MCCB ratings explained: frame size, In, Ue, Ui, Icu and Ics

Read an MCCB nameplate as one chain: Ue sets the voltage you may switch, In sets the load you may carry (a 125 A rating holds at the 40 C reference ambient the maker calibrates to), and Icu in kA must cover the prospective fault current at your panel. Because the breaker sits in a warm enclosure, derate In by the air temperature at the breaker, and pick Ics by how fast the process must restart.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 9 min read

Short answer: read an MCCB nameplate as one chain, not six separate numbers. Ue sets the voltage you may switch and interrupt at. In sets the load you may carry, and a plate value of 125 A holds only at the 40 C (104 F) reference ambient the maker calibrates to. Icu in kA must cover the prospective fault current at your panel, and Ics says whether the breaker still works after clearing it. The step most builds miss comes last: the breaker sits in a box where the air runs hotter than the room, and every kelvin above 40 C trims the current it may carry. Work the chain in that order and the nameplate picks the breaker for you.

The six marks on the nameplate

Mark Name on the datasheet What it decides for your panel
Frame size frame rated current, A The body class: terminal capacity, outline and which trip units fit
In rated current, A The continuous load it carries at the reference ambient, 40 C (104 F) on most IEC 60947-2 industrial MCCBs
Ue rated operational voltage, V The supply voltage the breaker is built to switch and interrupt
Ui rated insulation voltage, V The dielectric reference its insulation is designed and tested to
Icu ultimate breaking capacity, kA The highest fault current it can clear, quoted per Ue row
Ics service breaking capacity, kA The share of Icu it clears and stays in service afterwards

Read the marks in the order the power flows: Ue first, then In, then the two kA numbers. The frame is the chassis, and a 125 frame accepts several rated currents and trip units across one outline and one terminal set. On an adjustable unit the setting you dial can sit well below In, and that setting, not the frame number, is what protects the cable. Write the frame, the trip unit and the setting as three separate lines on the panel drawing, because a substitute breaker in the same frame can arrive with a different trip range.

Ue and Ui: switching voltage versus insulation

Ue, the rated operational voltage, is the supply voltage at which the maker assigns performance, including every kA figure on the datasheet. Match it to the system voltage, the AC or DC nature of the circuit and the pole connection before you compare anything else. Ui, the rated insulation voltage, is the dielectric reference the insulation is designed and tested against, and it sits above Ue by design. Ui sizes the insulation; Ue caps the operation. A breaker marked Ui 690 V is not a 690 V breaker when its Ue reads 400 V, and a high Ui never lifts that cap.

Then check two traps. The kA table is indexed by Ue, so the same frame shows a different Icu on each voltage row: copy the capacity from your row, not the boldest one. DC needs its own row too, because many AC ratings carry no DC value at all and a DC arc interrupts differently. Ui covers the breaker's own insulation; the air gap from its terminals to the mounting plate and the door is a separate check in the box, covered in air clearance and insulation inside an enclosure.

Icu and Ics: clear the fault, then keep working

Icu, the rated ultimate short-circuit breaking capacity in kA, is the highest prospective fault current the breaker interrupts at a stated Ue. IEC 60947-2 proves it with one opening and two close-and-open operations on the test breaker. Ics, the rated service breaking capacity, is the level the breaker clears and still carries current and trips within limits afterwards. Makers quote Ics as 25, 50, 75 or 100 % of Icu, and 100 % Ics means a maximum fault leaves a working breaker behind.

Choose Ics by what downtime costs at that feeder. A main incomer or a feeder on a continuous line wants Ics equal to Icu, so a worst-case fault still ends with the breaker ready to reclose. A branch circuit feeding equipment that has already stopped can live with 25 or 50 %. The nameplate also carries Icm, the rated making capacity: the peak fault current the breaker can close onto and carry clear, a number that matters when a switch-in lands on a fault that is already present. A selection guide to breaking capacity, making capacity and earth leakage walks the pairing in full.

The kA that matters: fault current at the breaker

Compare Icu against the prospective short-circuit current at the breaker's terminals in kA, from the fault study for that point in the system. Load current tells you nothing here: a lightly loaded branch behind a large transformer can face the same fault level as the main incomer. Start from the available fault current at the service, subtract the impedance of every transformer and cable run down to the panel, and read the Icu row at your Ue against that figure.

The chain keeps going inside the panel. A finished panel's short-circuit rating ends at its weakest device, so a terminal block or a drive rated below the breaker sets the mark, as how a terminal block sets the panel SCCR shows. Where an upstream breaker limits the let-through to this one, use the maker's published series combination alone. A large breaker upstream on the drawing by itself creates no rating; what sets a series rating on a panelboard explains where that limit comes from.

What the enclosure does to In

In is assigned for air moving freely around the breaker at the reference temperature. Inside a sealed box the air sits above room temperature by whatever rise the walls conduct away, and that warmer air is the air your breaker lives in. Two moves follow from that.

Size the box for heat first: the rise equals the heat load divided by the wall conductance, and the enclosure heat calculator runs that sum from your load, your box and your ambient. Stainless walls conduct about 3.7 W/m²K and painted steel about 5.5 W/m²K. The same watts ride a few kelvins cooler in painted steel, at the cost of corrosion resistance. Derate second: the worked-example figure in the next section runs about 1 % of In per kelvin above the 40 C reference. The correction table for your exact breaker and trip unit is the number to commit to. Losses climb in a warm box as well, because copper resistance rises about 0.39 % per kelvin. Measure where the breaker sits, since the top third of the box runs hottest; where to measure ambient temperature inside an enclosure shows where the probe belongs.

Worked example: a 125 A frame in a 20 x 16 x 8 in stainless box at 40 C ambient

Inputs, with their sources:

  • Breaker: In = 125 A at the 40 C (104 F) reference ambient, thermal-magnetic trip, continuous load 100 A. The 125 A plate value is the nameplate figure this article works from; the 100 A load is the example case, the 80 % point on a 125 A frame.
  • Enclosure: a sealed stainless wall-mount box of 20 x 16 x 8 in (508 x 406 x 203 mm). Custom builds take any dimensions you set; these are the example ones.
  • Wall conductance: k = 3.7 W/m²K for stainless, this site's reference value.
  • Heat load: 60 W total, a worked-example assumption standing in for the breaker's pole losses plus a control power supply; replace it with the sum of the dissipation figures on your device datasheets.
  • Ambient: 40 C (104 F), the design ambient this site uses for drives and most electronics.

The rule in words: temperature rise in kelvin equals heat load in watts divided by wall conductance, and conductance is the wall transfer figure times the surface area.

Arithmetic:

  • Surface: 2 × (20 × 16) + 2 × (20 × 8) + 2 × (16 × 8) = 640 + 320 + 256 = 1216 in², which is 0.785 m².
  • Conductance: 3.7 W/m²K × 0.785 m² = 2.90 W/K.
  • Rise: 60 W ÷ 2.90 W/K = 20.7 K, so the air at the breaker sits near 61 C.
  • Correction on the worked-example curve of 1 % per kelvin above 40 C: 21 K × 1 % = 21 %, so the frame carries 125 × (1 - 0.21) = 99 A.

Result and decision: the load is 100 A against a permissible 99 A, so the check fails by a hair, and a warm afternoon or one extra device tips it over. Three fixes, in the order to try them:

  1. Grow the box one size, to 24 x 20 x 10 in. Surface: 960 + 480 + 400 = 1840 in² = 1.19 m². Conductance: 3.7 × 1.19 = 4.40 W/K. Rise: 60 ÷ 4.40 = 13.7 K, air near 54 C, permissible current 125 × (1 - 0.137) = 108 A. The same breaker passes with margin and nothing else changes.
  2. Keep the box, step the frame up to 160 A. 160 × 0.79 = 126 A against the 100 A load. A larger frame dissipates a few watts more, so re-run the rise with its loss figure before you order.
  3. Cool the sealed box. A vent or filtered fan would drop the assembly below its rating: our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and the lowest-rated opening sets what the assembly keeps. On washdown duty that points to an air conditioner or an air-to-air heat exchanger, either of which holds the air at the breaker near ambient so the 125 A plate value applies as printed. Check the cooling unit's own short-circuit marking too; the air-conditioner SCCR article covers units with no marked rating.

