Size the enclosure for a video panel PC on the draw you measure with the cameras running, not on the datasheet's idle figure. Decoding live streams adds 5-15 W over static PLC screens on a fanless industrial unit; those are example figures, and a five-minute meter reading replaces them with yours. The uplift runs continuously, shift after shift. The wall math is one line: rise in C equals watts divided by (3.7 W/m²K × area in m²) for stainless in still air. A measured 38.4 W in a 0.67 m² stainless housing rises 15.5 C, so a 35 C ambient puts the inside air at 50.5 C. The same load holds a 10 C rise, and a 45 C inside target, in 1.04 m² of wall — a 600 × 500 × 200 mm box.
What live video does to the heat load
Static PLC screens load a panel PC lightly. The backlight holds a steady draw and the silicon idles between screen updates. Live camera streams are a different workload. The decoder works on every frame of every stream, the memory bus stays busy, and the unit never returns to idle while the feeds run. As an example range, expect 5-15 W more than the static draw, and plan on the top of the range when several 1080p streams run all shift.
The number that matters is the one you measure. Put a plug-in watt meter or a DC clamp meter on the 24 V DC input while the screen runs its real mix. Multiply volts by amps: 24 V × 1.6 A = 38.4 W. In a fanless unit essentially all of that dissipates inside the enclosure, and the few watts that leave as screen light only make the estimate conservative. Dimming the backlight on a schedule cuts the measured figure by whatever the meter then shows, so re-read after you set the brightness policy.
Add the other residents too. A PoE switch feeding those cameras sits in the same box, and its draw is heat as well. The component-by-component sum in the enclosure heat load calculation article keeps the total honest before any wall math starts.
What the datasheet figures and the ingress rating cover
A panel PC datasheet lists a typical draw and a maximum. The typical figure comes from a desktop showing idle screens, and the maximum is a transient peak. Neither is the 24/7 video figure. That is why the meter reading is the sizing input and the datasheet's ambient rating is the ceiling you protect.
The enclosure's ingress rating says nothing about any of this. IEC 60529 tests dust and water entry, and its second digit 6 is a 12.5 mm nozzle at 100 L/min. NEMA 250 adds Type 4X for hose-directed water plus corrosion resistance. No part of either test measures temperature rise. Thermal sizing is your calculation with the wall conductance below, and our housings are manufacturer rated, not UL listed.
The wall math for a sealed stainless housing
A sealed enclosure sheds heat through its walls by natural convection and radiation in still air. The rise above ambient is ΔT = Q ÷ (k × A), with Q in watts, A the total outside surface in m² and k the wall conductance in W/m²K. Area comes straight from the outside dimensions in metres: A = 2 × (H×W + H×D + W×D). The fuller method, with these same k values, is in the non-ventilated stainless sizing article.
| Wall material | k (W/m²K) | Rise for 38.4 W on 1 m² |
|---|---|---|
| 304 / 316L stainless | 3.7 | 10.4 C |
| Painted steel | 5.5 | 7.0 C |
| Plastic | 3.5 | 11.0 C |
Stainless is the washdown choice and the conservative one. At equal area it runs about 49% more rise than painted steel: 10.4 C against 7.0 C for the same load. Keep the box sealed. A fan-filter unit, a breather or a drain carries its own lower ingress rating and drags the whole assembly down to it, so a hose-down build lives or dies by wall area.
Worked example: four camera streams on a 15.6 in panel PC
Every input here is one you replace with your own figure. The panel PC is a fanless 15.6 in unit rated to 50 C ambient; that rating is a datasheet value in this example. It measures 1.0 A on static screens and 1.6 A with four 1080p streams decoding, both at 24 V DC. The housing is 304 stainless at 500 × 400 × 150 mm (20 × 16 × 6 in). Worst shade ambient is 35 C, and the target is 5 C below the rating, so 45 C inside.
Surface area: A = 2 × (0.5 × 0.4 + 0.5 × 0.15 + 0.4 × 0.15) = 2 × 0.335 = 0.67 m². Wall conductance: 3.7 W/m²K × 0.67 m² = 2.48 W/K. Static screens: 24.0 W ÷ 2.48 W/K = 9.7 C, inside 44.7 C. Four streams: 38.4 W ÷ 2.48 W/K = 15.5 C, inside 50.5 C. Halving the streams to two, assuming the decode uplift scales with stream count, lands at 31.2 W and 47.6 C inside.
| Case | Measured draw | Rise above 35 C ambient | Inside air |
|---|---|---|---|
| Static PLC screens | 24.0 W | 9.7 C | 44.7 C |
| Two camera streams | 31.2 W | 12.6 C | 47.6 C |
| Four camera streams | 38.4 W | 15.5 C | 50.5 C |
| Four streams, larger housing | same draw | 10.0 C | 45.0 C |
Static screens pass the 45 C target with 0.3 C to spare. The four-stream case misses both the target and the 50 C rating. The target allows 24.8 W in the small box (10 K × 2.48 W/K), so the fixes are area or a lower load. Required area: 38.4 W ÷ 10 K ÷ 3.7 W/m²K = 1.04 m². A 600 × 500 × 200 mm (24 × 20 × 8 in) housing delivers it, A = 2 × 0.52, and holds 45.0 C. Decision: at a 35 C ambient, give this measured video load 1.04 m² of stainless wall. The alternative is a 60 C-rated panel PC, which moves the target to 55 C and fits 50.5 C.
What moves the rise, and by how much
- Ambient. Every degree of ambient moves the inside air a degree. A site that sits at 45 C shifts the whole example table up 10 C, and the 45 C target is gone before any stream starts.
- Sun. Full sun adds watts no wall calculation covers on its own. The outdoor solar heat-gain method in the outdoor heat-gain article sizes that share, and you add it to Q before picking the housing.
- Wall material. Painted steel at 5.5 W/m²K carries the example load on the same 0.67 m² with 10.4 C of rise (45.4 C inside), on target with no new box. Indoors and dry, that is a real option; washdown and chloride duty put you back in stainless.
- Hot spots. The wall math sets the average, and a hot chipset still sits above it. Conduction into the rear wall flattens the peak, as the heat-spreader article sizes it, and a fully internal circulating fan evens the air without touching the rating.
- Hot sites. At 45-50 C ambient the wall alone cannot hold a 5 C margin under a 50 C-rated display. The cooling choices for 120 F summer heat start there, where a sealed air-to-air exchanger keeps the ingress seal intact.
Two checks close the loop. Re-measure the draw after any change to streams, resolution or brightness, because the decoder share moves with them. After the first full shift of live video, read the inside air temperature: it should sit 5 C or more below the panel PC's rating, which in the example means 45 C or less.
What to put on the order
| Line | Value to state | Basis / example |
|---|---|---|
| Heat load Q | measured worst case with streams running | 24 V × amps at the DC input |
| Ambient basis | worst shade ambient at the mounting wall | 35 C in the example |
| Inside target | datasheet rating minus 5 C | 50 C rating → 45 C target |
| Wall conductance k | 3.7 W/m²K stainless; 5.5 painted steel; 3.5 plastic | still-air natural convection |
| Wall area | Q ÷ (target − ambient) ÷ k | the example gives 1.04 m² |
| Sealing | sealed box, gasketed rear cover | keeps the assembly rating on a washdown wall |
| Mounting | VESA 100 rear; display cutout to the panel PC's front template | the HMI housing standard |
Our HMI housings are 304 stainless with a VESA 100 rear pattern and a gasketed rear cover, sized to the display from 7 to 23.8 in. The 15.6 in panel PC housing takes the example unit, and the 21.5 in panel PC housing is the step up when the screen grows with the job. The display front is an IP65-type seal with the display installed, manufacturer rated, not UL listed.
When the area your calculation calls for sits outside the display-sized range, order a custom enclosure built to your drawing; 600 × 500 × 200 mm is the example. The drawing comes back to you for approval, and the housing is delivered in 10 business days from that approval. The cutouts, glands and HMI windows guide lists what to dimension for the display opening, so the front cutout and the rear gland positions land right the first time.
Decisions by site, on the example numbers:
- Indoor room at 25 C or below: the display-sized housing works even with four streams running, since 15.5 C of rise puts the inside at 40.5 C, under the 45 C target.
- Outdoor shade at 35 C with continuous streams: 1.04 m² of wall, or two streams and 47.6 C against a 50 C rating.
- Washdown or hose-down duty: the same wall math, and the rating survives because the box stays sealed.
- Sun on the wall or ambient at 45 C and up: correct Q for sun and ambient first, and the housing follows the corrected number.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 15.6" HMI enclosure | 304 stainless | 11.69 x 17.64 x 4.13 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 21.5" HMI enclosure | 304 stainless | 14.69 x 23.03 x 3.86 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
| 20 × 16 × 6 in | 304 stainless | 20 x 16 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much heat does decoding live camera video add to a panel PC?
As an example range, 5-15 W over the static-screen draw for a fanless industrial panel PC; plan on the top of the range when several 1080p streams run continuously. A plug-in watt meter or DC clamp meter on the 24 V DC input settles it in five minutes: multiply volts by amps, so 24 V × 1.6 A = 38.4 W. Size the enclosure on the measured figure, because datasheet typical values are idle numbers.
Does the water rating of an enclosure tell me anything about how hot it runs?
Nothing. IEC 60529 tests ingress only: the second digit 6 is a 12.5 mm nozzle at 100 L/min from 2.5 to 3 m for at least 3 minutes, and temperature rise appears nowhere in it. Heat comes from wall conductance — 3.7 W/m²K for stainless in still air — so the example load needs 1.04 m² of wall to hold a 10 C rise. Our housings are manufacturer rated, not UL listed.
Can I fit a fan to cool a video panel PC in a washdown enclosure?
A fan-filter unit drops the whole assembly to the filter's own ingress rating, so on a hose-down box size the walls instead. A fully internal circulating fan keeps the rating and evens hot spots at the components, but the average inside air stays set by wall area and the 3.7 W/m²K conductance. The same holds for breathers and drains: each opening lowers the assembly to that part's rating.
What ambient should I size an outdoor video HMI enclosure for?
Start from the site's worst shade temperature and add solar gain separately; the worked example uses 35 C. When the panel PC datasheet is silent on ambient, work to 40 C, the default for industrial electronics. Keep the calculated inside air 5 C below the datasheet rating, so a 50 C-rated display gets a 45 C target — and the example load gets its 1.04 m² of wall.