Short answer: size a starter panel from the motor's full-load current, not from horsepower. A 10 hp motor at 460 V lists 14 A in the NEC full-load current table for three-phase motors. Conductors carry at least 125% of that, 17.5 A, which 14 AWG copper covers in the 75 °C ampacity column. Overloads trip from the nameplate, sized by service factor. The branch fuse or breaker comes from the NEC motor protection multipliers: a 25 A time-delay fuse or a 35 A inverse-time breaker for that motor. With the circuit sized, the panel is layout arithmetic — bending space at terminals, half-filled duct, clear working space in front — plus a heat check that decides the enclosure size and whether it needs cooling at all. Four steps below cover the circuit; a worked example carries a 10 hp panel from nameplate to an order.
What you need
The whole job needs the motor nameplate and four code tables. Pull these before you draw anything:
- The motor nameplate: horsepower, voltage, full-load amps, service factor and the locked-rotor code letter.
- The NEC tables: full-load current for three-phase motors, the ampacity table at 75 °C, the motor protection multipliers, the bending-space table and the grounding table.
- A backplate sketch: starter, branch breaker, control transformer, terminal blocks and two wire ducts.
- Real box dimensions to draw against — the enclosure size chart lists inside and outside dimensions of catalog sizes.
Size the circuit from the motor outward
Each step feeds the next, so run them in order.
- Take each current from the document that owns it. Horsepower, voltage and service factor come from the nameplate. Full-load current for conductor and protection sizing comes from the NEC full-load current table, not the nameplate; the code builds its multipliers around its own values, and the two can differ by a few percent. The nameplate current does one job only: it sets the overload. Starting current is a third number again, 6 to 8 times full-load current for a standard design B motor; the FLA and LRA wire-sizing article works that side in detail.
- Size conductors at 125%. Continuous-duty motor conductors carry at least 125% of table full-load current. Take the result to the ampacity table's 75 °C column and pick the smallest copper size that covers it. Ambient above 30 °C, bundled conductors and long runs push the size up; keep branch voltage drop at or under 3%, the usual design practice, which starts to bite past roughly 100 ft of run. Above 10 hp the branch conductors step up through 8 AWG (50 A) and 6 AWG (65 A); land those on compression lugs crimped with the die matched to the conductor — choosing crimp tools for 6 and 8 AWG copper conductors covers the selection.
- Set overloads from the nameplate. The NEC overload rules trip at 115% of nameplate FLA for a service factor 1.0 motor and at 125% for 1.15 or higher. Pick an overload whose dial covers the setting with room on both sides.
- Pick the branch short-circuit protection. The NEC motor protection table sets the starting points in this table; round up to the next standard fuse or breaker size. An instantaneous-only breaker works only inside a listed combination controller, so a panel built from separate parts takes a time-delay fuse or an inverse-time breaker. For per-pole settings, see breaker instantaneous settings per pole in a motor panel.
| Protection in the motor branch | Multiplier of table FLA | Raise to, when starting will not hold |
|---|---|---|
| Time-delay (dual-element) fuse | 175% | 225% |
| Inverse-time circuit breaker | 250% | 400% for motors rated 100 A or less |
Lay the panel out, then size the box
Draw the backplate before you pick a box, because the layout decides the size, not the horsepower. Arrange it so the build stays cool and quiet:
- Heat high, controls low. Contactors, starters, transformers and any drive sit near the top of the backplate; the PLC, terminals and the 24 V supply sit low.
- Split the ducts. Power wiring runs in its own duct, 24 V control wiring in another, and the two cross at right angles where they must meet.
- Fill duct to half. The 50% figure is what duct makers publish as the maximum fill under NFPA 79-2012 section 13.5.2, and in practice it is all the air gaps between round cables leave; the backplate and DIN rail layout guide carries the spacing rules.
- Leave bending space. NEC 312.6 asks 2.5 in for a 2 AWG conductor with one wire per terminal, and more where the conductor crosses the box from the wall opposite its terminal (Table 312.6(B)).
- Bond the box into the fault path. Size the equipment grounding conductor from the breaker rating in NEC Table 250.122, run insulated green conductor for 6 AWG and smaller (NEC 250.119), and land it on the enclosure, the backplate and the door; the grounding and bonding guide covers the path.
- Mind the room around the panel. Keep the highest breaker handle's grip center at or below 2.0 m (6 ft 7 in) above the floor (NEC 240.24(A)), and keep clear working space in front: at least 3 ft (900 mm) deep for 0-150 V to ground in Condition 1, deeper at 480 V, with the door opening a full 90 degrees (NEC 110.26(A)). The enclosure mounting guide sets the heights.
A starter, a breaker and terminal blocks make two or more power circuit components, so the assembly is an industrial control panel under NEC 409.2, and UL 508A is the standard that lists one; the finished panel also carries its enclosure type marking (NEC 409.110). The UL 50E and panel listing guide explains the listing. With the layout drawn, box width, height and depth fall out of the backplate area and device depths; the enclosure sizing guide walks that conversion, and the worked example below adds the heat check.
Worked example: a 10 hp motor at 460 V
The case: one 10 hp three-phase induction motor at 460 V, service factor 1.15 (the standard general-purpose rating; substitute your own nameplate), feeding a starter, a branch breaker, a small 24 V control transformer and terminals. The example box measures 20 x 16 x 8 in (508 x 406 x 203 mm) outside — an illustrative size, so match a real one against the enclosure size chart. Shop ambient sits at 35 °C. The rules are the four steps above plus the method in the enclosure heat calculation guide: rise = losses ÷ (wall coefficient × area), with 3.7 W/m²K for stainless walls.
The arithmetic, step by step:
- Conductors: 14 A × 1.25 = 17.5 A. The 75 °C column's smallest copper size above that is 14 AWG.
- Overload: the nameplate sits at the table value here, and service factor 1.15 trips it at 125% of nameplate — the same figure the conductors landed on. A service factor 1.0 motor would sit at 16.1 A.
- Branch fuse: 14 A × 1.75 = 24.5 A, so a 25 A time-delay fuse — the next standard size — with headroom to 31.5 A if the start will not hold.
- Branch breaker: 14 A × 2.5 = 35 A inverse-time, already a standard frame.
- Grounding: the 30 A and 40 A rows of NEC Table 250.122 both call 10 AWG copper, so the 35 A breaker carries a 10 AWG green conductor.
- Starter frame: 10 hp at 460 V is a NEMA Size 1 starter, rated 27 A continuous.
- Heat: screen the losses at about 30 W for starter, breaker and control power together (contact and coil losses, overload electronics, transformer idle; weigh the real devices when you have them). Wall area: 2 × (0.508 m × 0.406 m) + 2 × (0.508 m × 0.203 m) + 2 × (0.406 m × 0.203 m) = 0.78 m². Rise = 30 W ÷ (3.7 W/m²K × 0.78 m²) = 10.3 K, so the box runs near 45 °C inside a 35 °C shop.
Decision: a starter-only panel this size needs no cooling hardware in a sealed stainless box. The threshold to watch is about 60 W of continuous loss in this box: the rise doubles to roughly 21 K and the interior crosses 55 °C, past the 40 °C ambient that drives and most panel electronics carry. Past that point, step up a box size or add an enclosure air conditioner, and rerun the heat guide with measured wattages.
Checks when you finish
- The reel tag on every installed conductor matches the calculation, not just the drawing.
- The overload dial sits inside its range at the nameplate setting.
- The fuse or breaker sits at or under the multiplier table's ceiling.
- Duct lids close over the fill, and every power conductor lands with its bend clear of the terminal.
- The green conductor lands on the enclosure, the backplate and the door, and the door bond flexes without pinching.
- The door opens 90 degrees, the working space in front is clear, and the highest handle sits under the height limit.
- After a full day at load, the interior temperature sits within a few degrees of the calculation; about 45 °C confirms the example panel.
- The panel carries its enclosure type marking where the inspector reads it.
Mistakes that cost the rating
- Cutting holes without rated parts. Every gland, cord grip, window and blanking plug must carry the enclosure's rating; one plain drilled hole drops the whole box to whatever that hole holds. What NEMA rating a panel keeps after you cut it and mount devices walks the rule part by part.
- Ventilating a sealed box. A fan-filter vent ends a Type 4 or 4X rating on the spot. Sealed stainless panels shed heat through the wall; anything more needs an enclosure air conditioner or a bigger box.
- Sizing from horsepower. A panel that fits the devices can still cook them; the heat calculation decides the box, not the motor frame.
- Forgetting the room in front. The panel passes the build and fails the inspection when the door cannot open 90 degrees against clear floor.
- Sharing one duct. Control wire in the power duct works on the bench and faults in the plant for years.
Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; they are not UL listed. A UL listed enclosure carries UL's own evaluation to UL 50E, and where a specification or an inspector calls for that listing, the box comes from a listed line. For which rating the environment needs, the NEMA 4 vs 4X vs IP66 rating guide sorts it out.
What goes on the order
| Where the panel lives | What to order |
|---|---|
| Dry indoor shop | Powder-coated steel, Type 12 |
| Washdown or food area | 304 stainless, Type 4X |
| Salt air, brine, chemicals, pharma | 316L stainless, Type 4X |
| Outdoor, no washdown | 304 stainless, Type 4 |
Order the box with the cutouts specified: gland and conduit entries at the positions the duct plan puts them, a window only where an HMI sits, every spare position plugged. Custom stainless enclosures builds material, dimensions and every cutout from one piece and delivers in 10 business days, counted from your approval of the drawing. Check the inside dimensions against your backplate plan — plate area, duct stacks and device depths — before you commit the depth.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
What size wire do I need for a 10 hp motor at 460 V?
The NEC full-load current table lists 14 A for that motor. Conductors carry 1.25 times table FLA, so the circuit needs 17.5 A of ampacity; 14 AWG copper is the smallest size that covers it in the ampacity table's 75 °C column. Step up one size for long runs, hot ambient or voltage drop, and keep branch drop at or under 3%, the common design practice.
Do overloads follow the NEC table current or the motor nameplate?
The nameplate. The table current sizes the conductors and the branch fuse or breaker, but the overload relay protects the motor you actually installed, so its trip setting comes from nameplate FLA. The NEC overload rules allow 115% of nameplate for a service factor 1.0 motor and 125% at service factor 1.15 or higher.
Can a motor conductor sit under a breaker larger than its own rating?
Yes, and it is normal on motor branches. The NEC protection table lets an inverse-time breaker reach 250% of table FLA because the overload relay carries the overload duty while the breaker only clears short circuits and ground faults. A breaker sized at the conductor's own rating nuisance-trips on the start, when inrush runs 6 to 8 times FLA on a standard design B motor.
How much heat does a starter panel add, and does the box need cooling?
A starter, breaker and small control supply running a 10 hp load lose roughly 20 to 30 W together — coil and contact losses, overload electronics, transformer idle. In a 20 x 16 x 8 in stainless box that is about a 10 K rise over a 35 C shop, so near 45 C inside. A sealed stainless enclosure carries that with no cooling hardware; once continuous losses reach about 60 W in that box, step up a size or add an enclosure air conditioner.