Diagonal lines that crawl across the screen whenever the VFD spins the motor are common-mode noise from the drive output, and the cure comes in a fixed order. Run a dedicated ground wire from the drive's PE terminal to the motor frame, sized equal to the phase conductors: 12 AWG on a typical 12-15 ft spindle run. Twist the three motor leads and put them in metal conduit bonded at both ends. Clamp the motor cable shield 360 degrees at the enclosure wall, right where the cable enters. Buy shielded motor cable cut to length only for a run that stays noisy after all three fixes, because the grounding work costs an hour with hand tools and short-length cable is a special order by the foot. The numbers below show why the order matters, and the checks tell you when the cable earns its place on the order.
Why does a VFD put lines on the computer screen?
The lines are switching noise from the drive output: each PWM edge pushes a burst of charging current into the motor cable's capacitance, and any of that current returning through the PC chassis, the video cable or the controller wiring shows up on screen as diagonal interference. The pattern in front of you tells you where the noise lives:
- Lines only while the output runs, worse as speed rises: the noise rides the motor leads.
- Worst during acceleration and deceleration: edge current peaks during ramps.
- Lines with the motor stopped but the drive enabled: the output still switches at the carrier frequency (2-4 kHz on most small drives), so the drive is never actually quiet.
- Flicker or resets on other equipment sharing the bench: the return path is shared, not merely observed.
- A clean display with the drive powered and the output disabled: the PC, its supply and the display are innocent, and the fault is downstream.
Take that last check first as the baseline, before any wire is moved.
How does drive noise travel from the motor cable to the screen?
The output edges charge the cable's capacitance to ground, and that return current — amps at each edge, not milliamps — comes home through whatever metal is nearest, which is why a missing ground wire can turn a screen a few feet away into a noise indicator.
Worked example: a 4 m [13 ft] spindle run on a 230 V class drive. Three assumptions set the scale, and you should replace each with the real figure from your datasheets: 150 pF of charging capacitance per metre of cable per phase (typical for shielded motor cable), an output edge rising 3,000 V in 1 µs (3 kV/µs, typical for a small IGBT output), and a 4 kHz carrier frequency.
- Charging capacitance per phase: 150 pF/m × 4 m = 600 pF.
- Current per edge: I = C × dv/dt = 600 pF × 3 kV/µs = 1.8 A for about a microsecond.
- Edge count at 4 kHz: each phase switches twice per cycle, so 8,000 edges per second per phase and 24,000 across three phases.
A 0.1-0.2 µs edge concentrates its energy near 2-4 MHz, and up there a wire stops behaving like a wire: inductance, roughly 1 nH per millimetre of length, sets the impedance, not resistance. The same 12 AWG conductor that carries the 60 Hz current without warming can present several ohms to a 1.8 A edge burst. Wherever that burst returns — machine frame, PC chassis, video cable shield — a few volts of switching voltage land on metal you are watching through. On larger drives the same current also trips ground-fault protection; the isolation approach in why a drive keeps tripping on ground fault applies once the return path is fixed.
Which fix clears VFD screen noise first?
Fix in this order — dedicated ground wire, then twisted leads in bonded metal conduit, then the shield clamp at the enclosure wall, then the control cable — because each step closes a return path the next step depends on, and the first three together clear most short runs. The causes, most likely first, with the check for each:
- No dedicated ground from drive to motor frame. The most common gap on a retrofitted spindle. Measure continuity from the drive PE terminal to the motor frame; a frame bonded only to the machine base leaves the loop wide open.
- Motor leads loose in non-metallic flex. Rubber or plastic flex shields nothing. Identify the conduit material and measure from drive enclosure to motor housing through it.
- Shield landed as a long pigtail inside the box, or not landed at all. Look at the cable entry: a clamp at the wall, or a drain wire wrapped onto a terminal a hand's width away?
- Controller-to-drive signal wiring in ribbon or loose hook-up wire. Parallel signal-and-return runs make a fine receiving antenna; move to shielded twisted pair and follow the one-end bonding logic in why control-cable shields bond at one end.
- PC or controller chassis ground open. Measure from the PC case to the enclosure ground bus: a fraction of an ohm is a bond, and more than about 1 Ω means the chain is broken.
Steps 1 and 2 cost an hour and a handful of fittings. Spend them before spending on cable.
