors give the working values:

Motor Full-load current at 230 V Full-load current at 460 V
3 hp 9.6 A 4.8 A
5 hp 15.2 A 7.6 A
7.5 hp 22 A 11 A

The common swap — one 7.5 hp motor out at 22 A, two 5 hp motors in — adds to 30.4 A at 230 V. Read the continuous output-current rating off the plate before you buy: 32 A or more carries both motors at full load, and 27 A does not, whatever the badge says. Size the circuit at nameplate even when the fan or conveyor load never reaches it. The conductors and the overload dials live there too. Fan arrays run three or more matched motors from one drive on exactly this rule, and the drive still sees only the total.

Each motor gets its own overload

The drive measures one current: the sum of both motor leads. Split that sum any way the load likes, and the drive stays content while one motor cooks — the imbalance never shows at the drive terminals. That is why the NEC asks for overload protection at each motor instead of one relay for the pair.

Set each relay to its own motor's nameplate current, 15.2 A here, on a dial range that brackets it, such as 12.5-18.5 A. Trip class matters for a stall. The IEC trip-class tables define class 10 as a trip within 10 s at 7.2 × setting — about 110 A on this dial. A jammed motor pulls roughly 6 × its nameplate current, near 91 A, so the relay clears the stall in seconds instead of letting the winding cook.

For combined overload and short-circuit duty at the drive output, a motor-protection circuit breaker at each motor does both jobs in one device. That is the arrangement drive makers document for multi-motor outputs. Turn the drive's own motor-thermal point to the combined 30.4 A, or off. Its electronic motor model cannot see how current divides, so it protects the drive and the cable. The two external relays protect the motors.

Wire the contacts so either relay stops the drive

Each overload's normally closed auxiliary contact — terminals 95-96 on a standard IEC-style relay — wires in series with the other one into the drive's run or enable input. The input needs a 24 V DC signal at a few milliamps, well inside a standard contact's rating. Either relay tripping drops the permissive, and the drive ramps down on its own stop setting, so nothing opens under load.

That shared stop is the design. A contactor interrupting a driven output breaks up to 30 A of inductive current, and its arc spikes the drive's output stage. Reclosing onto a live output drops full voltage onto a spinning motor and trips the overcurrent fault. So both motors start together, run together, stop together, and no contactor sits between the drive and either motor. Rotation becomes a wiring choice instead. Both motors see the same phase sequence, so swapping any two of the three leads at one motor's terminals makes it turn opposite the other.

When one motor faults, the whole drive stops — the accepted consequence of a shared output. If your process cannot live with both machines down for one bad motor, the fix is two drives rather than downstream contactors. You then size each of those panels with the enclosure sizing guide.

What goes on the backplate

The bill of materials is short. A drive is IP20 — open terminals with no drip or dust protection — so the box is not optional. The rail, duct and terminal layout rules live in the backplate and DIN rail layout guide.

  • Drive with continuous output of 30.4 A or more at 230 V (32 A in the example), plus a rated input current for the feeder math, 30 A here.
  • Input breaker at 40 A on an 8 AWG copper feeder. The NEC sizes drive input conductors at 125 % of rated input current: 1.25 × 30 A = 37.5 A, and 8 AWG carries 50 A at 75 °C in the NEC copper ampacity table.
  • Two overload relays with a dial range such as 12.5-18.5 A, each with one normally closed auxiliary contact.
  • One gland per motor cable. An M20 gland with a clamping range of about 8-14 mm holds a 0.47 in [12 mm] cable; see the cutouts, glands and windows guide before you mark any hole.
  • Wire duct filled to at most half its interior cross-section, the NFPA 79 fill cap the duct tables publish, because round cables leave air gaps.
  • Ground bus bonded to box and backplate. NEC 250.12 asks for paint removed from threads and contact surfaces at grounding connections, and NEC Table 250.122 sizes each equipment ground from its protecting breaker; the grounding and bonding guide walks the whole fault path.

Size the box from the heat load

Read the heat-loss figure from the drive datasheet. Call it 180 W for this example — about 2.4 % of a 7.5 kW output, in line with the 97-98 % efficiency figures drive datasheets print. Drives carry a usual 40 °C (104 °F) ambient limit; if your room sits at 25 °C, the walls can hold a ΔT of 15 K.

Stainless sheds heat at k = 3.7 W/m²K. At a 15 K ΔT that is 3.7 × 15 = 55.5 W/m², so the box needs 180 ÷ 55.5 = 3.24 m² of surface. A 40 × 32 × 20 in [1016 × 813 × 508 mm] enclosure offers 2 × (1.016 × 0.813) + 2 × (1.016 × 0.508) + 2 × (0.813 × 0.508) = 3.51 m². That surface carries 3.51 × 55.5 ≈ 195 W — the 180 W load with roughly 8 % spare.

