Count volumes, not wires. Every conductor entering a junction box carries a cubic-inch cost set by its size. Each device strap then adds a double volume at the largest conductor connected to it. All the grounds together take one volume, and all the internal clamps together take one more. The total has to fit the volume marked on the box, and the National Electrical Code lets the total reach 100 percent of that marking. We build to a tighter line, 75 percent of the marked volume or less, so the splice, the pigtail and next year's circuit keep room to work. The example below, four 12 AWG and four 14 AWG conductors with one receptacle, grounds and clamps, totals 26.0 cu in. That clears a 30.3 cu in steel box at 85.8 percent, past our line, so the 42.0 cu in box is the one to order. You can run the whole count in about two minutes.
What you need
A fill calculation needs nothing you do not already have on the job. The volume marking is the number every other line compares against.
- The box's marked volume: metal boxes carry it stamped in cubic inches, nonmetallic boxes print it on the wall
- A conductor list by size, including any conductors that pass straight through
- The strap count, if a device or a fixture goes on the box
- The allowance table in the next section, on paper or in a fill app
What each conductor costs
The National Electrical Code's box fill table sets a volume allowance for every insulated conductor that enters the box. The values below cover the sizes a junction box usually sees.
| Conductor size | Volume per conductor |
|---|---|
| 18 AWG | 1.50 cu in |
| 16 AWG | 1.75 cu in |
| 14 AWG | 2.00 cu in |
| 12 AWG | 2.25 cu in |
| 10 AWG | 2.50 cu in |
| 8 AWG | 3.00 cu in |
| 6 AWG | 5.00 cu in |
A conductor that splices counts once, and a conductor that passes straight through counts once as well. A pigtail that starts and ends inside the box counts zero, which is why building splices on pigtails keeps a crowded box legal. Watch the bottom of the table if your box mixes sizes: one 6 AWG conductor costs 5.00 cu in [82 cm³], more than two conductors of the second-largest size put together.
Devices, grounds and clamps: the three add-ons
Each yoke or strap that supports one or more devices costs a double allowance, sized by the largest conductor connected to a device on it. A receptacle landed on the heavier circuit adds 2 × 2.25 = 4.50 cu in. A switch fed only by 14 AWG adds 2 × 2.00 = 4.00 cu in. The allowance follows the strap, so a duplex receptacle and a GFCI sitting on one strap cost a single double allowance rather than two.
All the equipment grounding conductors in the box take one allowance between them, at the largest ground wire present. Four bare grounds of the heavier size cost 2.25 cu in between them.
Internal cable clamps together take one allowance at the largest conductor entering, the usual case when NM cable lands in a metal box. Cables arriving on glands or connectors set in the wall of the box carry no clamp allowance, and the article on sizing a junction box without conduit covers that layout with its own method.
The count, step by step
- Isolate the circuit, lock it off, and verify absence of voltage before you open the box.
- List every insulated conductor entering the box by size, including pass-through conductors.
- Multiply each size by its allowance from the table and add the results.
- Add a double allowance for every strap carrying a device or fixture, sized by the largest conductor connected to it.
- Add one allowance for all the grounds together and one for all the internal clamps together.
- Total the cubic inches.
- Pick a box whose marked volume covers the total, and hold the total to 75 percent of the marking or less when you want working room.
- Above a 100 cu in box, size by the raceways entering and the terminal bending space NEC 312.6 sets instead; the enclosure sizing guide walks that path.
Worked example: mixed wire sizes and a receptacle
A steel 4 in square box, 2-1/8 in deep, marked 30.3 cu in [497 cm³], receives two NM cables of the heavier size and two of the lighter, each 2-conductor with bare ground. That is four conductors of each size, four bare grounds and four internal clamps. As a splice box the count runs:
| Item | Allowance | Volume |
|---|---|---|
| 4 × 12 AWG conductors | 2.25 cu in each | 9.00 cu in |
| 4 × 14 AWG conductors | 2.00 cu in each | 8.00 cu in |
| Grounds together, largest of the heavier size | one allowance | 2.25 cu in |
| Clamps together, largest of the heavier size | one allowance | 2.25 cu in |
| Splice-box total | 21.5 cu in |
21.5 cu in is 71.0 percent of the marking, under the 75 percent line, so the box holds the splices with room to spare.
