Short answer: contactor in the panel, relay on its coil. A 1 hp, 120 V single-phase pump draws about 10 A running and 60-80 A while the rotor is locked, and making that inrush is what kills contacts. UL 508, the standard for industrial control equipment, grades switching devices by load type - resistive, tungsten and motor horsepower at a stated voltage - so a 30 A resistive figure on a PCB relay covers heater duty; for a pump the number that counts is the horsepower row at your voltage. A contactor brings that rating, a clip-on overload and screw terminals for branch wire, and your relay ends up switching about 100 mA of coil instead of 10 A of pump. Both routes can be built right; the numbers show which one belongs in your box.
The rating that decides it
Contact ratings are load-specific. UL 508 separates resistive, tungsten and motor duty, and motor duty is quoted in horsepower at a stated voltage. The headline amperes on a PCB power relay are the resistive row. Datasheets in that class commonly add a motor row around 1 hp at 120 VAC; that row, at your voltage and phase, is the only one that speaks for a pump. A contactor bought on price with no datasheet buys no rating at all - the horsepower line on the nameplate or the sheet is the specification.
Running current sets the steady heating; starting sets the switching stress. An induction pump motor draws six to eight times full-load current until the rotor turns, so 60-80 A behind a 10 A nameplate. Each closure makes that current with contact bounce arcing on top of it. Each opening fights the motor's inductance, which keeps current flowing across the separating contacts. A rating proven at motor duty covers exactly this; a resistive rating was never tested for it.
Then count operations. Typical catalog endurance curves show about 100,000 operations at motor load for a PCB power relay in that amperage class, against about 1,000,000 at AC-3 duty for a compact contactor. Pressure-switch duty spends that difference fast.
Side by side: the relay against the contactor
| What you are buying | PCB power relay, 30 A class | DIN rail contactor with overload |
|---|---|---|
| Motor duty | Only with a printed hp row at your voltage | Horsepower printed per voltage and phase |
| Making locked rotor, 60-80 A at 1 hp | Covered only by that motor row | The rated job (AC-3 utilization category) |
| Stalled-pump protection | Add your own overload | Clip-on overload set to nameplate current |
| Power connections | Solder pins and traces; 10 A needs about 0.15 in of 1 oz copper (IPC-2221 chart) | Screw terminals for 14 AWG at marked torque |
| Short-circuit rating in the panel | Your board becomes the controller | Marked SCCR feeds the UL 508A panel rating |
| Three-phase pumps | Three relays, three coils, poles uncoordinated | One mechanism breaks every pole together |
| Service | Board rework | Unclip and swap, wiring untouched |
| Heat at 10 A | About 5 W in the contacts, plus the coil | 1-3 W at the terminals, 2-4 W coil |
| Footprint | On your PCB | About 45 mm of rail, plus the overload |
The pattern in the table: the relay is a component you qualify, the contactor is a starter you install.
Where the PCB relay wins
If the board is the product, the relay keeps the power path machine-made: soldered joints instead of hand-torqued lugs, no field wiring of the motor circuit, and creepage laid out in CAD where you control it. With a printed motor row at your exact voltage and modest duty - a few starts an hour, not pressure-switch cycling - a relay in the 30 A class is a legitimate motor switch, and it leaves the panel emptier than any contactor. Keep the board serviceable by mounting it in a DIN rail PCB enclosure inside a sealed cabinet. Read the horsepower row first and the amperes second; the resistive headline is the least informative number on the page.
Where the contactor wins
Motor duty is the contactor's day job. The AC-3 utilization category means it makes locked-rotor current on every start and breaks running current all day, and the clip-on overload completes the starter: the dial goes to nameplate full-load current, and a stalled pump drops the coil before the winding cooks. Screw terminals take 14 AWG stranded at a marked torque, and a three-phase pump gets every pole broken by one mechanism - three discrete relays can leave a pole made on a fault.
Listing gets simpler. NEC 409.2 defines an industrial control panel and UL 508A is the standard for listing one; a listed motor controller arrives with its ratings and short-circuit current rating already tested, and NEC 409.110 requires the enclosure type number on the finished panel. In US workplaces, OSHA 1910.303(a) requires approved equipment, which 1910.399 defines as listed, labeled or certified by a nationally recognized testing laboratory. Self-protected combinations to UL 508 Types E and F go further still: their maximum protective setting equals the motor's full-load current. Sharing a box with power distribution raises its own questions, and what the code allows inside a breaker enclosure covers them.
The coil is the job your relay keeps
Here is the build that answers the real question: relay and contactor, each at its own current. A 24 V DC coil on a compact contactor holds at 2-4 W - 80-170 mA - which a PLC transistor output in the 0.5 A class drives directly and a microcontroller pin at about 20 mA cannot; put a logic relay or a MOSFET between them. Suppress the coil or the switch-off transient eats the driver: a diode across a DC coil, an RC snubber across an AC coil, with the trade-offs worked through in relay coil suppression: diode for DC, snubber for AC.
