Short answer: latch the drive fault in a retentive PLC bit that only an operator acknowledge clears, wire the stop input and the fault reset as separate outputs, and set the drive's auto-restart tries to 0 for attended machinery. Left as found, a scheme that stops the drive by dropping its stop input also resets it: a genuine overload clears itself and the drive restarts — the example timing below works out to about 1,200 attempts per hour on a 3 s cycle, into a winding that is shorted to ground. The drive resetting itself was never the real danger. The system restarting itself was.
What the restart loop looks like
You will usually meet this on a line that trips and comes back with nobody at the panel. Match your symptom to the layer it points to; the checks in the next section separate the causes in about ten minutes.
- Trips, the PLC drops the enable, the drive runs again within seconds, loop repeats. Points to a control scheme that resets the drive as a side effect of stopping it.
- Display shows the fault, then healthy, then running, all inside a minute. Something at the drive layer clears the fault: the stop input, a control-power blink, or the drive's own auto-restart.
- The fault clears exactly when the enable relay clicks off. Stop and reset share one output or one relay contact.
- The drive self-resets with the PLC output forced off and the stop input still connected. The drive's auto-restart parameters are live and the wiring is innocent.
- Real overload trips that cluster on hot afternoons. The logic is fine and the enclosure is the problem; skip to the last section.
Why the fault clears with no reset command
Some legacy drive families list three reset paths in the manual: the local Stop key, a control-power cycle, and removing the stop input. The third one is the trap. Any design that stops the drive by opening the stop input issues a fault reset every single time it stops.
The wiring turns that trap into a loop. One PLC output drives a 24 V DC interposing relay labeled "drive enable", and that single relay ties the input common to both the stop input and the start input at once:
| Terminal | Function | Enable output ON | Enable output OFF |
|---|---|---|---|
| Input common | reference for both inputs | connected | connected |
| Stop input | stop circuit satisfied | tied to common | open, and on these drives an open stop resets the fault |
| Start input | run command | tied to common | open |
So the PLC's fault response, "fault seen, drop the enable output", performs a reset one scan later. The drive's fault contact goes false. The controller, holding an unlatched input, sees a healthy drive, passes the permissive chain, and fires the start again. A momentary fault contact was used as if it were a maintained condition, and nothing in the controller remembers the trip.
NFPA 79, the electrical standard for industrial machinery, is built on preventing unexpected start and restart; three-wire start/stop control with a seal-in contact exists for that reason. A drive that resets itself and accepts a still-held run command reintroduces, at the drive layer, exactly what three-wire control prevents at the contactor layer.
How to confirm which cause you have
Watch the drive display through one trip first. If the fault clears the instant the enable relay clicks off, the stop input doubles as the reset and your wiring is the cause. If the fault stays on the display after the relay drops, the drive's own auto-restart is the cause.
Then force the test. Switch the enable output off in the controller and jumper the stop input to its common by hand:
- Fault clears anyway → the auto-restart parameter is live; go to the parameter section below.
- Fault stays displayed → the wiring performed the reset; go to the fix below.
Time one full loop as well, because the number tells you what the wiring has been doing to your motor. These are worked-example values, so replace them with your measured times: trip at t = 0, PLC input scan 10 ms, the enable relay releases in 15 ms, the drive clears the fault 0.5 s after the stop input opens, and the auto-start logic refires within 2 s. One loop is 0.01 + 0.015 + 0.5 + 2 = 2.525 s; call it 3 s with ramp time.
3,600 s ÷ 3 s ≈ 1,200 restart attempts per hour. Each retry can push up to 150% of rated output current into the fault, the 60 s overload point on a general-purpose drive curve. On a 5 hp (3.7 kW), 460 V motor with about 7.6 A full-load current (the NEC motor table value), that is 7.6 × 1.5 = 11.4 A hammered into a winding already shorted to ground, 1,200 times per hour. The cycle also wipes the fault off the display before anyone reaches the panel, which is how a real electrical failure hides behind a line that keeps running.
The fix: latch the fault, split stop from reset
Four changes, in this order:
- Latch the fault in the controller. Set a retentive bit when the fault input arrives. The bit survives a control-power blink, which matters because a power cycle is itself a reset path on these drives.
- Gate the acknowledge. An operator pushbutton clears the latch, but only once the raw fault input has dropped. The controller clears the momentary pushbutton bit itself, so a stuck HMI write cannot acknowledge forever. Clearing an alarm and acknowledging a machine fault are different actions in a controller, and the difference is set out in clearing alarms versus acknowledging faults in a PLC.
- Write the enable output in one place. One rung: run request AND NOT fault latch AND the rest of the permissives. Two writers to one coil is how the shared-relay pattern creeps back in.
- Split stop from reset. Output A holds the stop input tied to common whenever the machine is enabled. Output B carries the start command. The fault reset becomes its own momentary output to a dedicated drive reset input, commanded deliberately and visible at the door.