Now mount the receptacle on the yoke, wired to the heavier circuit. The strap costs a double allowance at its largest connected conductor, 2 × 2.25 = 4.50 cu in, and the total moves to 26.0 cu in. Against the 30.3 cu in marking that is 85.8 percent: legal, past the line we build to, and thin on working room around a device body. Step up to the 4-11/16 in square box at the same 2-1/8 in depth, marked 42.0 cu in [688 cm³]. The same 26.0 cu in lands at 61.9 percent there, with room for the device body, its folded tails and the circuit someone adds later.
So the decision reads: the splices alone justified the smaller steel box, and the receptacle pushes the order up one size, to the 42.0 cu in marking.
Checks before the cover goes on
- Read the marking rather than the outline: the 1-1/2 in deep version of the same 4 in square is marked 21.0 cu in, a third less than its 2-1/8 in sibling.
- Keep every line in cubic inches; a square-inch figure in your spreadsheet column means a unit slipped somewhere.
- Re-run the count whenever a circuit lands later. An added cable of either size costs two conductor allowances more, because the ground and clamp allowances are already spent.
- Check depth as well as volume. With a device on the yoke, the body and its folded conductor tails sit behind the strap; a shallow box pinches them even when the arithmetic passes.
- Keep fill and ampacity separate. Fill sizes the box; conductors of mixed sizes sharing one raceway derate together, which wire derating guide for mixed conductor sizes covers.
Mistakes that blow the count
- Charging every ground wire its own allowance: the bundle takes one, at the largest ground in the box.
- Counting devices instead of straps: two devices on one strap cost one double allowance.
- Skipping the clamp allowance when NM cable lands in a metal box.
- Reading outside dimensions as volume: a 4 in square at 1-1/2 in depth is marked 21.0 cu in, not the 24 cu in of raw geometry.
- Borrowing raceway numbers: the 40 percent conduit cap, 53 percent for a single multiconductor cable, lives in the raceway tables, and the multiconductor conduit fill article keeps the two rules apart.
- Borrowing panel numbers: wire duct inside a panel fills to 50 percent of its interior cross-section, the limit the backplate and DIN rail layout guide works to.
- Carrying several motor circuits into one box: the volume method stands, and the NEC adds disconnecting and grounding demands on top, listed in the multiple motor circuits article.
- Stretching the volume table past its ceiling: above 100 cu in the NEC sizes pull and junction boxes from the raceways entering them instead.
Which box to order
Run the count first, then order the box that keeps the total at or under 75 percent of its marked volume. For the worked example that is the 42.0 cu in box, even though the splices alone fit the smaller marking. When the job wants stainless for a washdown wall or a made-to-measure depth, read the inside dimensions off the enclosure size chart. Or send your conductor list with a stainless junction box order and let the depth follow the numbers. Every box is made to order and delivered in 10 business days, counted from your order or, for custom work, from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much does a pigtail add to junction box fill?
Zero. A conductor that starts and ends inside the box adds 0 cu in at any size, so splices built on pigtails are free of charge. The count takes volume only from conductors that enter or leave the box: each insulated one at its own allowance, all grounds as one bundle at the largest, all internal clamps as one bundle. That is why a splice itself never moves the total: only incoming conductors, the ground bundle and the clamps do.
How much volume does a GFCI receptacle add?
The same as any receptacle: a double allowance at the largest conductor connected to its strap. On the heavier of the two common sizes that is 2 × 2.25 = 4.50 cu in, identical to a duplex receptacle, and two devices on one strap still count once because the allowance follows the yoke rather than the device. In a two-gang box, a GFCI on one strap costs 4.50 cu in while a switch fed only by 14 AWG on the other adds 2 × 2.00 = 4.00 cu in.
How many 12 AWG conductors fit a 4 in square metal box 2-1/8 in deep?
Eleven. One allowance covers the ground bundle and one covers the internal cable clamps, leaving 25.8 cu in of the marking for insulated conductors, and eleven come to 24.75 cu in. A twelfth pushes the count to 31.50 cu in, over the 30.3 cu in marking. In a PVC box with the same marked volume, where no clamp allowance is owed, twelve fit.
Does the volume count apply to boxes larger than 100 cu in?
It stops there. The volume table and the 100 cu in ceiling go together: at 100 cu in and smaller you count allowances, and above it the code sizes pull and junction boxes from the raceways entering, with bending space at the terminals. A steel pull box of 10 x 10 x 4 in, 400 cu in of raw geometry, needs no percentage; it needs room for the conductors to bend and for you to work. Once a job outgrows the small marked boxes, a made-to-measure stainless box sized from the conductor list is the cleaner path.