Short answer: a node that answers until its 3-wire PT100 lands, then goes silent, has a second earth path. Its sheath touches grounded process metal - a thermowell, a pipe, a tank wall. The RS-485 shield sits earthed at the cabinet, and the two earths bridge straight through an otherwise isolated controller. The offset drags the transceiver's reference outside the -7 V to +12 V common-mode window every compliant receiver must accept. The node goes mute while it keeps measuring. Float the probe to prove it, then earth the shield at the master end only and fit an isolated-tip PT100.
What each symptom points to
The pattern tells you more than any single reading, so start from what the master sees:
- Answers with the probe disconnected, silent the second it lands. This is the second-earth fault. Baud rate, parity, slave address and termination were fine a moment earlier, so the failure is electrical, not protocol.
- Silent even with the probe floated on a bench. Work the bus itself: swapped A/B pair, wrong address, a missing signal common, termination. The RS-485 common and shield conductor article sorts out the last two.
- Comms hold but the temperature wobbles when a drive starts. The sensor cable screen is in the loop as well as, or instead of, the bus shield. The PT100 shield grounding article works that variant through.
- The reading drifts slowly with cable temperature. Mixed conductors on the 3-wire input: lead compensation assumes three identical legs, and a swapped sense lead looks the same.
- CRC errors climb with no clean dropout. Earth noise on the segment, still below the mute threshold. The pH ground loop article shows the same loop biting a different instrument.
Why one landed probe silences the node
The controller is built isolated. Its supply is isolated from the analog input, the analog output is isolated from the supply, and the supply runs on line and neutral alone, with no protective earth needed for it to work. That arrangement lets the whole instrument float, and it holds only while nothing outside ties two earths together through the box.
The first suspect is the probe. A grounded-junction element, or a sensor cable screen bonded to the sheath, connects the input circuitry to the sheath, and the sheath sits on earthed metal. The RS-485 shield on the cabinet earth bar supplies the second earth. Any potential difference between the two drives current through the instrument and moves the transceiver's reference with it. Outside its common-mode band, the receiver can no longer resolve the pair, and the node is mute.
Next, in order: a sensor screen earthed at both ends even with an isolated element; moisture in the probe head tying one lead to the sheath; and a protective earth landed on the controller's 0 V, which gives the loop a third way in.
The checks, in order
Run these before you change any wiring for good:
- Float the probe. Land the PT100 on the input terminals, but rest the stem in air or on wood - out of the well, off machine steel. Poll the slave. Comms return means the sheath is the second earth point; still dead means the bus itself.
- Re-insert the probe while polling. The node should drop the instant the sheath touches grounded metal. Watch that once and the diagnosis is closed.
- Lift the RS-485 shield at controller end only. Leave it earthed at the master and poll again with the probe installed. Comms back means the loop was closing through the shield.
- Ring the probe. Ohmmeter from each PT100 lead to the sheath. An isolated-tip element reads open; continuity or an unstable resistance means a grounded-junction element or a wet head, and the sheath is wired straight into your input.
- Measure the offset. Probe out, shield lifted, meter between the shield's earth bar and the process metal the probe touches, on both AC and DC volts. Write both readings down; they size the fix below.
Working the numbers: a muted controller and the 19 V window
The worked check, on the case at the top of this article: a DIN-rail controller whose node dies the moment its probe lands.
Inputs.
- Receiver common-mode window: -7 V to +12 V relative to the transceiver's local ground, the range every compliant receiver accepts under TIA/EIA-485-A; the transceiver makers' application notes restate it.
- Driver output: at least 1.5 V differential into a 60 Ω load, from the same standard.
- Your meter reading from check 5, in volts AC and DC - the one number you supply.
The rule in words. The receiver decides data on the voltage between A and B while riding on the common mode. It decodes only while that common mode, measured against its own reference, stays inside the window. The probe loop moves the reference, so your meter reading lands squarely on the transceiver.
Arithmetic.
- Window span: +12 V - (-7 V) = 19 V of tolerance.
- Driver current into the termination: 1.5 V ÷ 60 Ω = 0.025 A = 25 mA.
- Window against signal: 19 V ÷ 1.5 V ≈ 12.7, so the receiver carries almost thirteen times its data amplitude as common-mode tolerance. The earth loop spends that tolerance.