The same box in a 35 °C washdown room holds a 5 K ΔT: 3.7 × 5 = 18.5 W/m². So 3.51 m² moves just 65 W against a 180 W load. That room gets an enclosure air conditioner, sized at 180 × 1.25 = 225 W with the usual margin, which makes a 300 W unit the pick. Inside, give the heatsink 4 in [100 mm] of clear air above and below, as most drive manuals ask.

Install it in order

  1. Confirm the drive plate: 30.4 A or more continuous output at 230 V, and note the rated input current for the feeder math.
  2. Lock out the feeder and confirm dead terminals with a meter before you land any conductor.
  3. Mount the cabinet so its door swings 90° with 3 ft [900 mm] of clear depth in front. That is the NEC 110.26(A) depth for a panel at 133 V to ground, inside the 0-150 V band; the mounting guide sets the heights and clearances. Set the drive with 4 in [100 mm] free above and below. Put the two overload relays on the rail nearest the gland exits.
  4. Land the 40 A breaker and the 8 AWG feeder; scrape paint from the ground threads and land the grounds on the bus.
  5. Run each motor circuit through its own overload to its own gland, holding the motor leads apart from the 24 V permissive pair.
  6. Set both dials to 15.2 A and wire the two normally closed contacts in series into the run input.
  7. Bump each motor uncoupled and read its rotation; swap two leads at one motor for the opposite direction.
  8. Set the drive's motor-thermal point to 30.4 A or off, give the ramp about 15 s for a fan-type load, torque the glands, and close the door on a seated gasket.

Checks when done

  • Clamp each motor lead at full load: each reads near its nameplate current and none exceeds its dial.
  • Press the test button on each overload in turn; the drive stops both times, inside its ramp.
  • Compare the two motor currents: a balanced pair sits within about 10 % of each other, and a wider split points at a dragging machine.
  • Run an hour and check the air near the top of the box against the drive's 40 °C limit.
  • A gland, cutout or accessory below the enclosure's rating drags the whole assembly down to that part's rating, so every entry gets the same care as the plate.

Mistakes that cost the motor or the rating

  • One relay for both motors: the drive reads 30 A and sits content while one motor burns. Set a dial per motor.
  • A contactor between drive and motor to pick machines in and out: interrupting a driven output arcs and trips the drive. Command the drive instead.
  • The drive's motor-thermal point left at one motor's nameplate current: it trips at half the combined load. Set it to 30.4 A or off.
  • A gland smaller than the cable: the seal never made contact, and the first hose-down finds the electronics. Match gland to cable OD.
  • Sizing by horsepower: a badge reading 10 hp can hide a 27 A output, and a 32 A plate beats the badge every time. Read amps.
  • Duct packed past half full: the 50 % cap exists because round cables leave air gaps. Split the runs or upsize the duct.

What to order

  • Indoor, dry and clean: a Type 12 painted-steel box passes; the rating pairs live in the NEMA types guide.
  • Washdown, hose-down, outdoors or salt air: 304 stainless, moving to 316L where chlorides or brine live, rated NEMA 4X / IP66 by the manufacturer; not UL listed.
  • A hot room: add the 300 W air conditioner to the same order.
  • The layout: mark every gland position on the drawing when you order. Configure it in the 3D enclosure builder or start from our custom stainless enclosures, and the box is delivered in 10 business days from your approval of the drawing.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can a 10 hp VFD run two 5 hp motors?

Judge it in amperes. At 230 V the NEC full-load tables give 15.2 A per 5 hp motor, so the plate must read 30.4 A or more of continuous output. At 460 V the same motors draw 7.6 A each — 15.2 A total — and a drive rated 20 A qualifies. The horsepower label decides nothing on its own.

Why does each motor need its own overload relay?

The drive reads only the total: 22 A on one motor beside 8 A on the other still sums to 30 A, under a 32 A plate, so no drive fault comes while the loaded motor cooks. A relay set to the 15.2 A nameplate trips the run permissive instead; a class 10 unit acts within 10 s at 7.2 × setting, about 110 A.

Can the second motor start later than the first?

Closing a contactor onto a live output drops drive voltage across a standing motor: the 32 A output sees the second motor at zero speed as a fault step, and the overcurrent protection acts. Start both from the drive's single run command with the ramp set; staggered duty is a case for one drive per motor.

What changes with three motors on one drive?

The rule scales and the box does not. Three 5 hp, 230 V motors total 45.6 A, so the plate needs a 46 A-plus output. At the example's loss share — 180 W on 7.5 kW, near 2.4 % — a drive carrying 11.2 kW loses about 270 W, which takes more than stainless walls shed in a warm room. Plan the air conditioner into the layout.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides