Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Terminal blocks above a PLC: the field wiring interface

That row above the PLC is a terminal-block interface: field cables land on one side of each block, small wires leave through slotted duct to the card, and jumpered 24 V DC and 0 V rails sit at one end. A 16-point input card with four spares takes a 218 mm [8.6 in] block run and a 25 x 25 mm [1 x 1 in] duct.

NEMA4 Enclosure engineering team · Published November 24, 2026 · 8 min read

That row of small plastic blocks above the PLC is the terminal-block interface between the field and the cabinet. Heavy field cables land on one side of each block; short cabinet wires leave the other side through slotted duct and finish at the card terminals. Jumpered supply and 0 V distribution groups sit at one end of the rail. Built this way, a chewed terminal costs one block and a screwdriver. Wired straight to the card, the same fault means pulling a card out of the PLC rack. The row also takes layout space you can compute before you order: a 16-point input card with four spare positions needs a 218 mm [8.6 in] block run and a 25 x 25 mm [1 x 1 in] duct between the row and the PLC.

What each part in the row is

Five parts cover everything you see in one of these rows, and each part has one job.

What you see What it is What it does
Small blocks clipped to a metal rail DIN-rail terminal blocks The connection between field wiring and cabinet wiring
Slotted plastic channel with a snap-on cover Wiring duct Routes and protects the cabinet-side wires
A bare strip across a group of blocks Jumper bar, or distribution strip Commons one supply rail across the group
Printed markers at each wire end Wire labels Map every conductor to the drawing and the card point
End plates part-way along the run Group separators Keep the supply rails and signal positions apart

The blocks connect, the duct routes, the labels remember. Run one multi-conductor cable per card, with enough conductors for the points plus the commons; the example's 16-point input card ties to its row through about 18 conductors. Screw-clamp and spring-clamp blocks hold the wire differently, and spring clamp vs screw clamp terminal blocks on DIN rail sets out the trade-offs — one style across the whole row keeps the spare parts simple. How far rows sit apart, and how much finger clearance the duct needs, is worked out in the backplate and DIN rail layout guide.

The two sides of one block

Follow one conductor through one block. The field cable lands on the top clamp, often 14 AWG or larger for a load: UL 508A control-panel design guides size single-load field conductors at 125% of full-load current, 14 AWG minimum, and a block used for field connection has to accept the conductor size its circuit needs. The cabinet-side drop leaves the other clamp, runs through the duct, and ends on the card terminal; in the worked example those drops are 18 AWG. One block, two gauges — and the gauge change is the point, because card terminals are made for small wire and the field cable is not.

The field cable moves with the machine. The block holds that movement at the interface instead of letting it work on the card connection; hanging cables on terminal blocks covers keeping the sway off the joint. The strain relief belongs to the gland at the wall, not to the card.

Why the row exists, and when a panel skips it

Four reasons, in the order they pay back:

  • Serviceability. A failed terminal means one block off the rail, not a card out of the rack — which is also why field cables go back on terminal blocks after a panel burn.
  • The gauge change. Field conductors land once, on blocks sized to take them, and stay there.
  • A test point. You meter at the block without probing a crowded card terminal.
  • A home for field wiring. UL 508A treats blocks used this way as field wiring terminals, matched to the conductor the circuit needs.

The decision comes out by cabinet. In a wall-mount or floor-standing enclosure, build the row. In a machine-integrated box with a few inches to spare and a handful of I/O points, wire direct and accept that the card terminals carry the service risk; door-mounted controls: terminal blocks or direct walks through that same call. Count the positions first — how many terminal blocks you need counts points, not blocks — and let the count make the call.

The 24 V DC and 0 V distribution groups

At one end of the rail, jumper bars turn plain blocks into a small distribution board: one group carries the positive rail, the next carries 0 V. Every position under a bar shares that rail, which is how sensor power and card commons get fed without a home run from each device to the supply. Keep each rail one unbroken group, keep the two groups apart — a 10 mm [0.4 in] gap in the worked example — and leave spare positions on both. A lost common drops the whole group rather than one point, so label the common at the group, not only at the wire.

Large conductors land differently. Where mains or a big load comes onto power distribution blocks, the UL 508A application notes for those blocks give 1 in [25 mm] through air and 2 in [50 mm] over a surface as the spacing, and NEC 312.6 sets their wire-bending space at the terminal — Table 312.6(A) when the conductor enters from the side, Table 312.6(B) when it crosses the wall opposite. What a jumpered group may carry comes from the block and jumper ratings printed on them.

What the markings and the rating cover

Each block carries voltage and current ratings on its housing, and those numbers cover the block alone. The duct carries a fill limit: wiring-duct fill tables cap the wiring at 50% of the duct's interior cross-section, the ceiling NFPA 79-2012 section 13.5.2 backs for raceway and duct fills, and the backplate and DIN rail layout guide shows the arithmetic. The worked example below stays inside it.

The enclosure carries the rating that keeps the water off all of it. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. That rating survives a new opening when the opening is engineered into the order — gland cutouts, seals and rear clearance settled on the approval drawing, the way the cutouts and glands guide lays out. A field-drilled hole or a half-seated gland is where Type 4X is lost. If the finished panel is listed, NEC 409.2 defines an industrial control panel, UL 508A is the standard it is built to, and NEC 409.110 puts the enclosure type number on the marking.

Worked example: the interface row for a 16-point card in a 20 x 16 x 8 in box

Inputs first, each with where it comes from. Swap in your own and redo the sums.

Input Value Where it comes from
Input points 16 The example card; read the count off yours
Spares 4 positions, 20% of the row Example choice, for a line that grows sensors
Block width 6.2 mm [0.24 in] Printed on the example blocks; read yours
Distribution groups 2 groups x 6 positions Example: one positive rail, one 0 V
Group gaps 2 gaps x 10 mm [0.4 in] Example layout choice
Cabinet-side drops 26 wires, 18 AWG, 2.5 mm [0.10 in] OD Example: 20 signal drops plus 6 rail feeds and commons

Two rules run the layout. Run length is positions x block width plus gaps. Duct fill is wire area divided by duct interior area, with 50% as the ceiling.

  • Signal run: 20 x 6.2 mm = 124 mm [4.9 in]
  • Distribution groups: 12 x 6.2 mm = 74.4 mm [2.9 in]
  • Gaps: 2 x 10 mm = 20 mm [0.8 in]
  • Total run: 124 + 74.4 + 20 = 218.4 mm, so 218 mm [8.6 in] — cut a 250 mm [9.8 in] rail
  • Wire area: 0.785 x 2.5 mm x 2.5 mm = 4.9 mm² each; 26 x 4.9 mm² = 127 mm²
  • Interior needed: 127 mm² ÷ 0.5 = 254 mm²
  • 25 x 25 mm [1 x 1 in] duct: 645 mm² interior, 322 mm² usable → 127 ÷ 322 = 40% of the fill limit → passes with headroom
  • 19 x 19 mm [0.75 in] duct: 363 mm² interior, 181 mm² usable → 70% → passes today and fills at the next card

Use the interior dimensions printed on your duct, not the outside of the channel. The decision: run 25 x 25 mm [1 x 1 in] duct between the rows. The 218 mm row and the card rail below it fit the 20 x 16 x 8 in [508 x 406 x 203 mm] box with both duct runs, leaving roughly 15 in [381 mm] of usable plate width after mounting margins. Past that, split the row into two rails or order a wider body. And the payoff that pays for the row: the failed terminal is one 6.2 mm block and one screw.

What to put on the order

  • Terminal positions: 32 blocks in the example — 20 signal, 12 distribution — plus your spares, all one clamp style, with blocks marked for field wiring where the cables land.
  • Jumper bars: one per distribution group, with end brackets and group separators.
  • Duct: 25 x 25 mm [1 x 1 in] slotted duct between the rows; where power devices share the box, give the duct runs extra spacing so they stay clear of the heat and the dropped screws.
  • DIN rail: one 250 mm [9.8 in] cut for the interface row.
  • Ground blocks: for the shields and grounds, biting the rail so it bonds; what has to be bonded, and how, is in the grounding and bonding guide.
  • The enclosure: width for the row, the card rail and both duct runs, with a gland cutout for every field cable. We build those to your drawing — size the box in the enclosure builder or send the drawing for a custom 304 or 316L body in custom stainless steel enclosures — and either one is delivered in 10 business days, counted from the order or, for custom work, from your approval of the drawing.

Keep the working space on the checklist too: NEC 110.26(A) asks for 3 ft [900 mm] clear in front of the panel at 0-150 V to ground in Condition 1, with room for the door to open 90 degrees.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
6 × 6 × 4 in304 stainless6 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
8 × 6 × 4 in304 stainless8 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10 × 8 × 4 in304 stainless10 x 8 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

What is the row of blocks above a PLC for?

It is the field wiring interface. Each block separates the field connection from the cabinet side: the big cable lands once on the block, and a short wire runs through slotted duct to the card terminal. A 16-point card takes 16 signal positions plus spares, with the distribution groups beside them — a 218 mm block run in the worked example. The point is serviceability: a damaged terminal costs one block, not the PLC card.

Can field cables land directly on the PLC terminals?

Card terminals are built for small cabinet wire, while field conductors for a single load are sized at 125% of full-load current and no smaller than 14 AWG in UL 508A design guides. The interface row lets each field conductor land once on a block built for that gauge, then continue as small wire to the card. In a tight machine-integrated cabinet, direct wiring saves the space; the card terminals then take every service call.

What is the strip across the tops of some blocks?

A jumper bar, also called a distribution strip. It ties a group of adjacent blocks to one rail — the positive rail on one group, 0 V on the other in a control-voltage panel — so every position under it shares that rail. Keep the two rails as separate unbroken groups; a 0 V block jumpered into the positive group is a wiring fault. The current a group may carry is set by the block and jumper ratings printed on them.

How wide does the terminal block row get?

Multiply positions by block width. The worked example's blocks measure 6.2 mm each: 20 signal positions make 124 mm, two 6-position distribution groups add 74.4 mm, and two 10 mm gaps bring the run to 218 mm [8.6 in]. Cut a 250 mm [9.8 in] rail, and re-run the sum every time you add a card.

Does a terminal block row change the enclosure rating?

The rating belongs to the box, and the row does not touch it: NEMA 4X / IP66 is the enclosure manufacturer's rating, not UL listed, and it holds when field cables enter through correctly fitted glands in cutouts made for them. A plain drilled hole or a half-seated gland is where that rating is lost, so put every gland position on the order drawing before the box is cut.

Where does the control power in the rails come from?

From a DIN-rail power supply inside the same cabinet, fed from the mains disconnect — the 24 V DC does not appear on its own. The same box can hold 480 V AC motor circuits well away from the low-voltage row, which is why a control-voltage label covers only its own section and the meter decides what is safe to touch.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start a junction box from 20 × 16 × 8 inRequest a custom quote

Stainless junction boxes: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides