Bond the meter skid to the main grounding grid and treat the new rods as auxiliary electrodes — that is the decision, and the NEC backs both halves of it. NEC 250.4(A)(5) keeps the soil out of the fault-return path; NEC 250.54 lets an added electrode supplement the equipment grounding conductor but never replace it. Size the bond from the overcurrent device ahead of the skid circuits: 10 AWG copper for a 60 A circuit, more on a long run. The flange isolation kits serve the pipeline's corrosion scheme, not electrical safety, and the shielded CAT-6 to the meter already ties the two grounds together. Below: what a fault does through soil alone, what touch voltage looks like when the grid rises, and the tests that close the job out.
Why must a separately rodded skid be bonded to the main grid?
Bond the skid because the NEC rules the soil out as a fault path: NEC 250.4(A)(5) demands a metallic, low-impedance route back to the source, and earth alone never provides one at any practical rod count.
Electrodes added beside a structure carry a name in the code: auxiliary electrodes. NEC 250.54 lets you connect them to the equipment grounding conductor and count their ohms toward the electrode system, but the conductor itself remains the fault path. The rods earn their keep on lightning and earth resistance; they clear no breaker.
The isolation kits change none of this. They sit in the pipe so cathodic-protection current stays on the line instead of leaking to earth through the steel; they were never an isolation for people. Bond the frame to the grid and leave the joints insulated — the two arrangements coexist. The fundamentals of bonding a box into that path live in the grounding and bonding guide; this page stays on the skid itself.
What happens to a ground fault that returns through soil only?
Assume a 240 V fault to the skid frame and two rods at the NEC's 25 ohm benchmark for a single made electrode: the current returns through 50 ohms of soil, so only 4.8 A flows and the frame rises to 120 V above remote earth.
Set the rest of the example with inputs a metering skid might see, and swap in your own where they differ: a 60 A thermal-magnetic breaker protecting the skid circuits. The arithmetic runs 25 ohms + 25 ohms = 50 ohms of return, 240 V / 50 ohms = 4.8 A, and a frame at 4.8 A x 25 ohms = 120 V. A breaker that size trips magnetically at roughly five to ten times rating, 300 to 600 A, so 4.8 A holds indefinitely.
Soil quality barely moves the touch voltage: two equal rods park the frame at half the supply, whatever they measure. Unbalance them and it worsens — a 1 ohm grid rod against a 25 ohm skid rod leaves 240 V x 25/26 = 231 V on the frame, at 240 V / 26 ohms = 9.2 A, still far below any magnetic trip.
The copper bond changes the physics. A 100 ft run of 6 AWG copper measures about 39.5 milliohms (0.395 ohms per 1,000 ft of copper at 20 C), and with source and terminations the loop lands near 0.2 ohms, so the same fault drives 240 V / 0.2 ohms = 1,200 A. The breaker clears in one to two cycles — one cycle is 16.7 ms at 60 Hz — and the frame rises just 1,200 A x 39.5 milliohms = 47 V, for those milliseconds only.
What does the touch voltage look like when the grid itself rises?
During a large fault elsewhere in the plant the grid potential rises, and a bonded skid rides up with it, so touch voltage between skid and plant steel stays small; an isolated skid stays near remote earth, and a person bridging the two takes the whole rise.
Put an example number on the rise, flagged as such: 1,500 V is the kind of figure a substation study produces for a big fault, a value to replace with the site study's own. Across 1,000 ohms of body, the low end of the wet-skin range, that is 1,500 V / 1,000 ohms = 1.5 A through a person touching the isolated skid with one hand and bonded steel with the other. That current is 50 times the 30 mA level IEC treats as RCD personal protection.
Step voltage is the same rise across a 1 m pace, and the soil gradient is steepest around the electrodes. A bonded skid shares the single rise, so the difference a person can bridge collapses to the drop across the bond itself. How a study reaches its rise figure is its own method: grounding grid potential rise calculation is worth a read before you argue with one.
Does the shielded CAT-6 already bond the skid to the grid?
Yes, whenever both ends land the shield on bonded chassis: Ethernet isolates its data pairs with signal transformers, but the connector shells, drain wire and patch panel still make one conductor of the skid and the main system.
That is why the "independent" ground leaks: equalizing current flows through the shield whenever the potentials differ, and a ground loop is simply a closed conductive path where that current turns into signal noise. A foil-and-braid shield is sized for signal current; fault current burns it open, usually after the ports at both ends have failed.
Read the shield as more evidence to bond deliberately. Give fault current the copper path sized for it and leave the shield to carry signal. How cabinets handle shield termination, one end or two, is its own question: see VFD control cable shield grounding, and what a drifting RTD reading says about a bad shield bond.