How big should the ground wire from VFD to motor frame be?
Size the ground wire from drive PE terminal to motor frame at least equal to the phase conductors — 12 AWG on a 12-15 ft spindle run — because IEC 60364 earth sizing calls for equal cross-section up to 16 mm² and drive grounding guides keep the motor PE matched to the phases. One conductor then does two jobs. It is the protective earth for the circuit, which NEC Table 250.122 sizes from the overcurrent device ahead of the drive — 12 AWG copper for 20 A — and it is the high-frequency return for the edge bursts in the worked example. Run it in the same conduit as the phases and twist it with them, so the loop stays small.
High frequency is where size alone stops helping. Skin depth in copper at 3 MHz is about 0.04 mm, so edge current rides a thin shell and extra diameter buys little. Drive grounding guides answer with surface instead: a second conductor, a flat strap, or the cable's braided screen. One major drive maker's grounding manual accepts the cable's symmetric PE conductor for motor ratings up to 100 kW, which covers most spindle and small-machine drives.
Land both ends on bright metal. NEC 250.12 calls for paint, lacquer and enamel cleared from threads and contact surfaces at grounding connections, so scrape the motor frame boss and bite the enclosure boss with the lug and toothed washers.
Should the three motor leads be twisted and run in metal conduit?
Yes — twist the three phase leads tightly along the full run and get them into metallic conduit bonded at both ends, because the twist shrinks the loop between phases and a bonded conduit wall gives the edge current a metal return running right beside them. Twist with a consistent pitch, tight enough to hold itself and loose enough not to nick insulation.
Rubber-jacketed non-metallic flex, however tidy, carries no return current at all; the shield duty needs metal. Flexible metal conduit bonded at both ends does the job, with fittings that bite bare metal at the drive enclosure and at the motor housing. Prove it with the meter: drive enclosure to motor frame through the conduit should read a fraction of an ohm, the same bond threshold as the chassis check above.
If the conduit fails that test — plastic core, or an unbonded fitting mid-run — the metal return does not exist, and that is the exact case where shielded cable earns its keep. For the hardware at the drive end, locking connector or conduit at the motor cable entry compares the two ways in.
How does the motor cable shield terminate at the enclosure wall?
Terminate the shield 360 degrees at the enclosure wall, at the cable entry itself, using an EMC-style gland or clamp ring, the standard instruction in drive grounding manuals, because a long pigtail to an interior stud measures roughly ten times worse at the edge frequencies. The worked example shows why. A 100 mm [4 in] pigtail of drain wire carries about 100 nH of inductance at 1 nH per millimetre. Its impedance at 3 MHz is X = 2πfL = 2π × 3,000,000 Hz × 0.0000001 H ≈ 1.9 Ω. A 360-degree clamp meeting the wall within millimetres presents roughly a tenth of that, about 0.2 Ω. At the example's 1.8 A edge bursts, the pigtail lifts the shield about 3.4 V off the wall while the clamp holds it near 0.4 V — ten times less voltage pushed into everything nearby.
Inside the box, keep the entry honest. Keep the unscreened tail between gland and drive terminals short; 0.3 m [12 in] is a sensible ceiling. Keep at least 100 mm [4 in] between motor leads and signal wiring, and cross unavoidable crossings at 90 degrees. The hardware choices are laid out in terminating shielded cable at glands or connectors, and the cabinet layout in shielding VFD motor and remote wiring in a steel enclosure.
If the run needs a splice or a terminal transition, put it in a metal box and carry the shield through: clamp at the entry gland, clamp at the exit gland, both bonded to the same wall. A shield that stops at a terminal block ends the shielding at the worst possible spot. A stainless junction box with a gasketed door does this and keeps the run sealed.
Guard the box's rating while you work. These stainless wall-mount enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and the rating survives only when every gland matches it and every unused cutout carries a plug. The weakest accessory sets the assembly rating, so a drip vent on a washdown box hands the rating back.
Do the control cable in the same session: shielded twisted pair from controller to drive, motor-cable shield clamped at both ends, signal shields bonded per their own rule. The difference between the two shield rules is covered in one-end versus both-end shield grounding practices.
When is it worth buying short-length shielded VFD cable?
