Short answer: yes, that is capillary action. Hydraulic oil that reaches a bare conductor end or a breached jacket at the pump climbs into the gaps between strands. It then travels the full run to your panel with no heat and no current flow involved. Fix it in three moves: seal the pump-end entry, install a junction box with a terminal strip within about 3 ft [1 m] of the hydraulic power unit, and replace the oil-soaked cable with insulation rated for the fluid. If only the outgoing wires for your two pumps are slimy, the fluid is arriving through those conductors, not from the cabinet air.
The same mechanism moves water, and the fix is the same shape; the water wicking through cable guide covers the sealing details. Ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed, which is what you want for a pump-end box in an oily, hosed-down area.
What the symptom points to
Fluid on one pair of circuits and nowhere else is a path problem, not an environment problem. Work through this list before touching anything:
- Slime only at the contactor lugs, on the pump circuits: fluid arriving through the conductors. Trace it back toward the pump.
- Slime along the whole conduit run or on the jacket only: an external leak, a fitting spraying the cable, or oil pooled inside the conduit. The wires are victims, not the path.
- Fluid emerging from under the insulation at a stripped end: confirmed internal wicking. Replace that conductor; cleaning the outside fixes nothing.
- Softened, swollen or cracked insulation on those same wires: the oil has had contact long enough to attack the jacket, so the run is old contamination, not a fresh spill.
Isolate the circuits and prove the absence of voltage before you open anything. Oil-soaked terminals can hide tracking damage that only shows up de-energized under a lamp.
Why 20 ft is easy for oil
Capillary action is liquid flow through a narrow channel driven by surface tension, with no external force. Between the strands of a stranded conductor, and between conductor and insulation, the channels are a fraction of a millimetre across. Hydraulic oil wets copper and most jacket polymers readily. Once the channel is filled, the oil moves along the whole path, because horizontal travel costs nothing against gravity.
Rough numbers for a stranded 12 AWG conductor (illustrative inputs, class B strand geometry):
- Gap between 7 strands, treated as an open capillary: r ≈ 0.1 mm
- Capillary pressure, P = 2γ/r, with hydraulic-oil surface tension γ ≈ 0.03 N/m: P = 2 × 0.03 / 0.0001 = 600 Pa
- Equivalent vertical lift, P/(ρg), with ρ ≈ 870 kg/m³: 600 / (870 × 9.81) ≈ 0.07 m, about 3 in
Three inches of lift sounds small, but your 20 ft [6 m] run is horizontal. A filled capillary feeds oil along its full length at essentially no pressure cost. A few pump seconds per hour is irrelevant: the oil migrates while the pump sits idle. That is why heat or run time explains nothing here.
Fix the entry first
The barrier box is your second move. The first is stopping oil from reaching the conductor ends at all:
- Isolate the pump circuit and verify absence of voltage before opening the motor junction box.
- Open the motor terminal box and the cable gland. Look for oil at the gland, at the terminal block, and at any hydraulic fitting within splash distance.
- Reseal the entry with a gland matched to the cable jacket OD, or fit an oil-rated sealing compound at the motor box if the cable is unstrung there.
- If the motor box itself floods from a nearby fitting, reroute or shield the cable and repair the fitting. A gland cannot hold back standing oil forever.
The barrier junction box
Put a stainless junction box with a terminal strip within about 3 ft [1 m] of the hydraulic power unit. The terminal strip physically ends the conductor: pump-side wires land on one side, fresh panel-side wires on the other. Oil can soak the short pump-side piece, but it has nowhere to go past the terminals. The copper path is broken, and each terminal is a discrete, inspectable point.
Why the box works and a plain splice does not:
- A wire nut or crimp splice leaves the strand gaps continuous end to end; oil walks straight through.
- A terminal strip forces the fluid to cross an open, visible air gap at each pole.
- The short pump-side pigtails are cheap to replace at the next service interval.
Use 304 stainless for a dry machine area and 316L where the box sees cleaners or brine; molybdenum in 316L buys pitting and crevice resistance against chlorides. Size the box for the terminal count plus 25 % spare. Mount it at a height you can inspect with the machine running: NEC 240.24(A) caps operating handles at 2.0 m [6 ft 7 in] above the floor, and the same height is a good target for an inspection box.
Replace, do not clean, contaminated cable
Cleaning oil-soaked stranded conductors is not a repair. The interstices hold fluid that keeps bleeding out for months. Replace the full soaked length with cable documented as compatible with your hydraulic fluid. PVC softens under many mineral-oil hydraulic fluids; cross-linked polyethylene and oil-resistant elastomer jackets (look for an oil-resistance class such as the IRM 902 oil test in the cable datasheet) are the usual choices. Confirm against the actual fluid name, not just "hydraulic oil", since water-glycol and synthetic fluids behave differently.
Strip and terminate the new panel-side conductors so no soaked section crosses the terminal strip. Inspect both sides of the new junction after the first week. A terminal strip stops the copper path, but oil running down the inside of a flooded box can bridge it, which is why the entry seal comes first. The sticky wire insulation article tells you how to tell old residue from fresh fluid.
Prove the fix
Run the pumps through several normal cycles, then check the same points at the next scheduled operating interval, since these pumps run only seconds per hour:
- Motor box interior and gland: dry.
- Barrier box, both terminal rows: dry on the panel side.
- Contactor lugs in the cabinet: clean, and still clean after a few days.
Fresh oil past the terminal strip means the entry seal failed or the box flooded internally. Dry everywhere means the migration path is broken. Insulation damage on other circuits near the old slime (tracking, brittling) means you should also check those terminations, since oil attracts dust and can become conductive over time.
For the cabinet end, keep the panel door gasket and any cable glands intact so oil on the outside of the cabinet never gets a route in; the glands and cutouts guide covers gland sizing by jacket OD. If the machine area gets hosed down as well as oiled, spec the barrier box from the washdown enclosure range, rated NEMA 4X / IP66 by the manufacturer; not UL listed.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can hydraulic oil really travel 20 ft along a wire?
Yes. The gaps between strands of a typical 12 AWG class B conductor run about 0.1-0.3 mm across, and capillary pressure in such a channel is on the order of 1-2 kPa. That lifts oil roughly 10-20 cm and pushes it horizontally for many feet, since level travel needs no lift against gravity. A 20 ft run is well within reach.
Does a short pump run time rule out wicking?
No. Capillary flow needs no heat and no current; it is driven by surface tension in the strand gaps. A pump that runs a few seconds per hour can still feed oil into the cable ends continuously, and the oil migrates while everything is off.
How close to the pump should the barrier junction box be?
Within about 3 ft (1 m) of the hydraulic power unit. The pump-side conductors then stay short, so the oil-soaked section you eventually replace is small. The long run back to the panel is protected by the terminal break.
Which insulation holds up to hydraulic oil?
PVC is a poor choice: many mineral-oil-based hydraulic fluids swell and soften it within weeks to months of constant contact. Cross-linked polyethylene and most elastomer jackets rated oil-resistant (a common oil-resistance class is the IRM 902 oil test) are the usual picks. Match the cable to your actual fluid using the cable maker's compatibility data.