Decision. Any readable offset confirms the loop, so apply fixes 1 and 2 below whatever the number reads. A reading that climbs toward a band edge explains a node that is fully mute rather than flaky, and sustained readings there also press the bus pins. Ordinary transceivers are specified to the band above; fault-protected families take up to ±60 V on the pins and keep working at ±15 V of common mode. An offset that survives the shield fix, or a segment that crosses to another building's earth, puts an isolator between the controller and the bus.
The fix, ranked
| # | Fix | What it does | Use it when |
|---|---|---|---|
| 1 | Isolated-tip PT100, or the probe mounted in an insulated bushing | Removes the second earth at the source and gives the input back its isolation | Always the permanent fix; mandatory where plant earth carries welding or drive return currents |
| 2 | RS-485 shield earthed at one point, the master end, lifted at the controller | Stops the shield acting as a return conductor between two earth potentials | Always, even after fix 1 |
| 3 | Sensor cable screen earthed at the controller end only, unbonded from the probe head | Keeps the sensor screen one-ended instead of a bonding strap | Any shielded PT100 cable |
| 4 | Isolated RS-485 repeater between controller and segment | Breaks the loop at the bus and tolerates large earth differences | Long runs, separate buildings, probes that must stay bonded |
| 5 | Supply kept floating as documented: line and neutral, no earth on 0 V | Avoids a third earth reference through the power terminals | Whenever the supply is documented isolated |
Fix 2 lives at the gland plate: the shield clamp lands on the cabinet earth bar at the master cabinet only. The enclosure grounding and bonding guide covers that bar, including the NEC 250.12 rule that paint leaves the contact surfaces. Where a segment already runs panel to panel with the shield landed at both ends, the RS-485 shield ground loop article works out which end keeps the earth.
The check that proves it. Poll the node for ten minutes with the probe back in the well and the nearest drive running. Read the process value and one configuration register twenty times. Zero timeouts and a steady value mean the loop is broken; timeouts that return only under drive load point at the sensor screen, so go back to fix 3.
Stop it coming back
- Specify isolated-tip probes at order time for every RTD that enters grounded metal; a probe swap later means draining a well.
- Keep one shield earth per segment, at the master cabinet, with the lifted end sleeved so it cannot touch a gland plate.
- On the 3-wire PT100, run all three legs as the same gauge, the same length and the same cable, and land the compensation pair on its designated terminals. A swapped sense lead shows as a reading that walks with cable temperature. The RTD cable shield grounding article settles which end of the sensor screen earths.
- Route the PT100 cable in its own duct, apart from drive output and contactor coil wiring, and cross motor leads at 90° where they must cross.
- Give any isolator a DIN-rail seat beside the controller, with its bus-side wiring in a separate duct from the sensor side, so a parallel cable run cannot bridge the isolation.
When the isolator is the right fix
The RS-485 isolation article decides when a node needs an isolator for ground domains and surge. For this fault, three conditions point there: the probe must stay bonded to process metal; the segment runs to another building or its own earth electrode; or the offset from check 5 survives fixes 1 and 2. The isolator then sits between the controller and the rest of the segment, with the shield earthed on the master's side of it only.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Why does the controller still show the right temperature while Modbus is dead?
The input section keeps measuring: the element and its three leads are all it needs. The mute part is the RS-485 transceiver, whose reference has been dragged outside the -7 V to +12 V common-mode window, so it can neither decode the pair nor drive valid levels onto it. The process value on the front panel is genuine; only the bus side is blind.
Will a transceiver with a wider common-mode range cure it?
Extended-range transceiver families hold -20 V to +25 V, a 45 V span against the standard 19 V, and fault-protected parts take up to ±60 V on the bus pins while working at ±15 V of common mode. That transceiver sits inside the controller, so it is a selection for the next build, not a field fix. Break the loop instead: one shield earth at the master, an isolated-tip probe, or an isolator on the segment.
The RS-485 shield is earthed at both ends - which end stays earthed?
Keep the earth at the master cabinet and lift the shield at the controller end, sleeving the drained end so it cannot touch the gland plate. One earth point per shield stops it acting as a return conductor between two earth potentials, and that arrangement stays correct even after an isolated-tip probe is fitted. Where the run crosses to another building or its own earth electrode, an isolated repeater between the controller and the segment does the job instead.
Can I earth the controller's 0 V terminal to stop the fault?
Earth it and you add a third reference: the supply is documented isolated and runs from line and neutral alone, so tying 0 V to cabinet earth sends the loop current through the input instead of around it. Keep the supply floating as drawn, keep the protective earth on the cabinet metalwork that NEC 250.96(A) bonds, and break the loop at the shield, the probe or with an isolator.





