Motor starter and wire sizing: FLA, LRA and the 125% rule

Size motor branch conductors at 125% of the NEC table full-load current, not the nameplate and not the locked-rotor amps: for a 125 HP, 460 V three-phase motor the table says 156 A, so 1.25 x 156 = 195 A and 3/0 copper at 75 C terminals. The starter comes from the NEMA size chart: Size 5 covers 200 HP at that voltage. The 908 A locked-rotor figure is covered by the starter's motor-switching duty, the overload relay's time curve and a starting voltage-drop check.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 7 min read

Short answer: size the branch conductors at 125% of the full-load current the NEC table lists for the horsepower, and pick the starter from the NEMA size chart at your voltage. For a 125 HP, 460 V three-phase motor the table says 156 A, so you need 1.25 x 156 A = 195 A of ampacity. That is 3/0 copper at 75 C terminals. The same motor takes a NEMA Size 5 combination starter: Size 4 stops at 100 HP and Size 5 covers 200 HP. Its 270 A continuous rating sits far above the 143 A nameplate. The 908 A locked-rotor figure never sizes the wire; it feeds two separate checks — starting voltage drop and the starter's motor-switching duty.

Which current sizes which part

A motor circuit has three protection jobs, and each one reads a different current. Mix them and you oversize the wire, or you land an overload setting that hides a real problem. Three numbers do all the work:

Current Where you read it What it sizes
Table FLA NEC three-phase table, 125 HP row at your voltage Branch conductors at 125%; breaker and disconnect at their own percentages
Nameplate FLA Motor nameplate Overload relay setting at 115% or 125%
Locked-rotor current Motor data at rated voltage Starting voltage drop; carried by the starter's motor-switching duty

The NEC's motor rules work from the table because they have to fit any 125 HP machine you connect. A specific nameplate can read lower, and the conductors still take the table basis; the table entry governs unless a nameplate reads higher. Once the motor is up to speed, the load sets the current: a lightly loaded blower runs below nameplate, a fully loaded one sits at it.

Where the 115% comes from

The 115% you half-remember belongs to the overload relay, not the wire. The motor rules cap that setting at 115% of the nameplate full-load current on a general-purpose machine. They allow 125% when the nameplate shows a 1.15 service factor or a temperature-rise marking of 40 C or less. On this nameplate that is a relay set near 164 A, or near 179 A on the service-factor machine.

A second 115% rule lives on the disconnect: it must carry at least 115% of the table current, which is 179 A here. The Size 5 unit's 270 A clears that with room to spare. Conductor sizing reads a different current with a different multiplier — 125% of the table value — and the two never mix. Service factor shapes the overload; the table shapes the wire.

The sizing, step by step

  1. Read the table current. NEC three-phase, 125 HP at your voltage gives 156 A here. Bring in the nameplate figure only when it is the higher of the two.
  2. Multiply by 1.25. That is 195 A minimum ampacity, before any ambient or grouping correction. In the 75 C copper column, 2/0 at 175 A falls short and 3/0 at 200 A clears it.
  3. Pick the starter by horsepower. The NEMA ICS 2 size tables list Size 4 to 100 HP and Size 5 to 200 HP at that voltage, so 125 HP is Size 5, with a 270 A continuous rating in the makers' tables.
  4. Set the overload from the nameplate. 115% of the nameplate current is 164 A; 125% is 179 A when the nameplate carries a 1.15 service factor or a 40 C rise marking.
  5. Set the breaker by its own rule. An inverse-time breaker in a motor branch reaches 250% of the table current: 390 A. Since that is not a standard rating, the next size up, 400 A, goes into the Size 5 unit.
  6. Check the start. Voltage drop at locked-rotor current over your actual run, against a blower's tolerance of about 15% at the motor terminals — worked below.

Worked example: 125 HP blower, 100 ft to the MCC

Inputs, each from the machine data or the code table: a 125 HP three-phase 460 V Design B blower motor; nameplate 143 A; locked-rotor 908 A at rated voltage; a one-way route of 100 ft; a NEMA Size 5 combination starter with a 270 A continuous rating and a thermal-magnetic breaker; the NEC table value, 156 A.

Rules in words: conductors carry 125% of the table current. Three-phase cable drop is 1.732 x current x the run's resistance, and 3/0 copper runs about 0.077 Ω per 1000 ft at 75 C in the standard copper tables — resistance only, no conduit reactance.

Arithmetic:

  • Conductor: 125% of the table value = 195 A → 3/0 copper, 200 A at 75 C terminations.
  • Overload: 115% of nameplate = 164 A, or 125% = 179 A on a 1.15-service-factor motor.
  • Breaker: 250% of the table value = 390 A → next standard rating, 400 A.
  • Start drop: 1.732 x 908 A x 0.0077 Ω = 12.1 V, which is 2.6% of rated voltage.
  • Run drop: 1.732 x nameplate current x 0.0077 Ω = 1.9 V, or 0.4%.

Decision: order 3 x 3/0 copper plus a 3 AWG copper equipment grounding conductor, sized from the 400 A device ahead of it, the Size 5 unit with its 400 A breaker, and an overload set at 164 A to 179 A. A 2.6% cable drop leaves you far inside the 15% starting allowance once the transformer's share is added. Running at 0.4% is a tenth of the usual 5% figure, so the ampacity pick stands. Even if total impedance came to double the resistance-only value, the start would still see about 5% of drop from the cable alone.

What the 908 A has to clear instead

The ratio 908 / 143 = 6.35 is textbook Design B, which locks rotor at six to seven times full load. Copper heating runs with the square of current, so the instantaneous rate at lock is (908 / 143)² = 40 times the running rate — for the seconds a start lasts. Two devices are built for exactly that duty.

The overload relay's curve lets a start through and trips on sustained overload. Trip classes are defined by how fast they trip at 7.2 times their setting: Class 10 inside 10 s, Class 20 inside 20 s, Class 30 inside 30 s. Pick the class that exceeds your blower's measured acceleration time; a loaded fan is the reason Class 20 and Class 30 exist.

The starter carries the making current through its size rating. A Size 5 has to start the largest motor in its class — 200 HP, a 240 A table machine whose locked rotor runs six to seven times that, past 1,400 A. The 908 A in this example sits comfortably inside that duty, which is why the horsepower chart selects the starter and the 270 A figure only confirms it. Trust the size designation from a major maker, and read the one line that changes it: plugging and jogging service lower the listed horsepower, as the NEMA ICS 2 service notes in every starter catalog state.

The enclosure the starter lives in

A Size 5 combination unit is a large assembly, and in an MCC it takes the wide bucket shown on the maker's dimensional drawing. Stand it in its own enclosure and the conductors drive the box as much as the starter does. Landing 3/0 takes bending space. NEC 312.6 sets it by conductor size in two tables, one for conductors that enter the wall opposite the terminal and one for those that do not, so plan the depth around it — the guide to sizing an electrical enclosure carries those tables. Entries come sized to the cable, with knockout diameters from UL 50's fitting dimensions; the cutouts and glands guide covers the details.

Bond the backplate or bucket and land the 3 AWG grounding conductor on it. NEC 250.12 wants paint, lacquer and enamel off the threads and contact surfaces at those connections, and the grounding and bonding guide walks the whole path. Heat joins the job too: the coil, breaker and conductors each add watts, and an MCC's heat adds up starter by starter rather than from the bus amps. When the starter stands in its own sealed box, run the total through the enclosure heat calculator.

Outdoors or in a washdown area, a standalone starter wants 316L stainless; our enclosures are rated NEMA 4X / IP66 by the manufacturer, not UL listed. At 3/0 scale you are into custom depth for the bending space, and custom enclosures are delivered in 10 business days from your approval of the drawing — the enclosure selector carries the inside dimensions to a quote. Mark the finished assembly's short-circuit rating against the fault current at the bus: the SCCR calculation for industrial control panels page covers the method, and disconnect switch sizing with SCCR covers the switching side. If the spec prefers fuses to the thermal-magnetic breaker, when to use a fused disconnect on motor circuits settles that choice.

Checks that prove the design

  • Starting voltage at the motor terminals: 2.6% of cable drop plus the transformer's share. For a blower, whose load torque rises with the square of speed, keep the total at or above 85% of rated voltage, about 391 V here.
  • Motors already running on the bus during the start: at least 95% of rated at their terminals, about 437 V in this case.
  • Running drop at nameplate current: 0.4% on this run, far inside the usual 5% figure.
  • Breaker: 400 A against its 390 A ceiling by next-standard rounding; overload class longer than your measured acceleration time; relay set between 164 A and 179 A.
  • Your bucket's watts added to the MCC heat total, or to the standalone box's heat balance.

Land nothing on a live bucket. Open the upstream device, lock it out, and check for absence of voltage at the starter's line side before you terminate.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Why does the NEC table show 156 A when the nameplate says 143 A?

The table entry covers the worst motor in that horsepower and voltage class, so it reads higher than an efficient nameplate. Conductor, breaker and disconnect sizing all start from the table figure; only the overload relay works from the nameplate. When a nameplate reads higher than the table, the nameplate governs everything downstream.

Will the 908 A locked-rotor current ever force a bigger wire size?

Through voltage drop, yes; through ampacity, no. At 908 A, each 100 ft of 3/0 copper drops about 12 V, so a 400 ft run drops roughly 48 V, near 10.5% of rated voltage before the source dip. When cable drop plus the transformer dip pushes the motor below about 85% of rated voltage during start, upsize the conductor.

What if the 400 A breaker trips during the start?

Measure before you change anything. Record the acceleration time and the current trace: a blower that takes longer than its overload class will also sit near locked-rotor current on the breaker curve. The motor rules already place you at the 250% ceiling, rounded up to that 400 A rating, so a trip points at a slow start — low voltage, unbalance or a damper that should start closed — rather than at the breaker.

Can I set the overload above nameplate if the motor runs hot?

Set it from the nameplate rule — 164 A at 115% or 179 A at 125% with a 1.15 service factor — and fix the heat instead. A motor pulling above nameplate is overloaded, under-volted or running on an unbalanced supply; raising the relay only moves the damage into the windings. The relay's curve already rides through the 908 A start, which lasts seconds.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece