Short answer: before anyone cuts sheet for your automation cabinet, five things go on paper: the environment and its rating target, a device-by-device heat schedule, a scaled internal layout, a cutout drawing dimensioned from fixed datums, and the name of who signs for the finished assembly. A workshop builds exactly what the drawing says, nothing else. Ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed. We build to your size and cutouts, delivered in 10 business days anywhere in the world, counted from your approval of the drawing.
What has to be on paper before anyone cuts sheet?
Five items, and each ends in a number or a name: the rating target for the environment, the watts the cabinet must shed, the layout's clearances, every cutout from its datums, and the party who marks the finished panel. Treat the drawing package as the whole specification. The minimum package:
- Environment line: indoor or outdoor, washdown or dust, chemicals, the ambient range, and the NEMA type or IP code you target.
- Heat schedule: every device's loss in watts, summed, with the maximum ambient you design to.
- Scaled layout: mounting plate, DIN rail, wire duct, terminals and cable zones drawn to scale, with bend space and tool access.
- Cutout drawing: every opening dimensioned from two datums, with the gland, plug or device seal named for each.
- Marking responsibility: the company that completes the assembly and puts its name on the panel.
The sections below take them in the order you meet them.
What rating does a machine-mounted automation cabinet need?
A machine-mounted cabinet facing washdown, coolant spray or outdoor air targets NEMA 4X; a dust-only indoor machine gets by with Type 12, and both hold their rating through the door gasket. NEMA 4X is the hose-down type with corrosion protection, and its usual companion marking, IP66, means a first digit 6, dust-tight, and a second digit 6, powerful jets from a 12.5 mm nozzle at 100 L/min. Neither marking covers immersion. Standing water is immersion duty: Type 6P, built as a custom design to an agreed depth, duration and fluid.
Put the seal on the drawing, in these terms:
- One continuous molded gasket around the door opening, material named. EPDM holds about −50 to 150 C and takes hot water, steam and caustic; silicone spans about −60 to 200 C but weakens against hot caustic.
- Every cable entry sealed by a gland rated for the target, and every unused opening closed with a rated plug.
- Windows and operator-panel cutouts sealed with the device's own gasket and clamped to the door.
A rating is a manufacturer's statement about a defined design. A shop that cannot show a test or a design basis for its door sells you a gasket, not a degree of protection, so ask who puts their name on the number before the first sheet is cut.
How do you total the heat the cabinet must lose?
Add up the watts each device turns into heat: a packaged 24 V DC supply sheds roughly 10-20 % of its output, and each energized relay coil a few watts, so a small automation cabinet lands near 70 W. Build the schedule before you size anything:
- List every device with its loss in watts at the load it actually runs, and its ambient ceiling, usually 40 C (104 F) for drives and most electronics unless the datasheet allows more.
- Count the relay coils energized at the same time, not the total on the drawing.
- Take conversion loss from one operating point: loss = input − output, or output × (1 − efficiency) / efficiency.
Worked example. One 24 V DC supply at 10 A, so 240 W output, at 85 % efficiency: loss = 240 W × 0.15 / 0.85 = 42 W. Eight interface relays energized together at 2 W per coil: 16 W. Terminals and indicators: allow 10 W. Total 42 + 16 + 10 = 68 W.
Now the cabinet: a 304 stainless box, 800 × 600 × 300 mm, wall-mounted, so five free faces, 1.32 m². With k = 3.7 W/m²K for stainless, it sheds 3.7 × 1.32 = 4.9 W per kelvin of rise. The rise is 68 / 4.9 = 13.9 K, so at 25 C ambient the interior sits at 39 C. That clears the 40 C ceiling by 1 C, which is thin: sun on the door, still air or a device added later pushes it over, and then you go up a size or add sealed cooling.
At 30 C ambient the same box fails at 43.9 C inside. You need 68 / (3.7 × 10) = 1.84 m² of free surface for a 10 K rise, and a 1000 × 800 × 400 mm cabinet gives 2.24 m², landing the interior at 38 C.
Mounting changes the free area, and the surface area by mounting type article has the factors. When a datasheet gives no loss figure, the heat loss values article shows how to get one.
How much space does the layout need?
Size the cabinet from the wiring: fill wire duct to at most 50 % of its interior cross-section, give terminals their NEC 312.6 bend space, and keep 2 in [50 mm] between the bottom wall and the terminal entry. The checks, as numbers:
- Wire duct at 50 % fill: one duct maker caps all its fill tables there, citing NFPA 79-2012 section 13.5.2, because round cables leave air gaps. A 60 × 40 mm duct holds 1200 mm² of wire, no more.
- Bend space by wire size from NEC 312.6: 2 AWG with one wire per terminal needs 2.5 in [64 mm] when the conductor does not enter the wall opposite its terminal.
- 2 in [50 mm] below the terminal row for cable up to 0.5 in [13 mm] OD, doubled to 4 in [100 mm] for armoured cable.
