Short answer: make the joint with a direct-burial inline splice kit, a bare mechanical or compression connector marked 1 AWG-250 kcmil inside heavy-wall adhesive-lined heat shrink. Shrink the sleeve until adhesive weeps at both ends: that weep is the seal. The sleeve is the enclosure, so the kit needs no box and stands rain, burial and 600 V on its own. Choose a Type 4X junction box with potting glands only when the joint has to reopen later. One safety note first: service-size lugs stay live even with the main breaker off. Lock out at the service disconnect and verify absence of voltage before you cut anything.
Inline kit or junction box: the decision
Both methods pass rain; they differ in what happens to the joint afterwards. The kit is the default because it adds no seals of its own to fail: no gasket, no glands, no door. Every fitting you put on a box is one more place water can work in. The box earns its place when you want the joint visible and reopenable, for testing, a future meter change or an addition on the same run.
| Case | Splice | Seal |
|---|---|---|
| Rain-exposed run, joint stays closed | Mechanical or compression splice, 1 AWG-250 kcmil | Heavy-wall adhesive heat shrink, shrunk to a weep at both ends |
| Buried or standing water | Same kit, marked for direct burial | Same sleeve; the kit is its own enclosure |
| Joint must reopen | Split-bolt or mechanical connectors | Type 4X box, potting glands, taped insulation on each connector |
| Salt air, brine or washdown chemicals | Either route | 316L stainless on the box route; the kit sleeve ignores salt |
| Aluminum strands | Dual-rated connector, antioxidant compound | Same sleeve or box |
On the listing: use a kit marked for wet locations and direct burial by a nationally recognized testing laboratory. OSHA 1910.399 defines acceptable electrical equipment as listed, labeled or otherwise determined to be safe by an NRTL, and that mark is what an inspector looks for on a splice with no box around it. The connector inside a kit is listed to the wire-connector standard, UL 486A-486B. When the shrink sleeve forms part of the insulation, the assembled kit is evaluated as a sealed insulated connector system to UL 486D.
For the fundamentals of what rain means for a box outdoors, the outdoor enclosure guide covers exposure and mounting; here we stay on the splice itself. The NEMA 3R vs NEMA 4 comparison sets out how much water each type shrugs off.
What you need
- Inline splice kit marked for wet locations and direct burial, connector range 1 AWG-250 kcmil, 600 V — all three marks on the label.
- Heavy-wall adhesive-lined heat shrink with a 3:1 ratio: its supplied ID is about three times the recovered ID, so it slides over the connector and grips when shrunk. Pick the recovered ID roughly 20% below the finished splice OD; the same interference rule that governs sizing shrink tubing over a wire bundle applies here.
- A heat gun that takes heavy-wall tubing to shrink temperature; a lighter scorches the wall before it shrinks it.
- Hex crimper or torque wrench matched to the connector, with the die or hex the kit names.
- A milliohm meter and a 500 V DC insulation tester.
- Cold-shrink sleeves (a pre-stretched sleeve on a spiral core) where an open flame is a bad idea; match the recovered diameter the same way.
- For the box route instead: a Type 4X junction box, two glands sized to the cable OD, self-fusing rubber tape and bonding hardware.
The heat budget for a 100 A splice on 3 m of conductor
The sleeve keeps water out; the arithmetic below keeps the joint from cooking itself. Inputs for a typical service-size extension:
- Load: 100 A. The NEC ampacity table rates 1 AWG copper at 130 A at 75 C [167 F], so 100 A is a working load with margin.
- Conductor: stranded copper of this size, about 0.15 Ω per 1000 ft at 75 C from standard conductor tables.
- Extension: a 3 m [10 ft] new tail, the usual add-on when an old run comes up short.
- Sound joint: the connector standards evaluate a listed splice by requiring resistance below an equal length of conductor, so a good joint adds almost nothing. Failure case under test: a loose or corroded joint sitting at 5 mΩ, this example's assumption for a joint left untightened or flooded.