Worked example: a 1 hp 120 V pump in a 16 x 16 x 8 in box
Inputs - replace each with your own:
| Input | Value | Source |
|---|---|---|
| Motor | 1 hp, 120 V, single phase, 10.0 A nameplate, SF 1.15 | nameplate |
| Duty | pressure switch, frequent starts | your process |
| Enclosure | 16 x 16 x 8 in stainless, 35 C ambient, k = 3.7 W/m2K | catalog and site |
| Panel heat | contactor 5 W, 24 V supply 3 W, controller 7 W, 15 W total | this example's assumption |
Rules in words: pick the switch from the horsepower row at 120 V; set the overload dial to nameplate current, with the NEC's trip ceiling at 125% for a 1.15 service factor; size the branch conductor at 125% and an inverse-time breaker at 250% of full-load current; enclosure rise is heat divided by wall transfer times surface.
The arithmetic:
- Locked rotor: 6 x 10 = 60 A to 8 x 10 = 80 A; carry 70 A as the stall case.
- Overload: dial at 10 A, ceiling 1.25 x 10 = 12.5 A.
- Conductor: 1.25 x 10 = 12.5 A, so 14 AWG copper at 15 A in the NEC's 60 C column.
- Breaker: 2.5 x 10 = 25 A inverse-time, a stock size.
- The relay doing the same job: contact resistance about 50 mOhm, the datasheet maximum for the class, so running loss is 10 x 10 x 0.05 = 5 W - and during a stall 70 x 70 x 0.05 = 245 W into one solder joint until something clears.
- Box surface: 16 x 16 x 8 in is 0.41 x 0.41 x 0.20 m, so 0.66 m2. Rise: 15 / (3.7 x 0.66) = 6.1 K, putting the inside at 41 C in a 35 C room - past the 40 C ambient most control gear carries unless its datasheet says more.
- One size up, 20 x 20 x 8 in = 0.93 m2: 15 / (3.7 x 0.93) = 4.4 K, so 39 C.
Decision: contactor with overload, relay on the coil, and the 20 x 20 x 8 in box. Keep the air inside at or below 40 C; the smaller box only works if panel heat drops to 12 W, and 12 / 2.44 = 4.9 K still sits at 40 C with no margin.
The decision by case
- Your board is the product, the datasheet prints the motor row at your voltage, starts run a few per hour, and you own the trace heating and protection: the PCB relay, chosen deliberately.
- Pressure-tank cycling, stall-prone pumps, three-phase motors, or a panel other people will service: the contactor with its overload.
- Washdown or outdoor sites: the contactor lives inside a 316L body where salt air, brine or chlorides reach it, 304 stainless for general washdown, and the controller board stays out of the spray.
What to put on the order
Custom enclosures take your material, width, height, depth and every cutout, built from one piece and delivered in 10 business days from your approval of the drawing. For this pump panel: a 304 stainless body for indoor washdown, 316L where salt air, brine or chlorides are present. Ratings on our boxes are manufacturer ratings - NEMA 4X / IP66, not UL listed - and Type 12 is the indoor pick where water is not the threat.
Layout items worth writing on the drawing:
- 2 in [50 mm] between the bottom wall and the lowest terminal for cord up to 0.5 in [12 mm] OD; double it for armoured cable.
- About 100 mm of DIN rail for the contactor and its overload, with duct below filled to half - the fill limit one duct maker prints from NFPA 79-2012 13.5.2.
- A mounting height that keeps the breaker handle grip no more than 6 ft 7 in [2.0 m] above the floor, the height NEC 240.24(A) allows.
The backplate and DIN rail layout guide sets the row spacing, the enclosure selector turns rail count and inside height into a size, and sizing an IP65 enclosure for a motor starter and contactor walks the heat for a starter-heavy build.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 16 × 8 in | 304 stainless | 16 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 20 × 8 in | 304 stainless | 20 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a 30 A PCB relay switch a 1 hp 120 V pump?
Yes, when the datasheet prints a horsepower rating at 120 VAC - that row is proven at motor duty under UL 508's load categories. A resistive amperage figure alone covers none of the 60-80 A locked-rotor making duty. Count cycles too: at 20 starts an hour, a small pressure tank logs 20 x 24 x 365 = 175,200 operations a year, against roughly 100,000 operations of typical relay endurance at motor load.
How do I drive a contactor coil from a 3.3 V microcontroller?
Through an interposing stage - a logic MOSFET or a small relay sized for the coil. A 24 V DC coil holds at 2-4 W, roughly 80-170 mA, while a microcontroller pin is comfortable near 20 mA; a PLC transistor output in the 0.5 A class drives it directly. Put a flyback diode across the DC coil and an RC snubber across an AC coil.
Does the contactor protect the pump on its own?
It switches; the overload protects. Set the overload dial to nameplate full-load current - 10 A in the worked example - and the NEC's trip ceiling is 125% of that, 12.5 A, for a 1.15 service factor. A Class 10 overload clears a locked rotor in about 10 s, where a 25 A inverse-time breaker can carry 70 A for tens of seconds.
Which device makes a UL 508A panel easier to list?
The contactor, by a wide margin. Listed motor controllers arrive with horsepower ratings and a marked short-circuit current rating, and UL 508A builds the panel rating from those marks - a 25 kA controller between 65 kA breakers can still support a 65 kA panel. A relay on your own board makes the assembly the controller, and every rating in it becomes yours to document.