Short answer: a line-voltage splice lives inside a listed box that stays accessible, with at least 6 in [150 mm] of free conductor on each side of the joint. If a repair left a splice bare in the wall, you have two legal fixes: open the wall, re-house the joint in a box sized by its fill, and leave a cover plate; or convert the joint with a splice kit listed for concealed NM cable and follow its instructions. Both start the same way: switch the circuit off and prove it dead before you touch copper.
What the code asks of a splice
The National Electrical Code (NEC) gives every splice the same home: a listed box, mounted so it stays accessible. Accessible means you can reach the box without removing or breaking any part of the building. A cover plate on the finished wall qualifies; drywall screwed over the box does not. You leave at least 6 in [150 mm] of free conductor at each splice, measured from the box opening, so the joint sits inside with room to work.
The box earns its keep in three ways. It contains the arc and heat when a joint fails. Its clamps carry the cable tension, so any pull lands on the fitting and never on the connector. And a grounded metal box gives fault current a low-resistance path that trips the breaker while the fault is still small; a joint pulled apart against a wood stud has neither containment nor a trip path. Splices are one of the five places a junction box earns its keep.
The two legal fixes for a splice in the wall
Fix one is the box. Cut the wall open at the joint, mount an old-work box, splice inside it, and fit a plate. The repair stays visible and inspectable for the life of the wall, and the next person finds the joint exactly where the NEC says it lives.
Fix two is the in-wall splice kit. A kit listed for concealed splicing takes the box's place. Its molded, insulated body is tested to contain a failed joint while buried. Use it on the cable type and size its listing names, and the wall stays legal. The listings are specific, so match the kit to the cable you are joining; a kit sold for 14 AWG NM carries nothing for 12 AWG.
Both fixes open the wall at the joint; the kit skips the box and the plate. Take the box whenever you can put a plate on the wall, because it stays serviceable. Take the kit when the splice must stay buried and the instructions cover your cable. A splice on a feeder follows the same rules with heavier copper, and the feeder splice article walks that case.
What you need for the repair
- A voltage tester, proven on a live circuit before you trust it on the dead one
- An old-work single-gang box with swing ears; the deep 3 × 2 × 3½ in body stamps 18.0 cu in [295 cm³] and clears the fill check in the worked example below
- A drywall saw and a screwdriver
- Twist-on connectors matched to the conductor count and gauge printed on their packaging
- A ground pigtail and a ground screw when the box is metal
- A cover plate with its screws
A damp, outdoor or washdown location changes the box, not the method: you fit a wet-location enclosure instead. Our stainless wall-mount junction boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and they take the same conductors and connectors behind a gasketed door. The NEMA 3R vs 4X guide sorts which outdoor duty each type covers, and the enclosure selector narrows a box by environment when the wall is anything but a dry interior.
Fixing the splice, step by step
- Switch the breaker off and prove the conductors dead with the tester.
- Locate the splice and cut an opening that lets the old-work box's wings bear on solid drywall.
- Pull both cable ends into the opening and measure: at least 6 in [150 mm] of free conductor from where the box opening will sit. Less than that, and you extend the run with fresh cable or splice inside the nearest existing accessible box.
- Feed the cables through the box's internal clamps and tighten them until the jackets cannot slide by hand.
- Strip each conductor to the connector's strip gauge and join black to black and white to white, seating every conductor fully in the body.
- Join the grounds, add a pigtail, and land the pigtail on the ground screw of a metal box; that bond keeps the fault path unbroken through the box, the way the grounding and bonding guide details it.
- Fold the joints behind the box face, seat the box, and tighten the wings.
- Fit the cover plate and restore the power.
Sizing the box for a repaired 12/2 splice
The case: a surge scorched a length of 12/2 NM on a 20 A receptacle circuit — the standard residential pairing, because the NEC caps 12 AWG copper at 20 A — and the damaged section is cut out, leaving two cable ends. The fill counts come from the NEC's box-fill table: each 12 AWG conductor counts 2.25 cu in [36.9 cm³], all bare grounds count together as one conductor, and the internal clamps count together as one conductor, counted only when they sit inside the box. The candidate box is the deep single-gang, stamped 18.0 cu in [295 cm³].
The rule in words: one count for every conductor that enters the box, one for the grounds as a group, one for the internal clamps as a group, times 2.25 cu in, held under the stamp.
- Four insulated conductors: 4 × 2.25 = 9.00 cu in
- Grounds as one group: 2.25 cu in
- Internal clamps as one group: 2.25 cu in
- Total: 9.00 + 2.25 + 2.25 = 13.50 cu in [221 cm³]
Result: 13.50 cu in against an 18.0 stamp — 4.50 cu in [74 cm³] spare. The splice-only repair passes with room to spare.
