Grounding a multisection industrial control panel

A multisection industrial control panel is one panel built as separate metal enclosures bolted, strapped or set flush together. Ground each section to its own lug or bar — an approved common bus is an option, not a requirement — and bond the grounds together with copper sized from NEC Table 250.122: 10 AWG at a 60 A panel, 8 AWG at 100 A. Bolted joints alone never carry the fault.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 8 min read

Short answer: a multisection industrial control panel is one panel built as two or more separate metal enclosures, and every section needs its own grounding termination. A common bus spanning the sections is one accepted route; separate lugs or bars on each section, bonded to each other, work just as well. What never works is trusting the bolts between sections. Size each bonding jumper like the circuit's equipment grounding conductor, per NEC Table 250.122: 10 AWG copper at a 60 A panel, 8 AWG at 100 A.

What counts as a multisection industrial control panel?

A multisection industrial control panel is one control panel built as two or more separate metal enclosures: sections joined by bolted flanges or straps, wired through connectors, or simply set flush side to side, with each distinct metal box counted as its own section.

NEC 409.2 defines the panel itself as an assembly of two or more power circuit components, control circuit components, or both. It leaves the term multisection to the shop, and the shop reading is simple: every separate metal box in the assembly is a section, whether the boxes hang on shared flanges, strap to each other, carry conduit between them, or just stand flush side to side.

You meet the same four shapes on most jobs:

  • Three wall-mount stainless cabinets bolted into one row, wired as one panel, feeding one machine.
  • A main drive cabinet with an operator station bolted to its side.
  • Two sections butted flush with no fasteners between them at all.
  • One cabinet plus a short remote section carried on a conduit stub.

The working rule: if you can unbolt it, unstrap it or slide it away, it is a section, and it gets a grounding termination of its own. Each of those boxes is exposed conductive metal that has to reach the fault path on purpose. The grounding and bonding guide covers that fault path; this article stays on what the sections change.

Is a grounding bus required for a multisection panel?

No — the bus is one accepted arrangement, and separate approved grounding lugs or bars on each section work equally well, provided every grounding point is bonded to the others so the whole line-up shares one fault path.

The rules demand the outcome, not one piece of hardware. NEC 250.4(A)(5) requires an effective ground-fault current path: low impedance, able to safely carry the fault current likely imposed on it, and the earth forms no part of it. NEC 250.96(A) reaches the metal parts: raceways, cables, equipment and enclosures serving as grounding conductors are bonded together so they can safely conduct that fault. A bus is one way to satisfy both at once; a termination in every section, chained, is the other.

Arrangement Where it fits best What it still needs
Approved common bus spanning the sections Line-ups supplied with a bus kit or continuous bar Every section bonded to the bar, and the bar bonded to the supply conductor
Approved lug or grounding bar on each section Any build, any number of sections Jumpers between sections, sized from NEC Table 250.122
Bolted flanges, straps, flush contact Holding the sections together mechanically A deliberate grounding connection beside them

Both routes qualify when the components do: a bus kit made for the job, or lugs listed for the conductor sizes you land on them. What no arrangement waives is the deliberate connection in every section. A flange that happens to conduct today is not something you can point to as the design; give every box its own landing and bond the landings.

For three sections or fewer, individual bars plus two jumpers are usually the cheaper, tidier answer. A bar per section keeps the landings ordered; whether that bar beats a single stud is a layout call, and the earth bar versus stud article works that trade at ten earth cables. The mechanics of landing a cabinet on a bus are in the piece on bonding an enclosure to a ground bus.

Keep this fault-current bonding apart from signal commons: how the 24 V DC supply 0 V terminals tie together is its own decision, covered on the page about connecting separate 24VDC power supply 0V grounds together.

What size bonding conductor joins the sections?

Size each bonding jumper from the rating of the overcurrent device ahead of the circuit, the same way NEC Table 250.122 sizes any equipment grounding conductor.

The jumper between two sections does the job of the equipment grounding conductor for that circuit, so it takes the same copper. Copper values, from NEC Table 250.122:

Overcurrent device ahead of the circuit Copper bonding jumper
20 A 12 AWG
60 A 10 AWG
100 A 8 AWG
200 A 6 AWG

Keep each hop short and direct, because every extra foot adds impedance to the path the breaker is watching. A single metal box has the same logic in miniature; the junction-box jumper article sizes that one, and the sub panel jumper article walks the two rules on a subpanel.

Worked example. Three stainless sections bolted in a row, fed from a 60 A branch breaker. Two hops between adjacent grounding bars, 30 in [760 mm] each, plus a 24 in [610 mm] drop from the incoming lug to the first bar: 84 in, or 7 ft [2.1 m], of bonding copper. NEC Table 250.122 at 60 A calls for 10 AWG. Ten AWG copper runs about 1.0 Ω per 1000 ft [3.3 mΩ per m] at 20 °C, and copper resistance rises about 0.39 % per K, so at a running 75 °C it sits roughly 21 % higher. Seven feet of hot 10 AWG adds 7 × 1.21 Ω / 1000 ft = 0.0085 Ω to the path. A fault pulling ten times the breaker rating, 600 A, then drops 600 A × 0.0085 Ω = 5.1 V across the bonding copper — a trivial share, which is what lets the 60 A breaker clear promptly.

How do you bond the sections, step by step?

Work through the line-up one section at a time: a termination on bare metal in every enclosure, jumpers chained bar to bar at the table size, and the supply grounding conductor landed where the power enters.

What you need:

  • One grounding lug or bar per section, sized for the jumper — a #10 lug for the 60 A worked example.
  • Copper jumper at the table size from NEC Table 250.122.
  • External-tooth lock washers, so the fastener bites through oxide into bare metal.
  • A wire brush or scraper for paint, mill scale and anodize.
  • A torque driver; lugs carry their torque value stamped on them.
  1. Lock out and tag the supply, then verify absence of voltage at the incoming terminals before the first wrench turns.
  2. Walk the line-up and list every separate metal section on the drawing, including one that only butts against its neighbour.
  3. Brush each landing to bare metal. NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding and bonding connections, unless the fitting is made to cut through them.
  4. Fasten a lug or bar to each section onto bare metal, with a toothed washer under the fastener head.
  5. Chain the sections: run the jumper bar to bar, section 1 to 2 to 3, at the table size, keeping every hop short and direct.
  6. Land the supply equipment grounding conductor on the section where power enters; the article on grounding conductor entry covers the connector and bond at the wall.
  7. Bond each hinged door to its own cabinet; hinge bearings are not part of the fault path, and the door bonding article sizes and routes that jumper.
  8. Torque every landing to the value stamped on the lug, and mark each grounding point so the next service call finds them.

What checks prove the ground path before you re-energize?

Confirm three things with the panel still locked out: a deliberate termination on every section, a continuous chain between them, and a resistance reading that matches the copper you installed — about 0.0085 Ω for the 7 ft of 10 AWG in the worked example.

  • Meter every hop end to end and compare it with the copper's own share. A 0.1 Ω reading on a hop that should carry 0.0085 Ω means a landing is adding twelve times the conductor's resistance; redo that joint.
  • Tug each jumper, then re-torque the landings after the first week of running; thermal movement loosens first-time joints.
  • Trace the drawing section by section and name the conductor on every hop. A section that reaches the path only through its flange bolts fails the trace.
  • Swing each door through full travel and watch its bonding jumper for drag or pinch.
  • Record the readings, and initial the grounding points on the panel drawing.

Which mistakes leave a section ungrounded?

The failures are predictable: a section trusted to its flange bolts, one jumper landing short of the last cabinet, a painted-over lug, a hinged door riding on its hinges, and an undersized hop counted as bonding.

  • Trusting the joint. Flanges, straps and flush faces hold the sections mechanically; paint, mill scale and corrosion spoil their contact over the service life. The bolts carry the weight; the copper carries the fault.
  • One ground for the whole line-up. Landing the supply conductor on section 1 and stopping there leaves sections 2 and 3 on bolted faith. Every section gets its own termination on the chain.
  • Paint left under a lug. The NEC 250.12 rule from step 3 applies at every section, not just the first.
  • A door left off the chain. Each hinged door carries its own bonding jumper; the hinges were never part of the design path.
  • A rod instead of the conductor. At an outdoor line-up, a driven rod is an auxiliary electrode under NEC 250.54: bond it to the equipment grounding conductor as a supplement, and keep the fault return in the conductor, because the earth is not part of that path under NEC 250.4(A)(5).
  • Undersized copper. A 14 AWG pigtail on a 60 A circuit is two sizes light of the 10 AWG the table calls for. When a hop runs long, one size up, 8 AWG, costs little and trims the impedance.

What do you send with an order for a multisection build?

Tell us the number of sections, each section's material and rating, and where you want a grounding bar or stud in each one; we build each section to your drawing and deliver the line-up in 10 business days from your approval of the drawing.

Materials first: 304 stainless in a #4 brushed finish covers indoor washdown, food and beverage and most outdoor sites; 316L covers salt air, brine, chlorides, pharma and chemical areas. The wall-mount sections are manufacturer-rated NEMA 4X-type / IP66, not UL listed.

Send the section count, each section's material and outside size, the enclosure type the job calls for, and the position of every grounding bar, stud and cutout. We send a drawing back for your approval, and the 10-day clock starts at that signature, anywhere in the world. The stainless size finder filters the wall-mount and HMI lines by grade and size, and custom enclosures is where the cutout-by-cutout build starts.

Where the project needs the panel itself listed, that review examines the finished assembly, and the UL 508A label walkthrough shows what gets checked.

The bench decision: count every separate metal box as a section, terminate each one on bare metal, chain them with copper sized from NEC Table 250.122 for the overcurrent device ahead of the circuit, land the supply conductor at the power entry, and let a bus serve only where the panel design brings one.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can the bonding jumper daisy-chain from bar to bar?

Yes. Chain one continuous jumper through each following bar, or land each hop as a separate length; both give every section its own termination on the shared path. In the 60 A worked example, two 30 in [760 mm] hops plus a 24 in [610 mm] drop give 7 ft of copper, about 0.0085 Ω when hot. Keep the hops short and support the conductor clear of sharp edges.

What size jumper for a 100 A or 200 A line-up?

NEC Table 250.122 sizes the copper from the overcurrent device ahead of the circuit: 8 AWG at a 100 A breaker, 6 AWG at 200 A. Where a hop runs long, one size up is cheap insurance, because the impedance of the path the breaker watches is what makes it clear promptly.

Does the neutral bar serve as the grounding bus for the sections?

It does not. NEC 250.6 exists to keep neutral current off the metal parts: neutrals land on the isolated neutral terminal and equipment grounds on the ground bus. Mixing them puts load current on every enclosure in the line-up, and a loose neutral-to-ground bond then energizes sections that should sit at ground potential.

Is a bright, scraped bolted joint enough between two sections?

Scrape the contact under every lug; that is what NEC 250.12 asks at grounding connections. The splice between two sections is a different job: paint and mill scale grow back, vibration works the joint, and corrosion creeps into the seam over the panel's life. Keep the copper jumper at the table size and the joint stops being a fault path to maintain.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides