Short answer: a trash room that gets hosed down is a wet location, and the panel that lives there needs a manufacturer-rated NEMA 4X / IP66 stainless wall-mount enclosure with factory cutouts — not a field-punched steel box. Use 304 stainless for detergent washdown and 316L where chlorinated sanitizers run daily. Set the bottom of the box about 5 ft [1.5 m] above the slab, out of the 2-3 ft [0.6-0.9 m] splash band that floor washing leaves on the walls. The room sets the rating for the 120 V supply and the 24 VAC Class 2 controls alike; the low-voltage side never relaxes it. The sections below settle the rating, the grade, the size with the heat math, and the lines to put on the order.
What rating does a trash room with a hose bib need?
Write NEMA 4X / IP66 on the panel spec: NEMA 250 tests a Type 4 box against a 1 in nozzle throwing 65 gal/min [4.1 L/s] of water from 10 ft for 5 min, and that is the closest standard test to a cleanup hose worked around a room.
The hose bib tells you the room is cleaned wet, so the enclosure needs jet protection rather than drip protection. Type 4X adds corrosion resistance on top of the hose shot: the standard puts a 4X box through 200 h of salt spray and grades it against an AISI 304 specimen. The same tests also cover rust, icing, oil and coolants, which is why the type number carries more than one water trial. Our stainless wall-mount boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed — NEMA writes the standard and the tests, and the maker builds to it and declares the rating. The NEMA 4X vs IP66 guide gives the full side-by-side.
Is a trash room with floor drains a wet location?
Yes — a room cleaned by hosing its floor is subject to saturation with water, the NEC's wet-location case, so every box in that room needs hose-down protection and a Type 3R rain-and-drip box is not enough.
The drains are the tell. A floor drain exists because someone expects water on that slab, and the hose bib beside it says the water arrives under pressure. Walls in such a room get wet from splash and spray bounce on every cleaning shift, and the wet-dry cycle repeats daily. NEC Table 110.28 lists which enclosure types suit which conditions, and pressurized wash water puts a box at the Type 4 level, well above the Type 3R level built for rain and drip. The 3R vs 4 comparison walks that gap in detail.
Splash also sets height. Water bounced off a wet slab climbs 2-3 ft [0.6-0.9 m] up the wall during floor washing, which is why the panel hangs at 5 ft [1.5 m] rather than at switch height. Anything that must sit low moves into a dry chase outside the wash zone.
Type 4X or IP66: which one goes on the spec?
Both: NEC 110.28 states that IP ratings are not a substitute for enclosure type ratings in US installations, so the submittal carries NEMA 4X and IP66 together, and one manufacturer-rated box delivers the pair.
The codes prove different things. NEMA 250 runs the hose shot and the corrosion grade above, and adds rust, icing, oil and coolant tests. IEC 60529 reads digit by digit: IP66 means dust-tight from the first 6, plus powerful jets from the second — a 12.5 mm nozzle at 100 L/min from 2.5 to 3 m. Neither rating includes immersion, so IP66 is not IP67 and the box still hangs above flood level in a room with drains. The practical overlap is close, which is why our catalog boxes carry both marks; the IP rating chart decodes any other pair you meet on a drawing.
Can you keep knockouts and stock junction boxes in the room?
Order factory cutouts and skip the field punch: a knockout driven through stainless on site breaks the gasketed edge the rating rides on, and a general-purpose steel box from the supply house is a rain-and-drip construction at best.
This is where ratings die in the first year. The panel arrives with cutouts made to your drawing, each sealed by a gasketed hub or a cord grip sized to the cable; the cutouts and glands guide shows the options. Field entries can still hold the rating, but they follow the drill-tap-seal discipline in field-drilled conduit entries, and any device mounted through a wall folds into the assembly per what a panel keeps after you cut it. The 120 V feed drops in through a hub or a wet-location flex connector.