Buy shielded motor cable once the grounding fixes still leave lines, or once the conduit cannot be bonded continuously end to end — and order a cut length, about 17 ft for a 12-15 ft run, because the reel sizes sold for long runs start at 100 ft. Pick the construction before the brand: conductors at least the size of the existing phases, a symmetric PE conductor in the same jacket, and a braided shield thick enough to take a 360-degree clamp. Foil-only screens handle neither flexing nor clamping well.
Motion and chain-cable makers sell VFD cable by the foot, which is how a 13 ft run stays a 13 ft purchase. Add about 30 percent for termination slack and a service loop: 13 ft × 1.3 ≈ 17 ft. Terminate both ends the same way, clamp at the drive gland and clamp at the motor junction box, with any pigtail kept under 25 mm [1 in].
Whether the cable is necessary at all is the earlier question, and the same logic that decides servo axes in when shielded servo cable actually helps decides a spindle run: grounding and bonding first, cable only for what survives them.
How do you prove the noise is gone and keep it away?
Prove the fix with the drive enabled and the motor stopped first, then at low, medium and full speed, then through an acceleration and deceleration ramp, because edge current peaks during ramps and any coupling left in the system shows itself there first. The sequence, four steps:
- Drive powered, output disabled: the baseline. Lines here point at the PC, its supply or the display.
- Drive enabled, motor stopped: the output still switches, so lines here condemn the motor circuit while the load contributes nothing.
- Low, medium and full speed: interference that tracks speed rides the motor leads.
- One acceleration and one deceleration ramp: the worst case, where remaining coupling shows first.
The carrier frequency is the last lever, after the wiring is right. Halving it halves the edges per second: 8,000 per phase per second at 4 kHz becomes 4,000 at 2 kHz. The trade is noise you hear rather than see, because the motor hums louder at low carrier, and high carrier settings often call for output derating in the drive manual.
Keep it fixed with two habits: re-check the conduit bond after any machine move, since flex conduit work-hardens at its fittings, and re-torque the gland clamps after servicing.
And when the box itself is plastic, this is the moment to re-specify. A fiberglass or polycarbonate enclosure offers no wall to clamp to and no return plane, so every fix above leans entirely on the cable. A stainless wall-mount enclosure — hinged gasketed door, removable mounting panel, wall-mount feet — rated NEMA 4X / IP66 by the manufacturer, not UL listed, gives the shield a wall and a corrosive washdown a corrosion rating. Choose the size in 316L NEMA 4X wall-mount enclosures and land panel, door and glands on one earth following the enclosure grounding and bonding guide.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much extra noise does every metre of motor cable add?
At the worked example's assumptions — 150 pF per metre per phase and a 3 kV/µs edge — each metre adds 0.45 A of edge current, since 150 pF × 3 kV/µs = 0.45 A. A run that grows from 4 m to 10 m therefore carries 4.5 A per edge instead of 1.8 A, and that is why long runs deserve a real cable shield while short runs often clear with grounding alone.
Can a VFD live in a plastic enclosure and still stay quiet?
It can run, but two of the three fixes weaken. A plastic wall offers no surface for a 360-degree shield clamp and no low-impedance return plane, so the enclosure contributes nothing and the shields must land on a bonded bus bar. Metal is the assumption behind every drive grounding manual. In a washdown or corrosive corner, a stainless wall-mount enclosure rated NEMA 4X / IP66 by the manufacturer (not UL listed) provides both the EMC wall and the corrosion rating.
What does changing the carrier frequency actually do to the noise?
It changes the count of edges, not their size. Each phase makes two edges per PWM cycle: 16,000 edges per second at 8 kHz, 8,000 at 4 kHz, 4,000 at 2 kHz. Halving the carrier halves the noise events, while each edge still delivers the same current burst into the cable capacitance. The trade is acoustic — the motor hums louder at low carrier — and many drive manuals call for output derating at high carrier settings.
Will hook-up wire in flexible metal conduit work instead of shielded cable?
On short runs it usually does. Twisted phase conductors inside flexible metal conduit bonded at both ends behave like a shielded cable, with the conduit wall doing the shielding. Keep the ground wire equal to the phases — 12 AWG beside 12 AWG, for example — and prove the bond with a continuity reading well under 1 Ω from drive enclosure to motor frame. If the conduit is non-metallic or the bond cannot be proven, order the shielded motor cable.





