Short answer: a switch with three different fuses is still one protective device in the study, and you plot it on the curve of the pole that clears last. Same class and same ampere rating across three makers: plot any one curve and note the brands on the one-line. RK1 and RK5 mixed in one switch: plot the RK5, which at a 10 kA available fault passes about 7 kA RMS let-through where an RK1 of the same rating passes about 4 kA. Different ampere ratings are a field defect, not a modeling choice — record them, bound the study with the largest and smallest rating, and replace the set.
What the model has to represent
Your study software draws one fuse symbol per switch and hangs one time-current curve on it. Physically, each pole's cartridge sits in series with its own phase conductor, so each phase is cleared by its own fuse. A three-phase bolted fault drives all three poles and the first cartridge to melt wins; a line-to-ground fault drives one pole alone. The single curve you plot stands in for whichever pole actually clears the fault on the table, and the defensible stand-in is the pole with the later curve and the higher let-through — the bounding pole. Pick that one, and the rest of the study follows.
Why mixed sets happen
Class RK1 and RK5 cartridges share the same standardized 600 V AC body, and both classes carry interrupting ratings up to 200 kA, so either class clips into the same switch and a mixed set looks entirely normal with the door shut. Years of truck-stock replacements do the rest: different makers go in one at a time as fuses blow, and one day a different class lands beside them with nothing to flag it. Curves for equivalent catalog numbers from different makers track within a few percent at the same class and ampere rating, which is why brand mixing alone is a paperwork problem. Class mixing changes the let-through, so it changes the model.
The curve to plot, by as-found set
| As-found set | What governs the model | Curve to plot | Paperwork |
|---|---|---|---|
| One class, one ampere rating, makers differ | Equivalent curves track closely | Any installed maker's curve | Note the brands on the one-line |
| RK1 and RK5 mixed, ampere ratings equal | RK5 clears later and lets more through | The RK5 curve | Note both classes and which one you modeled |
| Ampere ratings differ | Protection is unbalanced pole to pole | Both bounds: largest and smallest | Field defect; replace with a matched set |
| Voltage rating below the bus, or interrupting rating below the available fault | Capability, not curve shape | None until replaced | Flag to the owner |
Enter the ampere rating exactly as printed on the label; the library entry supplies the class, and the rating bends the curve. Every departure from a matched set goes on the one-line as a note, so the next engineer can rebuild your choice from the drawing alone.
Why the RK5 bounds a mixed set
RK1 is the more current-limiting class: it clears faster at high fault current and leaves a lower peak let-through current and less let-through energy behind it. The RK5 sits later in time and passes more, which makes it the safe stand-in for both outputs a study produces. For coordination, the upstream device stays to the right of the switch's total-clearing curve across the whole current range. A margin that holds against the RK5 also holds against the faster RK1 poles. For arc flash, incident energy at a given arcing current rises with clearing time, so the RK5 keeps the result honest; when you compare two candidate curves, compare current times time at the arcing current, never time alone. Confirm the library entry includes the fuse's current-limiting region, because that region decides the answer at high available current.
A third output rides on the fuses: the panel's short-circuit rating. Constructions built on current-limiting fuses name the class — often the catalog series — they were validated with, and a mixed set takes that basis away. Raising panel SCCR with a current-limiting fuse branch covers that construction; settle the marked rating once the set is matched.
Bounding a mixed 50 A set at a 10 kA available fault
The inputs, and where each comes from:
- As-found label photo for the switch: two 50 A Class RK1 cartridges and one 50 A Class RK5 — a 50 A field case, with the two classes sharing the 600 V body that lets them mix silently.
- Available fault current at the switch: 10 kA RMS symmetrical, from your short-circuit study — the value the class comparison below is quoted at.
- Class behavior, from fuse-class references: at a 10 kA available fault and the same ampere rating, an RK1 passes about 4 kA RMS let-through and an RK5 about 7 kA. Your own pair of numbers comes off the published peak let-through chart for the exact catalog number you photographed.
Rule in words: plot the pole with the later curve and the higher let-through — here the RK5 — and size the gap between the classes on let-through current and on the current-squared product that drives let-through energy.
The arithmetic, written out:
7 kA ÷ 4 kA = 1.75, so the RK5 pole passes 75% more RMS let-through current into its branch.
(7 kA)² ÷ (4 kA)² = 49 ÷ 16 = 3.06, so the current-squared product — the driver of let-through energy, I²t — is about three times higher through the RK5 pole.
Result: the switch is modeled as one 50 A RK5 time-current curve.
Decision: whenever both classes appear in one switch, the RK5 governs; a 3-to-1 energy gap is the size of the error an RK1-only model would hide. Note the mixed classes on the one-line, and put a matched replacement set on the next planned-outage list.
When the ampere ratings differ
Different ratings across the poles are a defect, not a modeling option — say 40 A, 50 A and 60 A across the three phases of one switch. The smallest cartridge opens on a load the others still carry, and the largest lets more current into its phase than that conductor is protected for. Record each pole's label data, then run the study twice — once on the largest rating, once on the smallest — and let the worse coordination or incident-energy result govern. Time-current curves are the standard tool for comparing fuses of different ratings, so the two-bound run is routine work. Replace the set with a matched one and the single-curve model applies again.
Recording the as-found set
Open the switch only with the feeder locked out under your site's electrical safety program, and only as a qualified person. Where the disconnect sits in its own enclosure, the line terminals stay energized until the upstream feeder is opened — why the line side stays live in a separate disconnect enclosure is the page to re-read first.
Record, per pole: maker, catalog number, class, ampere rating, voltage rating and interrupting rating, exactly as printed. On a typical 480 V industrial bus, the 600 V rating printed on an RK cartridge covers the voltage with margin, but the check is still yours to make. Compare the voltage rating with the bus voltage and the interrupting rating — commonly 200 kA for RK cartridges — with the available fault current. Replace any cartridge that falls short before any study work; the model assumes a fuse that can clear the fault in front of it. Photograph the labels and file the photo with the study so the as-found condition survives the replacement. Outdoor and washdown switches usually sit in boxes rated NEMA 4X / IP66 by the manufacturer, not UL listed, and the same open-door look covers the gasket; stainless NEMA 4X enclosures are the usual housing there.
What to specify on the replacement
Buy a matched set — one class, one ampere rating, one maker — and keep labeled spares at the switch. Both RK classes come as dual-element, time-delay cartridges, and fuse-makers' application guides size either class at 125-150% of motor full-load current, so a 40 hp 460 V motor at 52 A full-load current takes a 65 A cartridge either way. Choose the class for its let-through, not for holding the start; when to use a fused disconnect on motor circuits walks through that sizing. Keep the RK1 and the exact catalog series wherever the panel's SCCR validation names them.
Put the modeled condition on the one-line every time the installed set departs from a matched one. If the finding pushes you toward a new switch or a new panel, PLC panel disconnect switch sizing covers the load and feeder side, and the housing is an environment choice the enclosure selector settles by rating and inside dimensions. On the listing side, what UL 50E and NEMA 250 listing means is the background: UL 508A is the standard for listing an industrial control panel, and NEC 409.110 puts an enclosure type number on the panel. The study file and the panel marking should tell the same story.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Do fuses from different manufacturers need separate curves in the study?
Plot one. Pick any installed maker's curve at the labeled ampere rating and note on the one-line that the switch holds mixed brands. Before you file the study, pull the currently published time-current curve for the exact catalog number you photographed, because library entries lag catalog revisions.
Why does the RK5 curve stand in when RK1 and RK5 are mixed?
Because it bounds both outputs. The RK1 class clears faster at high fault current with lower peak let-through, so the RK5's later and higher-let-through curve holds the coordination margin against both classes and keeps the arc flash result from coming out low. At a 10 kA available fault the class comparison runs about 7 kA RMS let-through for the RK5 against about 4 kA for the RK1.
What do I do with three different ampere ratings in one switch?
Treat it as a defect and plan the replacement. Until the matched set goes in, record every pole's label data and run the study twice, once on the largest rating and once on the smallest; the worse coordination or incident-energy result governs. On a motor load the smallest cartridge opens first and leaves the motor single-phased, which is why this one does not wait for a convenient outage.
Can a mixed fuse set change the panel SCCR?
It can. Short-circuit ratings built on current-limiting fuses carry the class, and often the catalog series, that the construction was validated with, so a mixed set leaves the marked rating without its basis. Re-check the rating for the matched set you install, and meanwhile read the RK5's let-through as what the downstream branch actually sees.
How do I read a fuse peak let-through chart?
Up, over and down: start at the available fault current on the horizontal axis, go up to the curve for your ampere rating, then across to the vertical axis and read the let-through current. Run it for both classes at the same available current; the gap between the two readings is the let-through difference your model has to bound.