The decision flips when the box also holds a device. A receptacle yoke counts as two 12 AWG conductors, another 4.50 cu in. The total lands at exactly 18.0 cu in: legal, with zero margin, and one extra pigtail tips it over the stamp. That is the practical threshold — a fill within one conductor of the stamp calls for the 4 in square deep box, stamped 30.3 cu in [497 cm³]. The same arithmetic moves with the cable: a 14/2 repair on a 15 A circuit counts each conductor at 2.00 cu in [32.7 cm³], fills 12.00 cu in total, and squeezes into a shallow 3 × 2 × 2½ in box stamped 12.5 cu in [205 cm³], while a 12/3 repair lands at exactly 18.0 and takes the bigger box.
Checks when the repair is done
Pull each conductor firmly: the clamp holds the cable, the connector holds the joint, nothing slides. Recount the fill against the stamp — the 12/2 repair above sits at 13.50 cu in [221 cm³] against 18.0. Fold the joints in and fit the plate without pinching insulation, with no copper showing outside a connector. Restore power and run a normal load for an hour: a sound splice leaves the plate at room temperature, and a warm plate points back to the joint. A splice that has already cooked shows its history — discoloration, a burnt smell, a melted jacket — and the burned-splice causes and fixes article lists what each sign means and what to replace.
Mistakes that keep the splice illegal
- Burying the box again. Drywall over the plate kills accessibility, and the repair is back where it started; the plate stays on the finished surface.
- A kit beyond its listing. Concealed-splice kits list the cable types and gauges they cover; the instructions decide, and they travel with the kit.
- Reusing surge-heated copper. Trim back to bright copper; a discolored conductor stays a hot spot and re-bakes the joint.
- A strand outside the connector. One bare strand past a twist-on body can reach its neighbour; strip to the gauge and seat the conductor fully.
- Low-voltage cable sharing the box. Line and low voltage share a box only when every insulation carries the highest voltage present; NM cable is rated 600 V and most Class 2 cable is not, so the thermostat or irrigation pair takes its own box. The mixed-voltage inspection checklist gives the points to look at.
- A box behind a fixed cabinet back. A box behind a door that opens stays accessible; a box screwed behind fixed cabinetry does not.
The fix, by case
| Case | The fix |
|---|---|
| Splice only, dry interior wall | Old-work single-gang box, 3 × 2 × 3½ in, 18.0 cu in [295 cm³] stamp, plate left on the wall |
| Splice plus a receptacle in the same box | 4 in square deep box, 30.3 cu in [497 cm³]; the single-gang sits exactly at its stamp with the yoke added |
| Under 6 in [150 mm] of free conductor at the joint | Pull fresh cable between boxes or splice inside the nearest existing accessible box |
| Damp, outdoor or washdown wall | Wet-location stainless box, manufacturer-rated NEMA 4X / IP66; not UL listed |
| Splice that must stay buried | Splice kit listed for that exact NM type and gauge, used per its instructions |
Every row ends the same way: the joint sits inside something tested for the job, the wall opens far enough to work, and the plate or the kit stays findable for the next person who owns the wall.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a spliced wire stay inside a wall without a box?
Only inside a splice kit listed for concealed use with the cable type and gauge it names; the kit's molded body takes over the box's job of containing a failed joint. Every other in-wall joint sits in a box stamped with a cubic-inch capacity, reachable under a cover plate, with 6 in [150 mm] of free conductor on each side and the fill below the stamp.
How much free wire does a splice need?
The NEC sets 6 in [150 mm] of free conductor at each splice point, measured from the box opening. If the repair cut left less, the legal routes are pulling fresh cable between the nearest boxes or making the splice inside the nearest existing accessible box. A joint stretched tight to reach a new box fails the length rule.
Can line voltage and low voltage share one junction box?
Yes, when every conductor's insulation is rated for the highest voltage present in the box. NM cable is rated 600 V, so line voltage can share a box with control wiring whose insulation also carries 600 V; most Class 2 cable, such as thermostat, doorbell or irrigation pairs, is rated lower and takes its own box. Check each cable's voltage marking before you share a box.
Does the junction box have to stay reachable after the repair?
Yes. The NEC requires the box to stay reachable without removing or breaking any part of the building, so the cover plate stays on the finished wall. A box behind a cabinet door stays legal because the door opens; a box behind a fixed cabinet back or fresh drywall is a violation waiting for its inspection.





