Short answer: fit a bonding jumper across the hinge of every enclosure door that carries powered components, and size it to the largest circuit conductor landing on that door — 14 AWG [2.1 mm²] green copper covers most doors with a 120 VAC HMI on them. UL 508A, the standard for industrial control panels, lets a panel skip the conductor only when every door-mounted component sits on a control circuit rated 30 V rms or less, such as a 24 VDC logic circuit. A continuous stainless hinge pin looks like a bond and behaves like one only on the day it is assembled. Its contact resistance drifts with door motion, washdown water and oxide films, which is why the standards specify a conductor instead. The steps below take you from the circuit list to a fitted jumper and the milliohm check that proves it.
When the door needs a jumper
UL 508A sets the rule: an internal bonding conductor joins a metal door or cover that carries electrical components to the enclosure or its grounding terminal. The conductor's ampacity matches the largest circuit conductor used to connect the door-mounted components. There is one exception: when every door-mounted component connects to a control circuit rated 30 V rms or less, the panel ships without the conductor. DC counts at its own value, so a 24 VDC control circuit sits under the line and a 120 VAC door circuit sits far above it.
NEC 250.96(A) says the same thing at the installation level: metal parts intended to serve as equipment grounding conductors — raceways, cables, equipment and enclosures — are bonded together so they can safely conduct any fault current likely to be imposed on them. A door feeding a bolted ground terminal on an HMI is exactly such a part. The panel-side rules sit inside the wider grounding picture; the grounding and bonding guide covers the conductor sizing and the terminal work this article builds on.
| Door-mounted loads | Jumper | Size |
|---|---|---|
| Any circuit above 30 V rms: a 120 VAC HMI, door lights, a door-mounted fused disconnect | Required | Same as the largest door circuit conductor |
| Only control circuits at 30 V rms or less: 24 VDC logic, pilot LEDs | Optional under the panel standard; fit one anyway outdoors, in washdown and in classified areas | 14 AWG copper is the common choice |
| Nothing electrical | None | — |
Many doors also carry an interlock switch, and whether it rides the hinge edge or the latch edge decides where the jumper can run. An HMI in the door brings its own cutout and sealing questions; the cutouts, glands and HMI windows guide covers how an opening is specified without giving up the rating.
What the tables say about size and color
Two tables do the sizing work, and they agree. NEC Table 250.122 sizes an equipment grounding conductor from the rating of the overcurrent device ahead of it: 14 AWG copper for a 15 A circuit, 12 AWG for 20 A, 10 AWG for 60 A. The internal bonding table in the panel standard follows the same logic and lands on the same sizes at these currents; for a door circuit protected at 30, 40 or 60 A, 10 AWG copper covers it. Mirroring the largest door conductor gives the same answer with no table at all.
Color follows NEC 250.119: an insulated equipment grounding conductor of 6 AWG [13.3 mm²] and smaller is green, or green with one or more yellow stripes, so the jumper reads as a ground at a glance. UL 508A is also the standard a panel is listed to when the finished panel carries a mark; the UL 50E, NEMA 250 and panel listing guide walks what a listing covers. UL 508A, NFPA 79 and the NEC split the panel rules between them.
What you need
- Green insulated copper for the jumper: 14 AWG [2.1 mm²] for most doors, 10 AWG [5.3 mm²] when a 30-60 A circuit lands on the door
- Two crimped ring lugs matched to the wire size and the stud size
- Internal-tooth washers, two per landing, so the teeth bite both faces
- A ground stud or tapped hole on the enclosure body and on the door, each within about 6 in [150 mm] of the hinge
- A 4-wire (Kelvin) low-resistance meter — a continuity beeper reads far too high for this job
- A torque driver set to the lug maker's printed value
The enclosure-side basics live in the grounding and bonding guide, including why the earth is not considered part of the effective ground-fault current path under NEC 250.4(A)(5).
Fitting the jumper, step by step
- List every door-mounted component with its circuit voltage and conductor size. Mark the largest conductor; in the worked example below that is the feeder to a 120 VAC HMI. Any door circuit above 30 V rms makes the jumper required, and one jumper covers the whole door.
- Order the landing points with the enclosure. On a custom stainless box you set every cutout, so the two bonding holes go on the drawing beside the gland cutouts, with the sealing method called out for the approval drawing.
- Measure the closed-door run and cut with slack. The straight distance between landing points in the example is about 9 in [230 mm]; half again for the swing gives a 14 in [356 mm] jumper.
- Land the enclosure end on the body itself — a stud or tapped hole on the flange near the hinge, with a toothed washer under the lug and one on top. On powder-coated steel, NEC 250.12 calls for paint, lacquer and enamel to be removed from the contact surfaces unless the fitting is designed to bite through; on stainless the teeth cut through the oxide film.
- Land the door end the same way, again within about 6 in [150 mm] of the hinge so the jumper pivots instead of snagging. Where door circuits enter through glands, the gland shells sit on the same bond path, so land each gland shell on bare metal too.
- Route a drip loop so the wire dips below both landings and washdown water runs off instead of wicking into a lug. Tighten both fasteners to the lug maker's printed torque and tug each lug.
If the jumper run crosses the backplate layout, keep it clear of the DIN rail and wiring duct layout so the duct fill stays workable and the wire is not pinched under the rail.
Checks when done: the milliohm math
Worked example: a 24 x 20 x 10 in [610 x 508 x 254 mm] stainless wall-mount box on a washdown food line. The door carries an HMI fed at 120 VAC through 14 AWG [2.1 mm²] conductors on a 10 A breaker, plus three 24 VDC pilot lights on 18 AWG. The largest door conductor sets the size, so the jumper is green copper in that gauge, cut 14 in [356 mm] with the swing slack from step 3.
Wire resistance: copper is 1.72 × 10⁻⁸ Ω·m at 20 °C, and 14 AWG is 2.08 mm² of copper, so the wire alone gives R = (1.72 × 10⁻⁸ Ω·m × 0.356 m) ÷ 2.08 × 10⁻⁶ m² = 2.9 mΩ. Two crimped lug joints add a few milliohms, so the assembled jumper lands at about 5-10 mΩ. Inside a panel running at 40 °C, copper's 0.39 % per K temperature coefficient adds under 10 %, and the reading stays single-digit.
The hinge, for comparison, also reads milliohms the day the door is hung. Door motion and washdown water grow oxide films in the pin joint, and the reading can climb by orders of magnitude across a service year. That drift is the whole argument for a conductor.
Prove the joint: read door-to-enclosure with the door closed, swing the door through its full 120° ten times, then read again. A sound bond returns the same single-digit milliohm value; a climbing number points at a loose lug or a toothed washer that never bit the metal. Record the reading with the panel build documentation, and repeat the test at each shutdown on washdown boxes.
Mistakes that cost the bond
- Counting the hinge as the bond. No bonding table gives a hinge pin a size or a rating, and the drift pattern above is the normal course.
- Landing on paint. A lug on powder coat reads open circuit; NEC 250.12 wants bare contact surfaces or fittings designed to bite through.
- Skipping the jumper because the door is 'only 24 volts' while a 120 VAC HMI or door heater also hangs on it. One circuit above 30 V rms makes the jumper required for the whole door.
- Cutting the jumper to the closed-door distance. It pinches at the hinge knuckle, fatigues and fractures; the half-again slack rule keeps it whole.
- Field-drilling the landing holes on a rated box. A bare drilled hole ends the manufacturer's water rating, which is why the holes belong on the drawing.
Classified areas and what to order
A Class I Division 2 installation adds a layer the NEMA rating cannot supply: the enclosure itself and every door-mounted device need the equipment approval for the classified area. We build general-purpose and Type 4X stainless enclosures, so for a classified site you source the certified box from a supplier of approved equipment, and this jumper practice travels with it. In classified areas, fit the jumper even when every door circuit sits at or below 30 V rms, so the door cannot sit at a different potential from the body and arc across the hinge joint.
Order the bond with the box. On a custom enclosure you set material, size and every cutout, so the bonding studs go on the drawing next to the glands, pressed or welded through the wall, and there is no extra hole to seal. Pick the material for the area — 304 for most washdown plants, 316L for salt, brine and chemical mist — then lay it out on the custom stainless cutout page. Delivery is 10 business days from your drawing approval, anywhere in the world. The finished box is rated NEMA 4X / IP66 by the manufacturer; not UL listed — the panel mark is earned on the finished panel by the panel builder.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 20 × 10 in | 304 stainless | 24 x 20 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a door with only 24 VDC components need a bonding jumper?
The panel standard lets a panel skip the conductor when every door-mounted component connects to a control circuit rated 30 V rms or less, and 24 VDC sits under that line. Fit one anyway outdoors, in washdown zones and in classified areas: green copper jumper wire with two toothed-washer landings takes minutes to fit and holds a single-digit milliohm reading through years of door swings.
What size should an enclosure door bonding jumper be?
Match the largest circuit conductor landing on the door. NEC Table 250.122 gives the rows: 14 AWG copper for a 15 A circuit, 12 AWG for 20 A, 10 AWG for 60 A. The internal bonding table in UL 508A lands on the same sizes at these currents. Insulated conductors of 6 AWG and smaller are green or green with yellow stripes under NEC 250.119.
Can the stainless hinge pin act as the door bond?
Treat it as mechanical hardware only. A clean, dry pin joint can read a few milliohms on assembly day, but door motion and washdown water grow oxide films that push the reading up by orders of magnitude across a service year. A fitted jumper sized to the largest door conductor carries a couple of milliohms of copper in a 356 mm [14 in] run, plus a few milliohms for the crimps, and it holds that value.
How do you check a door bonding jumper after fitting it?
Measure door-to-enclosure resistance with a 4-wire low-resistance meter; a continuity beeper triggers at many ohms, which proves a path exists but says nothing about a bond measured in milliohms. Read with the door closed, swing it fully ten times and read again. A sound joint returns the same single-digit value; a climbing number means a loose lug or a toothed washer that never bit.