Splice boxes are the usual weak point. A standard 4 in square box with a flat blank takes water through its cover seam and fills. The wet-location versions NEC 314.15 describes take drainage openings of 1/8 in [3 mm] to 1/4 in [6 mm], which sheds rain and still is not hose-down construction. Put gasketed cast wet-location boxes on the room walls, mount them above the splash band, and bring the 4-conductor Class 2 cable in through cord grips whose clamping range matches the jacket — a typical 1/2 in gland clamps 0.16-0.31 in [4-8 mm].
Which stainless grade survives trash-room washdown?
Pick 304 for detergent-and-water washdown and step to 316L when chlorinated or acidic sanitizers run daily: chloride deposits pit 304 at room temperature, a different attack from the salt-spray grade behind the 4X rating.
Trash-room chemistry is milder than food-plant chemistry — detergent, water, maybe a quaternary disinfectant — and 304 handles it for decades. The decision turns on chlorides. Bleach-based sanitizers leave chloride deposits in gasket crevices and corners, and 304 pits at those deposits even without heat; the molybdenum in 316L raises pitting and crevice resistance for exactly this duty. Stress-corrosion cracking sits above about 60 C (140 F) for both grades, so tepid washdown water stays clear of it — pitting is the risk here, not cracking. Coastal salt air through the loading door argues for 316L the same way. The 304 vs 316L guide carries the full comparison, and why wet-dry cycling rusts 316L explains the brown film that rinses off.
Door gasket material matters as much as the alloy. EPDM rubber takes detergent water and stays flexible from about -50 to 150 C; silicone spans about -60 to 200 C but abrades. Either suits a trash room.
What size box fits a Class 2 supply and its controls?
A 16 x 16 x 6 in box carries this panel: its 15.88 x 15.88 in mounting panel holds two DIN-rail rows for the supply and relays, and 5.88 in of inside depth clears a 4.5 in transformer stack on a 0.5 in standoff.
Work the numbers. Under the NEC's Class 2 power tables, a single Class 2 output at 24 VAC tops out at 100 VA, so take a 100 VA supply, four 24 VAC relay modules and a terminal row. Two rails across 15.88 in give 31.8 in of module space; this stack uses about 20 in and leaves 11.8 in for spares. Depth: 5.88 in minus the 0.5 in panel standoff leaves 5.38 in; the deepest device sits 4.5 in off the rail, so the door closes with 0.88 in to spare.
Heat settles it. Dry-type transformer losses run about 1-3% of rating, so take the high end: 3% of 100 VA = 3.0 W, plus two relay coils energized at 0.5 W each = 4.0 W. Exposed wall of the 16 x 16 x 6 in box is the 256 in² front plus four 96 in² faces = 640 in² = 0.413 m². At the stainless wall figure of 3.7 W/m²K, the rise is 4.0 / (3.7 x 0.413) = 2.6 K, so at 35 C ambient the inside sits near 38 C — under the 40 C ambient most 24 VAC control gear carries. Step to the 20 x 16 x 6 in box and the same load rises only about 2.2 K, which is the margin to buy for a second supply. The 16 x 16 x 6 in 304 enclosure and its 316L version cover the single-supply panel, and the stainless size finder filters the range by grade and size.
Rail layout follows the backplate and DIN rail guide, NEC 312.6 sets the wire-bending space at the 120 V terminals by conductor size, and the enclosure sizing guide extends the math to bigger panels.
How do you mount and seal it so the rating holds?
Set the box bottom at 5 ft [1.5 m], keep 3 ft [900 mm] of clear working space in front under NEC 110.26(A), close every entry with a gasketed hub or cord grip, and leave the box sealed — one breather or drain re-rates the whole assembly.
Four points carry the install. Height: splash tops out at 2-3 ft and the hose points at the floor, so 5 ft of wall keeps the door out of the wash; a jet played straight at the door from 2 ft sits outside what the Type 4 test measures, which starts at 10 ft. Working space: NEC 110.26(A) asks 3 ft [900 mm] clear in front for 0-150 V-to-ground equipment in Condition 1, with the door free to swing 90 degrees.
Bonding: land the equipment grounding conductor on the box, sized from the overcurrent device ahead of it per NEC Table 250.122. Bare stainless arrives with conductive threads, and NEC 250.12 has coatings stripped from bonding surfaces if the box ever gets painted. Sealed means sealed: a vent or drain fitted later drags the assembly to that part's lower rating, as the breather vent article works through.
One safety line belongs here: lock out the 120 V feed and verify absence of voltage before the first entry. If a floor drain ever backs up, a wet floor sensor on the wall alarms the office before water reaches the panel.
What do you put on the order?
Order a manufacturer-rated NEMA 4X / IP66 stainless wall-mount box in 16 x 16 x 6 in or 20 x 16 x 6 in, 304 or 316L by the cleaning chemistry, with factory cutouts on your drawing and delivery in 10 business days, counted from the order or from your approval of the drawing when the cutouts are custom.
The 20 x 16 x 6 in 304 enclosure and its 316L twin are the rail-headroom picks, and the wall-mount line lists every size in both grades; the enclosure selector narrows a shortlist by environment and inside size.
| Line | Order it as |
|---|---|
| Rating | Manufacturer-rated NEMA 4X / IP66; not UL listed |
| Material | 304 stainless; 316L under daily chlorinated sanitizers or salt air |
| Size | 16 x 16 x 6 in outside, 15.88 x 15.88 x 5.88 in inside; 20 x 16 x 6 in for rail headroom |
| Cutouts | Factory cutouts: cord grips for the 4-conductor Class 2 cable, hub for the 120 V feed |
| Mounting | Wall-mount feet; bottom at 5 ft [1.5 m]; 3 ft [900 mm] clear in front |
| Sealing | Gasketed door as delivered; no field drains or vents |
| Grounding | EGC sized per NEC Table 250.122; bare bonding threads |
Then the decision by room. Hosed with detergent only: 304, NEMA 4X / IP66, bottom at 5 ft [1.5 m]. Chlorinated sanitizer or salt air every shift: the same box in 316L. Panel outside the wet room, in a dry closet: the room stops setting the rating and a standard indoor box does the job. Hose played against the door at close range every wash: move the panel or fit a stainless shield, because the Type 4 hose test starts at 10 ft [3 m].
Enclosures in this article
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 16 × 6 in | 304 stainless | 16 x 16 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 16 × 6 in | 316L stainless | 16 x 16 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 6 in | 304 stainless | 20 x 16 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 6 in | 316L stainless | 20 x 16 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does the 24 VAC Class 2 wiring relax the enclosure rating?
No. The room sets the rating for the whole box, line side and Class 2 side alike, and both live behind the same NEMA 4X / IP66 door. Keep the 24 VAC load wiring in listed Class 2 cable, separated from the 120 V conductors as the NEC's Class 2 rules ask, and feed it from a listed Class 2 supply; none of that changes the washdown rating.
Can I drill a drain hole so wash water cannot pool in the box?
You can, and you give up the rating by doing it. NEC 314.15 permits drainage openings of 1/8 in [3 mm] to 1/4 in [6 mm] in boxes listed for damp or wet locations, but a drained box sheds rain rather than hose water — that trade lands the panel near Type 3R. Keep the door sealed and the bottom at 5 ft [1.5 m] instead.
What if the crew sprays the panel directly at close range?
The Type 4 hose test starts at 10 ft with a 1 in nozzle at 65 gal/min, so a jet from 2 ft sits outside what the rating covers. Move the box out of the wash line, aim the hose down, or fit a stainless shield over the door; the 4X / IP66 rating then covers the splash behind it.
How much heat does the supply add inside the box?
About 4 W: 3% loss on a 100 VA supply is 3.0 W, and two relay coils at 0.5 W add 1.0 W. In the 16 x 16 x 6 in stainless box that is a 2.6 K rise, so at 35 C ambient the panel runs near 38 C, under the 40 C ambient most 24 VAC control gear carries.
Does the inspector need a listed enclosure here?
Our enclosures are manufacturer-rated NEMA 4X / IP66, not UL listed; a UL listed enclosure has been evaluated by UL to UL 50E, and a listed industrial control panel is built to UL 508A. Where the job calls for a listed assembly, that line sits alongside the type rating — the wet room still gets 4X / IP66 on the drawing either way.