Short answer: the walls and doors sweat because their surfaces sit below the dew point of the room air. At 24 °C (75 °F) and 75% relative humidity the dew point is 19.3 °C (67 °F). A metal door frame at 18.6 °C is already condensing, and the thermostat reading was never wrong. Lowering the setpoint is the last fix, not the first: it chills surfaces about as fast as it dries the air. Restore the fan coil unit (FCU) airflow and cooling, clear the condensate trap and correct the extract and make-up air path first, then hold every wettable surface at least 2 °C above the room dew point. Toilet condensation on walls and doors always reduces to one of the five causes below.
Where condensation actually starts
Surface condensation is a temperature comparison, not a dirt or leak problem. A wall, a door or a frame wets the moment its surface temperature falls below the dew point of the air touching it, and dries the moment it climbs back above. The room thermometer can read a comfortable 24 °C while the dew point sits at 19.3 °C; every surface below 19.3 °C collects water. The same arithmetic decides whether a chilled cabinet door fogs overnight; the enclosure condensation guide applies it inside sealed boxes.
| Room RH at 24 °C (75 °F) | Dew point | What starts to wet |
|---|---|---|
| 50% | 12.9 °C (55 °F) | chilled pipes and duct boots only |
| 60% | 15.8 °C (60 °F) | supply-air corners, metal frames over cold voids |
| 70% | 18.2 °C (65 °F) | tiled walls in the cool corners |
| 75% | 19.3 °C (67 °F) | walls and door leaves in the worked example below |
| 80% | 20.3 °C (69 °F) | nearly every surface, glass included |
Each 10-point rise in relative humidity lifts the dew point about 2 °C at this room temperature. A washroom that drifts from 60% to 80% RH moves its wetting threshold from 15.8 °C to 20.3 °C, and surfaces that were safe in the dry season start sweating. A cold surface below the dew point always collects water — the same physics that wets a cool device in a humid plant room.
What the wetting pattern tells you
Map the pattern before you measure anything; it usually halves the check list.
- Even wetting across walls and both door leaves points to the room air: the dew point has climbed above ordinary surface temperatures. Look at FCU drying and make-up air first.
- Wetting strongest where the supply grille throws, with dry tile elsewhere, points to a cold jet chilling those surfaces: an airflow or leaving-temperature problem at the FCU.
- Wetting that appears or worsens within an hour of the cooling stopping points to cold-soaked metal: the frames stored the chill and the returning humid air wets them.
- Water below the FCU, ceiling staining or a patch that never dries points to the condensate pan and trap, not to airborne moisture.
- Dry tile with wet metal frames only points to conduction: a chilled-water pipe or duct behind that wall or above that ceiling is cooling the metal.
- Musty smells in the corridor or dampness at the door undercut points to extract and make-up imbalance dragging air through leaks.
The causes, most likely first
- The FCU cools but does not dry. A loaded filter, blocked coil fins or a failed speed tap chokes the airflow. Temperature-only control makes it worse: when the entering air is cool but humid, the controller sees 24 °C and stops the coil before it has wrung the water out. Supply air then leaves at 12-16 °C — the band typical of chilled-water fan-coil selection data — while room humidity drifts up and the margin on every surface shrinks.
- Humid make-up air. Washroom extract is designed around 10 air changes per hour (common washroom extract practice), and ASHRAE 62.1's toilet rate lands near 25 L/s (50 cfm) of exhaust per water closet. Every extracted litre returns through door undercuts, transfer grilles or a ducted make-up route. If that route draws humid outdoor air in the wet season, or a shower-loaded adjacent space, the room dew point sits at 18-20 °C and no setpoint change removes it. The make-up air deserves its own check: checking make-up air dew point against the surfaces it reaches is the full method.
- Uninsulated cold surfaces. A chilled-water pipe or supply duct behind the wet wall, or above the ceiling near the frames, cools the metal by conduction. Tile stays dry while the frame below it sweats — the conduction signature from the list above.
- Condensate drain or pan fault. A blocked or dry trap, or an overflowing pan, raises humidity near the ceiling and leaves drips that read as condensation. The same trap-and-pan logic appears at enclosure scale in the condensate checks before repairing a cabinet air conditioner.
- Extract running backwards or a leaking duct (rare). A humming fan proves nothing about airflow: the wheel can spin with a blocked duct, or the wrong way, pushing air back into the room or dumping it into the ceiling void. Prove direction at the grille with a tissue strip or a vane, and judge nothing from noise.
Measure dew point against the surface
Measure during the hour the room actually wets, with the FCU in its normal state, and record whether the coil was cooling at each reading. A thermo-hygrometer that reports dew point directly, plus a contact surface probe, is the whole toolkit. Skip infrared on wet or glossy finishes: a wet or polished metal film can misread an IR gun by several degrees Celsius, so press a contact probe to the frame.
Worked example: a washroom wetting evenly over both door leaves. At 08:30 with the FCU running, the air beside the wettest door reads 24 °C and 75% RH. Saturation vapour pressure at 24 °C is 2.98 kPa, so the room's vapour pressure is 0.75 × 2.98 = 2.24 kPa. The Magnus relation turns 2.24 kPa into a dew point of 19.3 °C. The contact probe on the frame reads 18.6 °C — 0.7 °C below the dew point — so the frame must be condensing, and the physics is proven. The FCU readings then explain the humidity: entering air 27 °C, leaving air 13 °C, a 14 K split at a grille throw that barely reaches the door. A cold coil with a starving fan chills surfaces while the room dew point climbs to meet them. The same three readings settle whether a cooled space stays dry at any scale; dew point measurement in a cooled electronics chamber applies them inside a sealed box.
| Check | Healthy reading | What a bad reading points to |
|---|---|---|
| Air beside the wet wall | dew point at least 2 °C below the coldest surface | room air too humid: FCU drying or make-up air |
| Coldest surface, contact probe | dew point + 2 °C or more | chilled surface: jet wash, pipe or duct behind |
| FCU entering vs leaving air | 12-14 K split at design airflow (typical selection data) | small split: coil not cooling; large split with short throw: airflow starved |
| Condensate trap and pan | water seal present, pan draining while the coil cools | trap or pan fault |
| Extract grille | air moving outward; make-up dew point below the surfaces | extract or make-up fault |
The fix, in this order
- Restore airflow before anything else. Clean or replace the filter, brush the coil fins, put the fan speed tap back where the schedule puts it, and recheck the throw and the split the next day at the same hour.
- Give the coil time to dry the room. In the worked example, the same corner settles at 24 °C and 60% RH once airflow is back: vapour pressure 0.60 × 2.98 = 1.79 kPa, dew point 15.8 °C. The frame climbs to 19.0 °C, a margin of 3.2 °C, and the wall stays dry.
- Clear the condensate route. Prime the trap, set its depth to the unit's fan pressure as the unit's data sheet shows, and confirm the pan drains while the coil is actually cooling.
- Correct the extract and its make-up. Prove outward flow at the grille, trace where replacement air enters, and draw it from the driest path available. Balance the make-up so the room sits near neutral; a strongly negative room inhales humid air through every leak.
- Insulate what dehumidification cannot fix. A frame washed by a 13 °C jet needs a room dew point below about 13 °C to stay dry — roughly 50% RH at 24 °C. Lag chilled pipes and ducts behind the wet zone with closed-cell insulation and a sealed vapour jacket, and turn the grille to throw the jet off the frames.
- Trial the setpoint last, with a meter logging. Drop the setpoint to 22 °C and watch surface against dew point through the wettest hour; stop the trial if surfaces cool faster than the dew point falls.
The decision rule behind every step: keep the coldest wettable surface at least 2 °C above the room dew point. Any surface that falls to dew point + 2 °C or below is out of margin and still needs one of the fixes above.
Keep it dry through the seasons
- Repeat the dew-point-versus-surface check at the worst hour each season; the wetting hour moves with the weather.
- Wash or replace the FCU filter every 3 months in cooling season, or sooner when the grille throw shortens.
- Prime the condensate trap during months the FCU does not cool, so the seal does not dry out.
- Log room dew point where the wetting was worst; when it comes within 2 °C of the coldest surface, you have caught the condition before the walls do.
Escalate from repair to design when make-up air holds the room dew point at 18 °C or higher. Temperature-only control cannot hold a 2 °C margin there, because coil air leaves at 12-16 °C and wets every surface it touches. The two permanent fixes are control that runs the coil on dew point or humidity demand, and a make-up source dried before it enters. Continuous overcooling is not a moisture-control design.
The electrical boxes on those walls
A condensation film does not stay put: it runs, and the back boxes behind switches and sockets, the sensor spurs and the hand-dryer connections on those walls take the water. Damp terminations track and corrode, and the failure often shows weeks after the wall dries. Specify sealed stainless enclosures for anything live in the wet zone. Our wall-mount boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. That means dust-tight, and resistant to wash-down jets from a 12.5 mm nozzle at 100 L/min. They are built to your cutout layout and delivered in 10 business days. The range starts at outdoor and wet-area stainless enclosures. Where cleaning chemicals or coastal air bring chlorides, choose 316L; rust spots on a stainless enclosure explains the pitting difference.
A sealed box keeps splash and jet water out. It still condenses inside when the room cools overnight, because the air sealed in it reaches its own dew point. Finding water inside a sealed electrical enclosure starts that separate investigation, and sealing a junction box to a brick wall against running water covers the wet-wall entry points. One safety rule: isolate the circuit and verify absence of voltage before opening any box water has reached.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 316L stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 316L stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
At what surface temperature do walls start to sweat?
Read the threshold from the dew-point table above for air at 24 °C: at 60% RH walls wet below 15.8 °C, at 70% below 18.2 °C and at 80% below 20.3 °C. Take the dew-point reading beside the wet wall, not from the room thermostat, and hold every surface at least 2 °C above the measured dew point.
Will lowering the setpoint stop the condensation?
Rarely on its own. Cooling the room from 24 °C to 21 °C at a steady 75% RH lowers the dew point only to 16.4 °C, while surfaces washed by 13 °C supply air drop below that mark before the air finishes drying. Trial a lower setpoint only after airflow, coil and drain faults are fixed, with a dew-point meter logging through the wettest hour.
Can the toilet extract fan cause condensation by pulling moist air in?
Yes. Washroom extract is designed around 10 air changes per hour (about 25 L/s per water closet under ASHRAE 62.1), and it moves humid replacement air as readily as dry air. If the make-up path draws from humid outdoor air or a wet adjacent space, the room dew point can sit at 18-20 °C and no setpoint removes it. Prove flow direction at the grille with a tissue strip, then measure the make-up air's dew point.
What does the moisture do to switches and junction boxes on those walls?
A condensation film runs down the wall and wicks into back boxes, sensor spurs and hand-dryer connections, where damp terminations track and corrode. Fit sealed stainless enclosures with cable glands sized to the cable on any wet wall. Remember that IP66 means dust-tight plus jets from a 12.5 mm nozzle at 100 L/min — it is not an immersion rating. Condensation inside a sealed box is a separate dew-point problem, covered by the enclosure condensation guide.