Short answer: yes, and the box is built for it. The four raised dimples on the back of a metallic weatherproof box are mounting knockouts; the makers' own installation sheets list them for exactly that job. Pop them out, drive stainless screws through them with bonded sealing washers or self-sealing screws, bed the back in sealant, and run a bead along the top and sides that stops about 1 in [25 mm] short of each bottom corner so the wall side can weep. On a box listed for damp or wet locations, drill one 3 mm [1/8 in] drain hole in the bottom, inside the 3 mm to 6 mm [1/8 to 1/4 in] window NEC 314.15 allows. Mounted this way the box keeps its rating and its listing, because you fastened through the points the maker put there, not holes of your own.
Those dimples are mounting knockouts
Die-cast and sheet-metal weatherproof boxes carry thin spots in the back wall, usually four of them in a rectangular pattern. They break out with a flat screwdriver and one hammer tap from inside the box, easily, because the metal is thin there on purpose. The makers' literature identifies them as box mounting knockouts, so using them is the intended mounting method rather than field improvisation.
That distinction decides the inspection. A UL listed enclosure is evaluated to UL 50E as the factory ships it, and several makers print that drilling any hole the box was not made with voids that listing. The identified knockouts sit inside the evaluation; a fresh hole you add beside them sits outside it. Keep the instruction sheet from the box on the truck, because it settles the question at inspection in one page.
If your box has no dimples at all, it is a different job: punching clean holes in a box with no knockouts covers the tooling and the sealing that follow.
What you need
- Flat screwdriver and a hammer, or a knockout punch
- Four stainless screws with full thread engagement in solid material; count on a 1 in [25 mm] bite into sheathing or a stud
- Bonded sealing washers, a steel washer with EPDM bonded to the underside, or self-sealing screws
- Non-corrosive sealant that stays compatible with the cover gasket
- One 3 mm [1/8 in] drill bit, for the drain
- A sealing locknut or threaded hub for the cable entry
- The box's instruction sheet
| Box you are mounting | Where the screws go | Bottom of the box |
|---|---|---|
| Metallic weatherproof box, 3R-type design | Through the four mounting knockouts, a sealing washer or self-sealing screw under each head | One 3 mm [1/8 in] drain at the low point |
| Stainless wall-mount enclosure, 4X | Through the mounting feet, outside the sealed volume | No drain; every opening ordered as a cutout |
Mount the box in eight steps
- De-energize the circuit, verify absence of voltage at the box, and open the cover. Every step after this happens with the box open.
- Push the four knockouts out from inside: screwdriver tip near the center of each dimple, one firm tap. You get four clean holes, exactly where the maker planned them.
- Dry-fit the box against the siding and level it. Lap siding wants a flat block behind the box so it sits square; mark two diagonally opposite holes.
- Lay a continuous bed of sealant on the back of the box, around all four knockouts, so every screw passes through sealant on its way to the wall.
- Drive all four screws with bonded sealing washers under the heads, snug until each washer visibly compresses. The bed behind and the washer inside seal the same hole from both sides.
- Make the cable entry with a sealing locknut or a threaded hub; conduit hub or sealing locknut for outdoor entries compares the two, and the same sealing logic holds at the back of a box.
- Drill one 3 mm [1/8 in] drain hole at the lowest point of the bottom and deburr it. One hole, the smallest size in the code's window, out of direct spray.
- Run sealant along the top and both sides. On a 3 x 5 in [76 x 127 mm] single-gang box, three sides total 5 + 3 + 5 = 13 in [330 mm]; leave the bottom 1 in [25 mm] of each side open and you lay 13 - 2 = 11 in [280 mm] of bead, with two weep gaps where anything behind the box can escape.
The drain hole: what the code allows
NEC 314.15 permits drainage openings of 3 mm (1/8 in) to 6 mm (1/4 in) in boxes and conduit bodies listed for damp or wet locations. UL 50E and NEMA 250 build that drain opening into the Type 3R and 3RX designs, so a drained weatherproof box is a listed configuration. Pool electricians have drilled the 1/8 in hole for years for the reason you would expect: a box half full of water trips the GFCI feeding it. The Type 3R vs Type 4 guide draws the line between drained and sealed designs.
The line is the rating. A Type 4X or IP66 box is tested with a sealed bottom, and one drilled hole trades that rating for drainage. On sealed boxes you handle condensation with a heater or a breather instead, which the outdoor enclosures guide covers, and you buy the box with its openings already made.
Here is the arithmetic behind sealing the screws and still drilling the drain. The air inside a single-gang box is about 0.6 L [20 fl oz], or 0.0006 m³. At 20 °C [68 °F] and 80% relative humidity it holds 0.8 × 17.3 g/m³ = 13.8 g/m³ of vapor; the 17.3 g/m³ is the standard saturation value at 20 °C. Cooled overnight to 5 °C [41 °F], where air saturates at 6.8 g/m³, it gives up 13.8 - 6.8 = 7.0 g/m³. In 0.0006 m³ that is 7.0 × 0.0006 = 0.004 g, about 4 mg, under a tenth of a drop. A box found holding 300 ml [10 fl oz] of water contains roughly 70,000 times what its air can drop, so the water arrived through the screws, the entry or the cover seal. Seal those, and keep the drain for the day one of them weeps anyway. Treat the box volume and the temperatures as illustrative; the method and the saturation values are standard.
The plug side of that same 1/8 in drilled opening is standard hardware elsewhere too: 1/8 in drilled pipe plug applications shows how they are used in valve assemblies.
Checks when the box is up
- Run a hose down the wall above the box for 5 min, a sheet of water rather than a jet. Open the cover with the circuit still dead and look for tracks; a dry interior is a pass.
- Sight along the bottom: the drain sits at the true low point of a level box, and the two 1 in [25 mm] weep gaps at the corners are open.
- Press each screw head: no movement, the washer compressed, sealant squeezed out evenly around it.
- Close the cover and confirm the gasket is seated all round before the latch pulls it tight. In pool and hard-splash areas, a thin bead of gasket-compatible sealant along the top edge of the cover gasket is standard field practice.
Mistakes that cost the rating
- Fresh holes beside the knockouts. Several makers print that any other drilling voids the box's listing, and wet-location inspectors enforce it. If the holes are already in, sealing a wrongly drilled hole in an enclosure is its own repair, done with a listed plug rather than a smear of caulk.
- Caulk over the screw head and nothing under it. Water rides the threads into the box; the seal belongs under the head, as mounting screws through an outdoor enclosure without leaks shows.
- A drain hole in a Type 4X box. One hole converts a sealed enclosure into a drained one; for what cutting does to a rating in general, read what NEMA rating a panel keeps after you cut it and mount devices.
- Caulk closed all the way round. A full perimeter traps water behind the box; the two open corners are part of the design.
- A plastic box bedded flat to the wall. Its ears stand it off so the wall behind can dry; metal boxes take the sealant bed instead.
Bigger boxes mount outside the seal
A stainless wall-mount enclosure settles the bracket question by design: the mounting feet sit outside the gasketed volume, so you fasten to the wall without piercing the enclosure at all. The hinged, gasketed door and the removable mounting panel never meet a drill. Every opening you need, conduit hubs, cable glands, a breather, you order as drawn cutouts: you set the material, the width, height and depth and every cutout, from one piece, delivered in 10 business days anywhere in the world, counted from your order or from your approval of the drawing for custom work. These boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. For splices and pull points, stainless junction boxes cover the nine smallest wall-mount sizes, and the outdoor enclosures page covers what weather does to each rating.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What are the dimples on the back of an outdoor electrical box?
They are mounting knockouts. The makers' installation sheets identify them as the intended points to push out and fasten through, usually four in a rectangular pattern. Two diagonally opposite will hold a small box with a light cover; use all four when a while-in-use cover will hang a cord on the box. Because the maker put them there, using them keeps the listing; drilling fresh holes elsewhere is what voids it.
Can I drill a drain hole in a weatherproof box?
Yes, on a box listed for damp or wet locations: NEC 314.15 permits drainage openings from 3 mm (1/8 in) up to 6 mm (1/4 in), and UL 50E and NEMA 250 build that drain into the Type 3R and 3RX designs. The same rule limits it to listed boxes, so an indoor box takes no drain. On a Type 4X or IP66 box, leave the bottom alone and manage condensation with a heater.
What screws keep water out of the mounting holes?
Stainless screws with bonded sealing washers, or self-sealing screws with the seal built into the head. A bonded washer converts any stainless screw you already carry; the self-sealing screw brings its own seal, and one maker rates those at 20,000 psi [138 MPa]. Either way the seal sits under the head, where the threads pass through, not as caulk smeared over the top.
The inspector failed a box drilled through the back. Now what?
Remount through the maker-identified mounting knockouts with listed sealing hardware and keep the instruction sheet on site; shown the sheet, most inspectors accept the knockouts as the sanctioned points. If you drilled where there was never a knockout, replace the box or close those holes with a listed sealing plug. A bead of caulk over the hole will not restore a wet-location rating.