Out of the example comes the rule: at or below 40 C (104 F) at the breaker, the nameplate applies as printed; each kelvin above costs about 1 % of In on the worked-example curve; when the derated value falls below your continuous load, buy box volume or cooling before you buy frame size.

Specify it in this order

  1. Write Ue first: system voltage, AC or DC, frequency and poles. Every ampere and kA figure keys off that row.
  2. Pull the fault level at the breaker's terminals in kA and check it against Icu at your Ue. Take Ics by downtime: main incomer at 100 % Icu, branch feeders at 25 to 50 %.
  3. Size In to the continuous load at the derated air temperature, and set the trip at or below both that value and the conductor's protection limit.
  4. Back-check the chain: with an upstream breaker backing this one, use the maker's published series table, and confirm nothing downstream, terminal blocks included, carries a lower short-circuit rating than the mark you want.
  5. Size the enclosure for the air at the breaker: run the heat check and add box volume or sealed cooling before you add frame size. The enclosure sizing guide carries the layout and wire-bending dimensions that set the box depth around a large frame.
  6. Mark the panel. Two or more power or control circuit components make it an industrial control panel under NEC 409.2, and UL 508A is the standard a shop lists it to; NEC 409.110 puts the enclosure type number on the mark. In US workplaces OSHA 1910.303(a) requires approved equipment, and the UL 50E and UL 508A listing guide sets out what that means for the box itself.

When the box is the part on your order, we build stainless enclosures to your dimensions from one piece, with the breaker cutout on your drawing, delivered in 10 business days from your approval of the drawing. Send the frame width, the clearance the breaker needs around its terminals and every conduit or gland entry. What NEMA rating a panel keeps after you cut it and mount devices tells you what the finished box still holds.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 10 in304 stainless24 x 20 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

What is Icm on an MCCB nameplate?

Icm is the rated short-circuit making capacity: the peak of the worst asymmetrical fault the breaker can close onto and carry. It matters when a breaker closes onto a fault that is already present, for instance at a switch-in after maintenance. IEC 60947-2 ties Icm to Icu through the test circuit power factor, so the two ratings rise together; read them from the same voltage row of the datasheet.

How much of a 125 A breaker can I load continuously?

North-American practice keeps a continuous load at or under 80 % of the breaker rating unless the assembly is listed for 100 % loading, so a 125 A frame serves 100 A of continuous load. The IEC plate value of 125 A is itself a continuous capability at the 40 C reference ambient; the 80 % figure comes from North-American listing practice, and it stacks on top of any hot-box derating.

What derating applies at 50 C or 60 C inside the box?

On the 1 % per kelvin worked-example curve this article uses, a 125 A frame carries about 113 A at 50 C air and 100 A at 60 C. Treat those as placeholders until you read the correction table for your exact breaker and trip unit; electronic trip units hold their calibration better than thermal-magnetic ones, so their curves flatten near the top of the range.

Does Icu have to cover the utility's fault rating?

Cover the prospective fault current at the breaker's terminals, after every transformer and cable run, not the utility headline at the service. For scale: a 1,000 kVA transformer at 5.75 % impedance and 480 V three-phase carries about 1,200 A full-load, so its secondary bolted-fault level starts near 21 kA, and cable impedance pulls it down from there. Pick the Icu row at your Ue from that panel figure.

Can I vent the enclosure instead of derating the breaker?

A vent or filtered fan ruins the ingress rating: on a sealed NEMA 4X / IP66 box the lowest-rated opening sets the assembly's rating, so washdown and outdoor panels keep the seal and cool with an air conditioner or an air-to-air heat exchanger instead. Indoors where only dust matters, a filtered fan on a Type 12 box is often the cheapest 10 kelvins you will buy.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 20 × 16 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides