Spec the power path as a pair, not as a single part. That means a panel-mount inlet and its mating plug, rated by the connector maker at IP66 or IP67 in the mated state, plus a cap with the same digit for the unplugged hours. A 300 W load draws 1.3 A at 230 V and 2.6 A at 115 V at power factor 1. With a switch-mode supply at 0.9 efficiency and 0.95 power factor, the same 300 W takes 1.5 A and 3.1 A. A 10 A inlet covers either voltage with more than double the margin, so the connector's amp rating is not what decides this choice. The mated seal, the wall cutout and the gasket torque are.
Size the inlet on input current, not watts
Nameplate watts are the output figure. The current through the inlet is the input, and single-phase gives it as I = P / (V × PF). At power factor 1, a 300 W resistive heater draws 300 / 230 = 1.30 A at 230 V and 300 / 115 = 2.61 A at 115 V.
A switch-mode supply moves both numbers up, because the line carries the losses and the reactive component as well. A supply delivering 300 W at 0.9 efficiency and 0.95 power factor draws 300 / (0.90 × 0.95) = 351 VA. That is 1.5 A at 230 V and 3.1 A at 115 V.
| Supply voltage | 300 W at PF 1 | 300 W output, supply at 0.9 efficiency, 0.95 PF |
|---|---|---|
| 230 V | 1.3 A | 1.5 A |
| 115 V | 2.6 A | 3.1 A |
Power factor moves the number fast. At 0.8 with the same efficiency, the 230 V input is 300 / (230 × 0.90 × 0.80) = 1.8 A, a third more than the 1.5 A case. Read efficiency and power factor from the supply datasheet rather than borrowing this example's 0.9 and 0.95.
The selection rule: take the worst case, 3.1 A here, and double it. That 6.2 A is the floor for the contact rating, and the 2x margin covers imbalance and a warm cabinet. A family with 10 A contacts clears it at either voltage. An IEC 60309 16 A frame clears it with room to spare, at the cost of a larger cutout and a heavier shell.
What the inlet meets outdoors
The inlet sees whatever the wall sees: wind-driven rain, hose washdown, driving dust, sun and freeze-thaw. All of it lands on three parts — the plug's seal, the inlet's gasket and the cord entry — so this is a sealing choice before it is an electrical one.
Two states carry different ratings. Mated, plug and inlet form one sealed unit. Unmated, during a service swap, the open inlet is a hole in the wall until a cap closes it. Buy for the mated state first, then make the cap a fixed line on the parts list.
Water sets the digit. A hose washdown is the IPX6 powerful-jet test; driven rain and spray sit lower, at IPX3 or IPX4. Immersion is IPX7, a state an outdoor cabinet rarely meets. Sun is the largest heat load on an outdoor box, and it works the gasket seams year after year; the heat and condensation side belongs to the outdoor enclosure guide. Near salt air, brine or chemical washdown, the wall itself moves from 304 to 316L stainless and the inlet's exposed metalwork should follow; outdoor weatherproof enclosures is where that material call is laid out.
Decision: for a box that lives outside and gets hosed, spec IP66 on the mated pair. Add the 7 only when immersion is written into the product's spec, and read what an outdoor-rated label leaves out first.
The rating lives in three places
IEC 60529 defines the digits. First digit 6 is dust-tight: no dust ingress. Second digit 6 is powerful jets: a 12.5 mm [0.5 in] nozzle at 100 L/min from 2.5 to 3 m for at least 3 min. Second digit 7 is temporary immersion: 1 m [3.3 ft] of water for 30 min. Digit 8 means continuous immersion under conditions the maker and the user agree in advance; an IP68 claim without stated conditions is a series name, not a number.
The first place is the mated pair. The IP code on a power connector describes the assembled pair, seated as the datasheet shows. The same rule holds for sealed M12 and M8 data connectors: only the mated state carries the code. IP ratings for mated versus unmated connectors works through the unplugged case in detail.
The second place is the cap. Unplugged and uncapped, the inlet hands the assembly's rating back. The cap needs the same digit, and it belongs on the drawing beside the inlet.
The third place is the wall. The cutout, the gasket seat and the torque decide whether the inlet's rating reaches the inside of the box. Every other penetration plays by the same rule, and the lowest-rated part sets the assembly: an IP66 box with an IP54 inlet is an IP54 box, the same arithmetic as after you cut a panel and mount devices.
In US installations, NEC 110.28 states that an IP code does not replace the enclosure type rating. A specification written in NEMA types needs the type on the box; many enclosures carry both marks. Our wall-mount stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. UL 50E versus NEMA 250 explains where a listing enters the picture. Immersion duty on the enclosure itself is a custom design review with depth, duration, fluid and penetrations stated; stock wall-mount boxes do not carry it.
Which connector family fits the job
IEC 60309 pin-and-sleeve is the industrial workhorse. At 50–60 Hz the plugs and inlets are colour-coded by voltage range: yellow for 100–130 V, blue for 200–250 V, red for 380–480 V. The keyway and the earth-pin clock position change between voltage ranges and between frame sizes. A 115 V cord cannot enter a 230 V inlet, and a 16 A plug will not enter a 32 A one. Frames start at 16 A, and the shells are built for dragging, weather and frequent plug cycles. For a 300 W input that hardware is oversized; the value is the keying, and the cost is a large hole in a thin wall.
A product that keeps its cord attached does the same job through a smaller sealed circular family, in a smaller hole. Choose on the datasheet lines that matter. The IP code must be stated for the mated pair, with a cap carrying the same digit. Contacts need 10 A or more, and the clamping range must cover the cord's outside diameter. Write the exact part numbers of inlet, plug and cap into the spec. IP claims attach to part numbers: a series can hold a low base rating while only some of its variants seal to IP67, and the variant datasheet wins over the brochure.
The voltage side of the inlet — what it must tolerate across markets, and what happens when the wrong cord arrives — has its own page: outdoor power inlet voltage compatibility.
Decision by job:
- One voltage, permanent cord: a sealed circular inlet, 10 A contacts, cap to the same IP digit.
- Two markets, 115 V and 230 V: two non-interchangeable inlets, one per voltage. IEC 60309 yellow and blue make the mismatch physically impossible.
- Rough service or frequent mating: the IEC 60309 16 A frame, with its larger cutout planned from the start.
Mount the inlet without giving the rating back
- Cut the wall to the connector datasheet's hole drawing and hold its tolerance. The hole and the flat ring around it are the gasket's seat, and a hole outside that drawing costs the rating; drilling into an enclosure covers the mechanics, and the cutouts and glands guide the layout.
- Seat the gasket flat on clean metal and tighten the inlet fasteners to the datasheet torque in a cross pattern. Under-torque leaves a weep path; over-torque squeezes the seal past its recovery.
- Land protective earth on the inlet's PE terminal and bond it to the enclosure's earth point. On a metal box, NEC 250.12 calls for paint and lacquer to be cleared from the contact surfaces under the lug. NEC 250.96(A) calls for the bonded metal parts to carry the fault current likely to be imposed on them. The grounding and bonding guide holds the working details.
- Match the cord's outside diameter to the plug's clamping range, and use the molded strain relief where the family provides one. A seal gripping outside its range weeps along the jacket.
- De-energize the panel, close it with the cord mated, and play a hose over the inlet area for a minute at normal line pressure. Open up and look behind the gasket. Dry passes; a wet trace means re-torque and repeat. Recheck earth continuity afterwards.
What goes on the order
The custom builder takes material, size and every cutout from your drawing, and custom stainless enclosures start from one piece. Put these lines on the order:
| Order line | What to write |
|---|---|
| Enclosure | 304 stainless wall-mount inland; 316L for salt air, brine or chemical washdown |
| Enclosure rating | NEMA 4X / IP66, manufacturer-rated; immersion only through a custom design review |
| Connector family | Sealed circular for a permanent cord; IEC 60309 for two voltages or rough duty |
| Contact rating | 10 A minimum: the 3.1 A worst case at 115 V, doubled |
| Cap | Same IP digit as the mated pair, captive |
| Cutout | The connector datasheet's hole drawing, tolerance and mounting-hole pattern |
| Delivery | 10 business days worldwide, counted from drawing approval for custom work |
The decision, by case. Rain and hose washdown with a permanent cord on one voltage: an IP66 mated pair, an IP66 captive cap, 10 A contacts, 304 stainless inland or 316L near salt. Immersion written into the product's spec: IPX7 on the pair, and a custom enclosure review on the box, because a stock NEMA 4X / IP66 wall-mount part is not an immersion enclosure. Two voltage markets: two keyed, non-interchangeable inlets, yellow for 100–130 V and blue for 200–250 V, each named on the drawing beside the cord that belongs to it.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What current does a 300 W load draw at 230 V and 115 V?
At power factor 1 the arithmetic is 300 / 230 = 1.3 A and 300 / 115 = 2.6 A. A switch-mode supply raises the line current: at 0.9 efficiency and 0.95 power factor the input is about 351 VA, giving 1.5 A at 230 V and 3.1 A at 115 V. Take the larger figure, double it, and pick contacts rated 10 A or better.
Does IEC 60309 keying stop a 115 V cord entering a 230 V inlet?
Yes. At 50–60 Hz the plugs are colour-coded by voltage range: yellow for 100–130 V, blue for 200–250 V and red for 380–480 V, with the keyway and earth-pin clock position changed between ranges and frame sizes. A yellow 115 V plug cannot enter a blue 230 V inlet, and a 16 A plug will not enter a 32 A inlet of the same colour.
Is the inlet still IP67 while the cord is unplugged?
Only with a cap the connector maker rates at IP67 fitted over the inlet. The IP code on a power connector describes the mated pair, seated as the datasheet shows; unplugged, the pins and the inlet cavity are open to the weather. Spec a captive cap at the same digit and put it on the parts list beside the plug.
Which sets the assembly rating, the enclosure or the inlet?
The lowest-rated penetration does. A NEMA 4X / IP66 wall-mount box with an inlet, cap or cord gland rated lower holds that lower figure, and a hole cut outside the connector datasheet's drawing leaks at the first hose test. Spec every penetration — inlet, cap, gland, antenna connector — at the box's rating or above.
Can the enclosure arrive with the inlet cutout already cut?
Yes. A custom stainless enclosure is built from one piece with every cutout taken from your drawing: send the connector datasheet's hole size, its tolerance and the mounting-hole pattern, and the wall arrives ready for the gasket and the inlet fasteners. Delivery is 10 business days worldwide, counted from your approval of the drawing for custom work.
Why do US specs ask for a NEMA type when the inlet carries an IP code?
Because in US installations NEC 110.28 keeps the two marks separate: an IP code does not replace the enclosure type rating. An enclosure carrying both — a NEMA type for the US spec and an IP code for the international one — answers both readers at once. Our wall-mount boxes carry NEMA 4X and IP66 as manufacturer ratings.