The latch logic, with illustrative names, types and initial values:
Fault_Raw : BOOL := FALSE; // drive fault contact input
Fault_Latch : BOOL := FALSE; // retentive: TRUE means fault captured
Ack_PB : BOOL := FALSE; // HMI acknowledge pushbutton, momentary
Run_Req : BOOL := FALSE; // auto-start permissive chain
Enable_Out : BOOL := FALSE; // drive enable relay coil
Fault_Latch := Fault_Latch OR Fault_Raw; // set on any fault
IF Ack_PB AND NOT Fault_Raw THEN
Fault_Latch := FALSE; // clear only after contact drops
Ack_PB := FALSE; // kill a stuck button write
END_IF;
Enable_Out := Run_Req AND NOT Fault_Latch; // written here, nowhere else
The test that proves it: force Fault_Raw TRUE for one scan and drop it, and Fault_Latch holds while Enable_Out stays FALSE. Pulse Ack_PB while Fault_Raw is still TRUE, and the latch refuses to clear. Pulse it after the contact drops, and the latch clears while the button bit resets itself. Repeat trips now need a person each time.
Add the lockout so an impatient operator cannot cycle a marginal fault: count the trips, and at 3 trips inside a 10 min window set a lockout bit with its own alarm; a supervisor key switch clears the counter. After the split, the PLC removes the start command and leaves the stop input satisfied, so the fault stays on the drive display for diagnosis. The drive may still reset itself internally, and that is fine. The system cannot restart itself, and that was the problem. Before the first restart after a motor failure like this, megger the motor leads phase-to-ground and phase-to-phase; the loop fix does not repair a shorted winding.
Set the drive's auto-restart on purpose
Read the two auto-restart parameters from the keypad or the drive software: the number of tries and the delay between them. Drive makers run the try counter inside a trail window that starts at the first restart, so 3 tries means 3 automatic restarts inside that window. For attended machinery set tries to 0 and let the PLC latch own the decision. The one case where auto-restart earns its keep is an asset nobody attends — a remote irrigation pump is the classic example — and there a starting pair of 3 tries at a 10 s delay keeps a nuisance trip from costing a site visit. Record the as-left values in the machine documentation so the next person who opens your panel inherits a decision instead of a mystery.
Many current drives behave better by design: the auto-restart sequence aborts on a stop command from any source, on a reset command, on removal of the enable input, and on a parameter change. The stop-input reset trap is mostly legacy behavior. Keep the PLC latch and the operator acknowledge anyway, because they stop a genuine repeating fault from cycling restarts.
Door hardware, terminals and the order
The fix has a face on the enclosure door. Three devices cover most panels: a red fault light, an acknowledge pushbutton, and a supervisor key switch for the lockout; add the reset pushbutton wired to its dedicated input when the drive takes one. Cutout positions for all of them belong on the drawing. The guide to enclosure cutouts, glands and HMI windows covers placement and sealing, and adding an external fault reset push button to an enclosure door covers the wiring habit: reset on its own terminals, away from the stop circuit.
Split the circuits at the terminal blocks too: stop, start and reset each get a labeled group, so the next person cannot bridge them back into one relay. The backplate and DIN rail layout guide keeps those groups and their relays physically separated, and the VFD enclosure wiring checklist covers the bond and filter side of the same panel. Pick the material by environment, set the size and cutouts in the enclosure builder, and the box is delivered in 10 business days, counted from your order or, for custom work, from your approval of the drawing.
When to re-specify the enclosure
Re-specify when the trips are real rather than spurious. Genuine overload trips that cluster on hot afternoons usually mean the sealed box sits above 40 C (104 F), the ambient at which most drives deliver rated output before derating; the answer is size and cooling, and sizing a VFD enclosure from heat and clearance works that arithmetic. Re-specify when the door grows devices it has no holes for: fault light, acknowledge button, key switch and reset pushbutton want four cutouts at operating height, cut once into a custom door instead of field-drilled later. On a washdown line, a 316L door station rated Type 4X / IP66 by the manufacturer carries all four devices and hoses down clean afterwards; those are manufacturer ratings for the specified design, and the enclosures are not UL listed. Custom stainless enclosures start from your size and cutout list, one piece minimum, with the drawing sent back for your approval before anything is cut.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a control-power dip also clear the fault?
Yes. A control-power cycle is a documented reset path on these drives, so a brownout that blinks the control supply also wipes the drive's fault memory. That is the case for keeping the latch in the PLC rather than only in the drive: a retentive bit holds the fault through the dip, so the drive may forget the trip but the system still refuses to restart until an operator acknowledges.
How many auto restarts should the drive be allowed?
For attended machinery, set the tries parameter to 0 and let the PLC latch own restarts. For an unattended asset, a remote irrigation pump is the classic case, start at 3 tries with a 10 s delay and confirm the drive's trail window, which counts restarts from the first one. Treat about 5 tries as the ceiling; more just hammers a possibly damaged motor.
What should the motor read before restarts are allowed again?
Megger phase-to-ground and phase-to-phase at 500 V DC. A dry 460 V stator reads in the hundreds of megohms; a reading under about 1 MΩ confirms the ground fault, and that motor stays out of service. Phase-to-phase resistance should balance within about 5%. The logic fix changes the control side only; it does nothing for the winding that started the loop.
Why is the acknowledge refused while the fault light is still on?
Because acknowledging a standing fault would let the permissive chain refire the start into the same fault within one 10 ms scan. Gating the acknowledge on the raw fault input forces the trip to drop first, and clearing the pushbutton bit inside the controller kills a stuck HMI write that would otherwise acknowledge continuously.