- Device clearances as each datasheet gives them, heat sources placed high and heat-sensitive parts low, with clear air between.
In front of the door, NEC 110.26(A) sets working space wherever the panel is serviced live. The depth is at least 3 ft (900 mm) at 0-150 V to ground in Condition 1, more at higher voltages. The width is at least 30 in [760 mm] or the equipment width, the height at least 6.5 ft [2.0 m] or the equipment height, and the door needs room to open at least 90 degrees. On a machine, check that swing against the frame before the cabinet exists.
The backplate and DIN rail layout guide has duct and rail spacing, and the enclosure sizing guide walks depth and fill. For the operator display, the machine-mounted HMI article covers its cutout and seal.
What belongs on the cutout and sealing drawing?
Dimension every opening from two fixed datums, the bottom edge and the hinge-side edge, and name the gland, plug or device that seals each one, so nothing on the door is left to guess. The drawing carries:
- Hole size, corner radius and position for every opening, taken from the device maker's template, with the sealing land flat and clear of welds.
- A gland schedule: entry size, gland type and the cable OD range each must grip, so the shop drills exactly the entries on the list.
- Gasket material and profile, written on the drawing so the seal is part of the design.
- Protective bonding: a stud on the body, one on the door and one on the mounting plate, bonded so they carry any fault current imposed on them, as NEC 250.96(A) requires, with paint cleared from the contact surfaces under NEC 250.12. The grounding and bonding guide sizes that conductor from the breaker ahead of it.
Every opening added after delivery is your work, and the rating of that opening sits with you. Plan the operator-panel and cable cutouts on the drawing instead of on the machine; the cutout drawing checklist lists what a quote needs, and the cutouts and glands guide has knockout and gland dimensions.
Who signs for the finished panel's rating?
The party that completes the assembly signs for it: NEC 409.110 puts the enclosure type number on an industrial control panel's nameplate, and UL 508A is the standard for listing one. Your relays and 24 V DC supply in one box make an industrial control panel under NEC 409.2, an assembly of two or more power-circuit or control-circuit components. In US workplaces, OSHA 29 CFR 1910.303(a) requires electrical equipment to be approved, and listing by a nationally recognized testing laboratory is the usual route.
Our enclosures are one component of that panel, rated NEMA 4X / IP66 by the manufacturer; not UL listed. When the job calls for a listed panel, a UL 508A panel shop lists the finished assembly, and it will ask for your heat schedule and layout, so keep both current. The listing guide explains what a listing covers and what a manufacturer rating covers.
One habit for first power-up: isolate the cabinet and prove absence of voltage at the terminals before you touch anything inside.
What do you send with a quote request?
Send five things: outside width, height and depth, the material, the NEMA type, the cutout drawing with its datums, and the heat schedule with your design ambient. Each one pins down part of the build:
| You send | It pins down |
|---|---|
| Width × height × depth and mounting | The blank, and the free surface for the heat check |
| Material, 304 stainless or 316L | 304 for indoor washdown and machine building; 316L where salt air, brine or chlorides reach the cabinet |
| NEMA type, 4X for washdown duty | The gasket and entry spec |
| Cutout drawing with datums and gland schedule | Every hole, sealed by name |
| Heat schedule with design ambient | The size that passes |
The enclosure builder takes your size, material, NEMA type and cutouts in 3D and returns a drawing for your approval, and custom enclosures start at one piece. Delivery is 10 business days anywhere in the world, counted for custom work from your approval of the drawing, so the drawing you send is the cabinet you get.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a plain control transformer count the same as a 24 V DC supply in the heat schedule?
Not quite. A dry-type transformer loses about 1-3 % of its rating, so a 300 VA unit adds only 3-9 W of heat. But a transformer alone gives you AC: the rectifier and regulator behind it each add loss, often more than the transformer's own. Count each stage at its real load, or fit a packaged supply and take its 10-20 %.
What if the power supply datasheet gives only an efficiency?
Work the loss out at the load you actually run: loss = output × (1 − efficiency) / efficiency. At 90 % efficiency a 240 W supply loses 240 × 0.10 / 0.90 = 27 W; at 85 % the same supply loses 42 W. Published efficiency usually falls at part load, so use the curve point nearest your real draw.
What happens to the heat check on a 35 C day?
Your headroom drops to 5 K, because 40 C stays the ceiling for most electronics. The example's 68 W then needs 68 / (3.7 × 5) = 3.7 m² of free surface, while a 1200 × 1000 × 400 mm cabinet offers about 3.0 m². At that ambient, shed load or add sealed cooling such as a cabinet air conditioner; a fan-and-filter would break the washdown rating.
Does a bigger cabinet always run cooler?
Yes, and predictably: heat shed goes with the free surface, and surface grows with the square of the dimensions. Double the example box to 1600 × 1200 × 600 mm and the five free faces go from 1.32 m² to 5.28 m², so the same load gives a 3.5 K rise instead of 13.9 K. Past about a doubling, the cabinet gets impractical and sealed cooling takes over.