The rule: every ohm in the path turns current into heat, P = I²R.
- Tail resistance: 0.15 Ω/1000 ft × 10 ft = 0.0015 Ω. Heat at 100 A: 100 × 100 × 0.0015 = 15 W, spread over 10 ft.
- Sound splice: the 3 in [75 mm] of copper it displaces is about 0.00004 Ω, so under 0.5 W at the same 100 A.
- Corroded joint at 5 mΩ: 100 × 100 × 0.005 = 50 W at one spot, more than three times the heat of the whole tail and concentrated under the sleeve. Adhesive-lined tubing is typically rated near 90-110 C [194-230 F] continuous (typical tubing datasheets), and 50 W in a few centimeters drives the surface well past that.
Decision: keep the finished joint under 1 mΩ, which is 10 W at 100 A. Measure across the splice with the milliohm meter before you shrink anything; above 1 mΩ, cut it out and remake. Torque the set screws to the kit's printed value, because a loose screw is how a sound joint creeps to 5 mΩ within a year.
Making the splice, step by step
- Slide the heavy-wall sleeve onto one cable before anything else; a finished connector never passes through a shrunk sleeve.
- Cut the sheath back and strip each conductor to the strip gauge cast into the connector, keeping the strands unbroken.
- For aluminum, brush the strands to bright metal and work antioxidant compound in; copper needs no compound.
- Insert both conductors to the stop and torque the set screws to the printed value, or crimp with the die the kit calls for; let the tool finish its stroke before you pull.
- Measure across the joint with the milliohm meter: under 1 mΩ, or remake it.
- Center the sleeve over the joint and shrink from the middle outward, gun always moving, until adhesive weeps at both end collars.
- Let it cool about 5 minutes before the splice takes flex, then clip or strap the run so the joint carries no cable weight.
The junction-box route for a splice you will reopen
When the joint gets reopened, for a meter swap, periodic testing or a future extension, put it in a box you can unbolt. A split bolt sized for this conductor runs about 3 in [75 mm] long, so give each one 2 in [50 mm] of clear room on every side and let the tails land without a hard bend. NEC fill rules cap how much conductor a given box volume holds, so count the tails and the two connectors before you pick the size; how to size an electrical enclosure walks through the fill arithmetic. The connector choice inside the box, crimp versus split bolt versus clamp, follows the same range and torque logic as the kit route.
Waterproofing the box is a gland problem. Insulated copper of this size measures roughly 0.5-0.65 in [13-16 mm] across depending on insulation type, so measure your cable and pick a gland whose clamp range covers it, a potted or O-ring gland for a wet wall. The weakest part sets the rating: one gland printed IP54 holds the whole box to IP54. The sealing steps are the same as for any outdoor box, and the cutouts, glands and HMI windows guide covers hole sizes and gland selection.
Bond a metallic box to the equipment grounding conductor. NEC 250.96(A) requires metal parts serving as grounding conductors to be bonded together so they can safely conduct any fault current likely to hit them, and the grounding and bonding guide shows the landing order. Insulate each bare split bolt with self-fusing tape to at least the thickness of the cable insulation.
On US work the enclosure type number is the mark the code reads: NEC 110.28 pairs locations with enclosure types in Table 110.28, even when the box also prints an IP code. The NEMA 4 vs 4X vs IP66 guide sets out where 4X earns its premium. Our Type 4X boxes are rated to the type number by the manufacturer; not UL listed.
A sealed box still breathes with the daily temperature swing, and that cycle can lay condensation on the lid overnight; the condensation guide works out when a splice box should stay sealed and what that moisture does inside.
We build the box to your layout: two gland holes wherever your cable lands, in 304 or 316L stainless, through the custom enclosure builder. It is delivered in 10 business days, counted from your approval of the drawing.
Checks that prove the splice is sealed
- Adhesive weep line at both end collars: no weep, no seal, so re-heat the ends until it shows.
- Sleeve wall smooth and uniform; a bubbled or scorched patch is a thin spot in the dielectric, so remake rather than tape over it.
- Milliohms across the finished joint: under 1 mΩ, so under 10 W at a 100 A working load.
- Insulation test at 500 V DC, conductor to conductor and to ground: sound new 600 V insulation reads in the hundreds of megohms; a reading near 1 MΩ means water is already in the joint, the old rule of thumb for 600 V cable, so open it and remake.
- The splice hangs supported, carries no cable weight, and its location is marked on the conduit so your next visit finds it in seconds.
Mistakes that let water back in
- Tape as the only seal: the layers track water to the connector within a couple of seasons. Tape goes over a shrunk sleeve, half-lapped, and only as a jacket.
- Sleeve forgotten until after the joint: the sleeve cannot pass a connector, so the job restarts with a new kit.
- Recovered ID above the splice OD: no interference fit, the adhesive bridges a void, and the void is where water sits. Keep the recovered ID about 20% below the finished splice.
- Flame parked on one spot: a scorched wall is a thin dielectric. Keep the gun moving and work the heat to the ends.
- A buried joint over an unrated connector: the sleeve cannot upgrade the connector inside it, so the wet-location mark on the kit is the one that decides.
- Reusing a shrunk sleeve: the adhesive has already flowed once, and a second shrink never seals.
The decision for each case
| You have | Build this |
|---|---|
| Rain on an open run, joint stays shut | Inline kit: 1 AWG-250 kcmil connector, heavy-wall sleeve shrunk to a weep, joint under 1 mΩ |
| Burial or standing water | The same kit marked for direct burial; the sleeve is the enclosure, no box |
| Reopening ahead: testing, meter, extension | Type 4X box, split bolts torqued to the label, glands on the measured OD, bonding done, connectors taped |
| Salt air or washdown chemicals | 316L stainless on the box route; the kit sleeve shrugs salt off |
| Aluminum tails | Dual-rated connector and antioxidant compound in either route |
One number runs the whole job, the finished joint under 1 mΩ, about 10 W at 100 A, and one mark: adhesive weeping at both ends of the sleeve before the first rain reaches it.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 8 × 6 × 4 in | 304 stainless | 8 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 4 in | 304 stainless | 10 x 8 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a direct-burial splice kit need a junction box?
No. The sleeve over the connector is the enclosure; a kit listed for wet locations and direct burial is accepted on its own. The NEC requires conductors and splices in wet locations to be suitable for wet locations, and the kit's 600 V wet and direct-burial marking is that suitability. Inspectors look for the listing mark: OSHA 1910.399 defines acceptable equipment as listed, labeled or otherwise determined to be safe by a nationally recognized testing laboratory. A box earns its place only when the joint must reopen.
Can self-fusing tape make a 1 AWG splice waterproof?
Tape buys one or two seasons, then water tracks between the layers to the connector — outdoors it is a jacket, not a seal. Wrap self-fusing rubber tape over a shrunk sleeve as abrasion armor: two layers, half-lapped, a 50% overlap each turn. The listed sleeve underneath stays the seal; the tape keeps gravel, sun and snags off it.
What connector size fits 1 AWG wire?
A bare mechanical or compression splice marked 1 AWG-250 kcmil, dual-rated for copper and aluminum. That range covers this conductor size (130 A at 75 C in the NEC ampacity table) and lets the same kit take a 1/0 tail at 150 A if the extension grows later. Match the tool to the connector: the hex crimp die or the torque wrench set to the printed value.
Is a Type 4X box needed for an outdoor splice, or is Type 4 enough?
Type 4 keeps hose-directed water off the joint; Type 4X adds corrosion resistance. A splice box on plain conduit away from salt spray is fine as Type 4. Near a coast, in brine splash or washdown chemicals, the 316L stainless of a 4X box is the one still sound after ten years. Our Type 4X boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.