When is a skid allowed to stay isolated?
Stay isolated only where the isolation kits serve cathodic protection: the insulation belongs to the pipeline's corrosion scheme, while NEC 250.96(A) still requires the skid's metal parts to be bonded so they can safely carry the fault current likely to hit them.
In practice the two coexist. Bond the structural steel to the grid, leave each flange pair insulated downstream of its kit, and megger every finished joint — expect megohms, because an ohm-level reading means a tool, a support strut or a stray lead is bridging the kit. Never route the bond through the pipe beyond an insulated flange: that jumper hands the corrosion scheme its leak back.
Where a signal must cross the boundary without bonding it, run fiber across that span. Glass adds no metallic path, and all-dielectric cable keeps it that way; Ethernet's transformer isolation would have left the shield bonded anyway.
What size conductor bonds the skid to the grid?
Size it like any equipment grounding conductor, from the overcurrent device ahead of the skid circuits: a 60 A breaker takes a 10 AWG copper bond under NEC Table 250.122, and 6 AWG buys margin on a long run.
Insulated conductors of 6 AWG and smaller run green or green with yellow stripes (NEC 250.119). Bolt the lug to skid steel at a bare spot: NEC 250.12 wants paint, lacquer and enamel off the threads and contact surfaces at grounding connections, so brush the coating away before the lug lands. Keep the run short and direct, and land it where a test clamp can reach it later. The wall entry and its connector get their own treatment in grounding conductor entry: connector and bond, and the boundary between that conductor and the plant grid is covered in the equipment grounding conductor versus the plant grid.
How do you check the bond before the skid goes live?
Three readings settle it before energizing: a fraction of an ohm from skid steel to the nearest grid riser, megohms across each insulated flange, and near-zero volts between skid and bonded steel with the instruments running.
Bonding work and continuity readings happen de-energized: lock out and verify absence of voltage before the first lug moves. Then work the list.
- Continuity. Four-terminal low-resistance ohmmeter from skid frame to the nearest grid riser: a fraction of an ohm overall, milliohms across a single lug pair.
- Flange isolation. Megohmmeter across each finished kit: megohms every time, re-tested after any pipe work on the skid.
- Equalizing path. With the metering instruments live, skid-to-plant-steel voltage should read millivolts. Volts mean the copper bond is missing and the CAT-6 shield is doing that job.
- Test access. A disconnect link in the bond run lets the next crew measure the grid without dismantling the joint; the handhole version is its own article on adding a grounding grid test disconnect link.
Which enclosure belongs on a bonded metering skid?
Order the skid's boxes to match the site: 304 stainless for inland weather and washdown, 316L for salt air, brine and chemical plant air, each manufacturer-rated NEMA 4X / IP66 and not UL listed.
Every box rides the skid's potential, so the bond protects its door and terminals as much as the pipe. Land the bond lug inside the box on a ground bar or bonding boss, and bring the conductor in through a gland that keeps the box's rating. Stainless wall-mount junction boxes come gasketed and hinged with a removable panel for exactly this kind of wiring.
For a box outside the catalog sizes, the custom enclosure builder takes your material, width, height, depth and every cutout from one piece, delivered in 10 business days and counted from drawing approval.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can the skid's own ground rods ever replace the bond to the grid?
No. NEC 250.54 treats electrodes added beside a structure as auxiliary: they may connect to the equipment grounding conductor, and the conductor remains the fault path. Two 25 ohm rods return a 240 V fault at 4.8 A, which a 60 A breaker holds indefinitely while the frame sits at 120 V. The copper bond returns the same fault at about 1,200 A and clears in roughly two cycles, 33 ms at 60 Hz.
Does a fiber data link remove the need for the copper bond?
No — fiber removes one metallic path across the boundary, nothing more. Power conductors, conduit and the structural steel still tie the skid's fault path to the source, so the bond stays. Fiber earns its place when flange isolation serves cathodic protection: an all-dielectric cable crosses the boundary without reintroducing the metallic path the kits exist to stop.
What touch voltage does a bonded skid see during a fault?
Millivolts between skid and grid steel, because the bond makes them one conductor. In the worked example, 1,200 A through 39.5 milliohms of 6 AWG lifts the frame about 47 V, and only for the one to two cycles the breaker needs to clear. An isolated skid instead holds 120 V for as long as the fault lasts.
What does the 25 ohm rod benchmark actually buy?
A serviceability ceiling for a single made electrode, not a safety rating for the fault path. A skid can measure 25 ohms to earth and still hold 120 V on its frame during an earth-return fault, because rod resistance and bond impedance answer different questions. Well-spaced added rods pull the earth reading toward half each time the count doubles.





