Start at 3% of the drive's real input power: that is the 97% efficiency assumption behind every first-pass drive sizing, and it turns a 5 kW servo axis into about 155 W of heat. Add the watts of every reactor, supply and transformer mounted inside the box, then divide the total by the enclosure's wall conductance, k x A. A sealed 20 x 16 x 8 in stainless box sheds 21 W per 10 K of temperature rise, so a full-load drive needs a rated enclosure cooler rather than a bigger wall-mount box. The worked example is a 10 A, 400 V axis, and every assumption in it is labelled so you can drop in your own figures.
How much heat does a VFD make?
Plan on 3% of real input power becoming heat, which is the same as assuming the drive runs at 97% efficiency; a drive pushing 5 kW out to its motor then loses about 155 W inside your box.
The percentage's power basis matters. Output power runs at 97% of input power, so 3% of input equals 3.09% of output. When the known quantity is the shaft load, use P_loss = P_out × (1/0.97 − 1): on a 5,000 W shaft that is 5000 × 0.0309 = 155 W. Applying 3% straight to 5,000 W reads 150 W and understates the load by 5 W.
The real figure moves with drive size, switching frequency and duty point, which is why every drive manual carries a power-loss table. Take 3% for the first pass and the layout, then substitute the loss-table watts of the drive you actually select before you size any cooling hardware.
What do you need before you start?
Five inputs fix the answer: real power at the duty point, your room's hottest normal ambient, the lowest ambient limit among the mounted parts (40 C for most drives), the enclosure's outside dimensions, and the documented watts of every current-carrying option inside the box.
- Duty-point power. Measured input kW or motor shaft kW; the nameplate counts only when the machine truly runs there.
- Ambient. Use your worst normal value: 30 C is fair for a plant floor, 35 C beside a rooftop or oven line in summer.
- Temperature limit. 40 C ambient for drives and most electronics unless the datasheet allows more.
- Enclosure. Outside H x W x D. Stainless walls conduct at k = 3.7 W/m²K and painted steel at 5.5 W/m²K, the values used across our sizing guides.
- Option losses. Each line reactor's data sheet lists its watts loss per frame; the braking chopper, the 24 V supply and the control transformer each carry their own.
Every size in the worked example is a catalog wall-mount size, so you can lift dimensions straight from the wall-mount stainless range.
How do you get from kilowatts to watts of heat?
Multiply measured input real power by 0.03, or motor-side power by (1/0.97 − 1) ≈ 0.031; both return watts, and the only decision is which side of the drive you measured.
- Measure real input power, not apparent power: P_in = √3 × V_LL × I_line × PF, with volts and amperes giving watts. Drive input current is distorted, so use a true-RMS three-phase power meter rather than a plain clamp reading.
- Heat from the input side: P_loss = 0.03 × P_in. At a measured 5.15 kW, 0.03 × 5150 = 155 W.
- Heat from the motor side: P_loss = P_out × (1/0.97 − 1). At a 5.0 kW shaft, 5000 × 0.0309 = 155 W.
- Add every inside option's documented watts: the input reactor from its own data sheet, the 24 V supply's stated dissipation, and a dry-type control transformer at about 1-3% of its rating.
- Sum the column. The total in watts is the enclosure's heat load; the same addition for mixed panels is set out in how to calculate enclosure heat load from component losses.
- Replace the 97% estimate with the selected drive's loss-table watts at your duty point before you pick a cooler or commit to a box size.
What else in the box adds heat?
Every current-carrying option inside the gasketed boundary adds its own documented watts on top of the drive's figure; the input line reactor is the usual omission, and in the worked example it contributes 35 W, an example figure to swap for your data sheet's value.
The rule is the heat boundary: count a device when its losses are released inside the seal. A braking resistor bolted to the wall outside dumps its heat into the room and adds nothing to the box; the chopper inside does count. Mount the reactor outside a sealed box and its 35 W leaves the load. A 500 VA dry-type control transformer at 1-3% losses sheds 5-15 W, small but worth its line in the sum.
How much heat can a sealed stainless box shed?
Heat leaves a sealed box through its walls at Q = k × A × ΔT; with stainless at k = 3.7 W/m²K and five exposed faces, a 20 x 16 x 8 in box sheds about 21 W for a 10 K rise.
ΔT is the limit you must protect minus the ambient you have: a drive allowed 40 C on a 30 C floor gives 40 − 30 = 10 K. The five faces are front, top, bottom and the two sides; the back sits against the wall and contributes little. Double the rise and you double the watts the box carries.
| Box outside (H x W x D, in) | Five-face area (m²) | Watts at 10 K rise | Watts at 20 K rise |
|---|---|---|---|
| 10 x 8 x 6 | 0.19 | 7 | 14 |
| 16 x 12 x 8 | 0.41 | 15 | 31 |
| 20 x 16 x 8 | 0.58 | 21 | 43 |
| 24 x 24 x 12 | 1.11 | 41 | 82 |
| 36 x 30 x 12 | 1.72 | 64 | 127 |
Even the largest wall-mount size tops out near 64 W per 10 K. The full method, through cooler selection, sits in the enclosure heat calculation guide, and sizing a non-ventilated stainless enclosure by heat dissipation runs the same numbers across bigger boxes.
How does a 10 A servo axis work out in practice?
A 10 A servo axis delivering 5 kW to its motor makes about 155 W of drive heat; the example reactor adds 35 W, and the 20 x 16 x 8 in sealed box sheds 21 W at the allowed rise, so the passive arrangement falls 169 W short.
- Drive: 5000 × (1/0.97 − 1) = 5000 × 0.0309 = 155 W.
- Reactor (example data-sheet figure for the frame): 35 W. Total inside: 155 + 35 = 190 W.
- Box walls: 20 x 16 x 8 in outside = 0.508 x 0.406 x 0.203 m. Five faces: 0.206 + 0.083 + 0.083 + 0.103 + 0.103 = 0.58 m².
- Wall conductance: 3.7 W/m²K × 0.58 m² = 2.15 W/K.
- Capacity at 40 − 30 = 10 K: 2.15 × 10 = 21 W. Shortfall: 190 − 21 = 169 W.
- Run it as-is and ΔT = 190 / 2.15 = 88 K, roughly 118 C inside on a 30 C day. The drive trips long before the capacitors finish drying out.
The 97% efficiency, the 35 W reactor and the 30 C ambient are labelled example inputs; swap in your drive's loss table, your reactor sheet and your site's summer ambient. The box is the 20 x 16 x 8 in 304 stainless wall-mount enclosure, manufacturer-rated NEMA 4X-type / IP66 and not UL listed. The 316L twin shares the walls and the thermal result, so choose it for chlorides and washdown, not for heat; both grades sit in the stainless size finder.
What keeps the drive below 40 C?
Above roughly 50 W you move the heat out on purpose: a sealed enclosure cooler rated for the total watts, or a ventilated enclosure with a fan-filter set at a lower assembly rating, because passive convection tops out near 64 W even in the largest wall-mount box here.
Coolers publish capacity at a stated temperature difference. Heat-exchanger capacity falls in proportion as that difference narrows, so read the rating at your own ΔT rather than the largest figure printed. Moving the reactor and the braking resistor outside trims the sealed load: 190 − 35 = 155 W still needs the cooler. VFD enclosure size for a drive combines these watts with clearance and layout, and wall-mounted drive enclosure: heat and humidity checks first covers the checks to run before you seal the door.
| Case | Heat inside | Decision |
|---|---|---|
| Logic only: PLC, HMI, small supply | 20 W or less | Sealed 20 x 16 x 8 in box; 21 W at a 10 K rise covers it |
| Drive at light duty, loss-table figure verified low | 40 W or less | Sealed 24 x 24 x 12 in box; 41 W at 10 K, 82 W at 20 K |
| Full-load drive | 150-250 W | Sealed box plus a cooler rated for the total watts at your ambient; pick one rated for the box, because the weakest part sets the assembly rating |
| Ventilation acceptable | any | Fan-filter set sized to the watts; the assembly rating drops to the fan-filter's own rating |
Which mistakes ruin the number?
Three errors dominate: reading apparent power as real power, sizing from the nameplate when the machine runs lighter, and forgetting a reactor mounted inside; the power-factor slip alone turned a 480 V, 10 A reading into 249 W of supposed heat instead of 150 W.
- Apparent against real. √3 × 480 V × 10 A = 8.3 kVA. At a distortion-heavy PF of 0.6 that is 5.0 kW, so the honest heat is 150 W at 3%, and the kVA route overstates it by 99 W. Measure real kW or read the drive's own input metering.
- Nameplate sizing. Below full load the loss falls, but never in proportion, because control and switching losses are fixed. Use the partial-load row of the loss table for an axis that rarely reaches rated torque.
- The forgotten reactor. 35 W in the example, read straight off the sheet that ships with the reactor.
- Boundary slips. Counting a resistor mounted outside, or missing a chopper mounted inside, moves the answer by tens of watts in either direction.
- A vent on a sealed box. Do not fit a fan-filter to a Type 4X box and keep calling it 4X; the assembly rating falls to the fan-filter's rating.
After startup, close the loop: run the machine at its duty load until the internal thermometer stops climbing, compare the reading with the 40 C limit, and measure input watts against your estimate. Measuring drive watts loss to verify efficiency above 90 is the direct test of the 3% assumption; if the measured loss runs higher, put the difference into the cooler's size.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 6 in | 304 stainless | 10 x 8 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much heat does a painted steel version shed compared with stainless?
Painted steel walls run k = 5.5 W/m²K against stainless at 3.7 W/m²K, about half again more. The same 20 x 16 x 8 in box then sheds 32 W per 10 K rise instead of 21 W. Our catalog boxes are stainless in 304 and 316L, and both grades share the 3.7 value, so the grade changes corrosion behaviour, not the thermal math.
Is 3% of the motor rating the same as 3% of the input power?
Close, but the honest pair is 3% of input or 3.1% of output. On a 5,000 W shaft: 5000 x (1/0.97 - 1) = 154.6 W, while 3% applied to that same 5,000 W reads 150 W, about 5 W low. Small at this size, but matching the percentage to its power basis keeps bigger drives honest.
Can a sealed stainless box carry a 155 W drive with no cooler at all?
No. The 20 x 16 x 8 in example box moves 21 W per 10 K rise; 155 W over the same 2.15 W/K of wall lifts the interior 72 K, so on a 30 C floor it settles near 102 C. Fit an enclosure cooler rated for the total watts, or mount the reactor and braking resistor outside the sealed box.
Which ambient goes into the sizing sum?
The hottest the location normally reaches, not the yearly average. A floor that averages 25 C can touch 35 C on summer afternoons; at a 35 C ambient the drive's 40 C limit leaves only a 5 K rise, cutting the example box from 21 W to 11 W of passive capacity. Size at your worst normal ambient.