Space knockouts by the fittings you will bolt on, not by a code table: set the hole centers at least half the outside diameter of each installed locknut or bushing apart, plus 0.25 in [6 mm] of clearance. The table that does exist is UL 50 Table 71-1A, which lists knockout diameters and fitting dimensions. The NEC takes over only on pull and junction boxes with 4 AWG and larger conductors: entries sit at least 8 raceway trade sizes apart on a straight pull and 6 on an angle pull. On a stainless wall-mount box that works out to one session with calipers, a punch and die sized by trade, and two layout lines. The hole diameters, the spacing arithmetic worked through on a 16 x 12 in wall, and the sealing checks follow.
What sets the distance between knockouts
Two rules decide it. On every box, the installed hardware sets the spacing: a locknut on the outside face and an insulating bushing or hub on the inside are each wider than the hole, and both need room to seat and turn. Make the center-to-center distance at least half of each fitting's outside diameter, summed, plus 0.25 in [6 mm] between them. For two identical entries that is one fitting OD plus the clearance. A punch and die set pays off here: the die's overhang runs close to the size of the locknut or bushing, so the die doubles as a spacing gauge on the layout.
The NEC adds entry distances only where conductors are 4 AWG and larger in a pull or junction box. Straight pulls need at least 8 times the trade size of the largest raceway between the entries. Angle pulls need 6 times, measured between the entries that share a conductor and from each entry to the opposite wall. The full sizing arithmetic for that case lives in the enclosure sizing guide. Conductors that land on terminals also need bending space, which NEC 312.6 sets by wire size: for 2 AWG with one wire per terminal, 2.5 in [63 mm], as the backplate and DIN rail layout guide works through.
Cut the holes to the trade diameters UL 50 Table 71-1A tabulates:
| Raceway trade size | Knockout hole diameter |
|---|---|
| 1/2 in | 7/8 in [22 mm] |
| 3/4 in | 1-1/8 in [29 mm] |
| 1 in | 1-3/8 in [35 mm] |
| 1-1/4 in | 1-11/16 in [43 mm] |
| 1-1/2 in | 1-15/16 in [49 mm] |
| 2 in | 2-7/16 in [62 mm] |
| 2-1/2 in | 2-15/16 in [75 mm] |
| 3 in | 3-9/16 in [90 mm] |
Match the fitting to the hole as well as to the trade: cord grips and hubs each cover a span of hole sizes, as the cable gland spacing article shows in practice. Hole quality, gland seats and display openings are covered in depth in the guide to enclosure cutouts, glands and windows.
What you need
- Calipers, to measure the outside diameter of every fitting on both faces of the wall.
- A punch and die set in the trade sizes; the die overhang tracks the locknut or bushing.
- A step bit or hole saw for one-off holes, with cutting oil for stainless.
- A deburring tool or file and a rag for the swarf.
- A center punch, square and marker for the layout lines.
- The fittings themselves: locknut, insulating bushing, or a gasketed hub on wet and washdown entries.
- Gasketed plugs for any hole that stays unused.
Laying out and cutting the holes
- Measure each fitting's outside diameter with calipers, outside face and inside face. A hub or cord grip runs larger than the locknut in its trade, so measure what you actually bought.
- Compute the minimum center-to-center distance: half of each fitting's OD, summed, plus the clearance between fittings. When the box serves large conductors as a pull box, compute the NEC entry distances too and lay out to the larger number.
- Mark the hole centers on layout lines, keeping every fitting at least its own clearance away from the flange, gasket bead, hinges and weld seams.
- Center punch each mark and pilot drill about 1/4 in [6 mm].
- Punch or saw each hole to the trade diameter in the table, cutting oil on stainless throughout.
- Deburr both faces and wipe the swarf off before it marks the finish.
- Install each fitting: insulating bushing inside, locknut outside, and a gasketed hub wherever water can sit on the entry.
- Fit a gasketed plug in every hole you are not using yet.
Worked example: a 1 in and a 3/4 in entry on a 16 x 12 in wall
The case: two conduit entries side by side on one flat side wall of a wall-mount junction box. The wall measures 16 x 12 in [400 x 300 mm], a hypothetical example sized for the arithmetic.
Inputs. Entry A: 1 in trade conduit, knockout hole 1-3/8 in [35 mm], the trade diameter UL 50 Table 71-1A tabulates. Entry B: 3/4 in trade, hole 1-1/8 in [29 mm]. Fittings, assumed for the example: a locknut and insulated bushing of outside diameter 1-3/4 in [44 mm] on entry A and 1-1/2 in [38 mm] on entry B — measure your own, because a hub or cord grip runs larger. Clearance between fittings: 0.25 in [6 mm].
Rule in words. Minimum center-to-center distance = half of entry A's fitting OD + half of entry B's fitting OD + the clearance.
Arithmetic. 1.75 in / 2 + 1.50 in / 2 + 0.25 in = 0.875 in + 0.75 in + 0.25 in = 1.875 in [48 mm].
Result and decision. The entries need 1-7/8 in between centers at minimum; lay them out at 2 in [50 mm] centers so the marks land clean. At 2 in centers the fittings keep a gap of 2 − 0.875 − 0.75 = 0.375 in [10 mm], above the clearance. Any layout under 1-7/8 in crowds the two fittings inside the clearance, so move a hole or step one entry down to a narrower fitting. With centers at 7 in and 9 in from the wall edge, both fittings sit mid-wall with room for two more 3/4 in entries at the same spacing.
Checks before you close the box
- Every fitting covers its hole: cord grips and hubs list a span of hole sizes, and an oversize hole leaves the seal nothing to clamp.
- The insulating bushing seats flush and the locknut will not turn back by hand.
- Fittings sit clear of the gasket bead, flange and hinges, and the door closes without pinching the gasket.
- Wet or washdown entries carry gasketed hubs; unused holes carry gasketed plugs.
- On a large-conductor pull box, the NEC entry distances and the terminal bending space still hold after the layout.
- A concentric knockout pressed into service for a large raceway gets its bonding bushing where the code calls for one.
- Our stock stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. A field-cut hole holds that sealing level when its fittings and plugs match the duty and go in per their instructions. Run the knockout quality checklist before the box ships.
Mistakes that cost the rating
- A hole over the flange radius or gasket bead. The seal path breaks where the cut crosses it. Shift the hole into the flat and let the hardware rule set the distance to the edge.
- An oversize hole. The gland's sealing ring has nothing left to clamp. Redress to the trade diameter, or move up one fitting size.
- A push-in cap sealing an outdoor hole. Swap it for a gasketed plug; a friction cap holds dust, not water.
- A stamped concentric knockout carrying a large raceway bare. Where the code calls for one, fit the bonding bushing.
- Swarf left overnight on 304. It rust-specks the finish; wipe and clean the same shift.
What to put on the order
For a box you cut yourself, order a blank: the stainless junction box range covers the nine smallest wall-mount sizes in 304 and 316L, each with a hinged gasketed door, a removable mounting panel and wall-mount feet. For a box that arrives with the holes in it, lay the openings in the cutout designer: it places holes, glands and operators on any face, checks the spacing you just computed, exports the layout and sends it with the quote request.
Factory cutouts come deburred and exactly where the drawing says, and the box is delivered in 10 business days from your approval of the drawing. Depth matters as much as spacing: leave room behind each fitting for the locknut, the conductor bend and the NEC 312.6 bending space. Indoors and dry, 304 holds; washdown, coastal or chemical duty goes 316L. The custom stainless cutouts page contrasts a standard body with new openings against a fully custom body and carries the drawing checklist to send with the order.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How far apart do two knockouts need to be?
Set the center-to-center distance at half the outside diameter of each installed fitting plus the clearance margin. With equal hardware that is one fitting OD plus the margin: two 3/4 in entries with 1-1/2 in [38 mm] insulating bushings sit at 1.75 in [44 mm] centers, and layouts round that to 2 in [50 mm]. Measure the hardware itself, because hubs and cord grips run larger than a locknut in the same trade size.
Is there a code table for knockout-to-knockout spacing?
UL 50 Table 71-1A lists knockout diameters and fitting dimensions, which set hole size and the space the fitting needs. The NEC sets entry distances only for pull and junction boxes with 4 AWG and larger conductors: at least 8 times the largest raceway trade size between entries on a straight pull, 6 times on an angle pull. Everywhere else, the installed locknut or bushing sets the spacing.
What hole size does a 1 in knockout need?
1-3/8 in [35 mm], the trade-standard knockout diameter for 1 in conduit. Punch it with a 1 in die and deburr both faces, then check the fitting you plan to install lists that hole size in its range, because cord grips and hubs each cover a span of hole diameters.
Does a field-cut hole keep a NEMA 4X rating?
The NEMA 4X / IP66 rating on our stainless boxes is the manufacturer's rating, not UL listed. A field-cut hole holds that sealing level when its gasketed hub or cord grip and its plug match the duty and go in per their instructions. One open or loosely sealed hole is the leak path that ends the rating for the whole box.