Short answer: in 46 °C [115 °F] desert sun, a small sealed stainless box carrying a 2 W board settles around 64 °C [147 °F] inside - about 24 K past the 40 °C ambient rating most electronics carry. Full shade plus a light finish brings that near 50 °C, and a filtered fan sized at CFM = 1.76 × W / ΔT(°C) - about 5 CFM here - holds the air within 10 K of ambient with the sun still on the box. The arithmetic below takes ten minutes with a multimeter, and it ends with the holes that keep the rating honest.
How hot does a sealed box actually get in full sun?
Plan on 15-25 K above ambient for a small unshaded stainless box under 1000 W/m² of sun, so a 46 °C afternoon puts the inside near 65 °C - and the sun supplies almost all of it, not your board. A sealed box can only run at ambient or warmer; there is no passive path below it. Your 2 W board, spread over 0.326 m² of stainless at k = 3.7 W/m²K, adds 2 / (3.7 × 0.326) = 1.7 K on its own.
The sun is the other 17 K of that rise. Clear-sky noon delivers about 1000 W/m² in the US Southwest; the clearest published desert readings reach about 1044 W/m². A heavy overcast drops to 100-300 W/m², and the whole result falls roughly in proportion. For the full method - wall areas by orientation, hour by hour - read the solar heat load article, and see outdoor enclosures for siting on a sunlit wall.
How do I measure the heat my electronics really make?
Measure the watts going in: a Pi-class board with a camera draws about 5.1 V × 0.4 A = 2.0 W at a USB power meter, and that measured figure - not the adapter's nameplate - is the heat your box must shed. Every watt that enters the box leaves as heat, so the input power is the heat load. Nameplates mislead: adapters are rated for peaks two to three times the running draw.
Put a USB meter inline, or a DC clamp around the supply pair, and log for a day to catch duty cycles. A camera streaming with IR LEDs at night can draw double its daytime current. A small single-board computer lands between 1 W and 3 W, which is why you measure it and then go after the sun: on this box the sun load is ten times the electronics.
How much of the sun's heat gets into the box?
On the example box - 12 × 10 × 6 in [305 × 255 × 152 mm] stainless - full desert sun puts about 40 W onto the walls, and roughly half of that, 20 W, crosses to the inside air. Absorbed solar = irradiance × effective sun-facing area × absorptance. The roof is 0.077 m², the sunward side adds a little at low angles, so take 0.10 m² as the effective area. Mill stainless absorbs about 0.40 of sunlight (typical solar-absorptance table values; a named paint's datasheet wins): 1000 W/m² × 0.10 m² × 0.40 = 40 W.
The wall sheds part of that straight back to the outside air. With the similar inside and outside surface films behind k = 3.7 W/m²K, about half of the absorbed 40 W reaches the inside air: 20 W. Add your 2 W board and run the balance:
- Surface area A = 2 × (0.305 × 0.255 + 0.305 × 0.152 + 0.255 × 0.152) = 0.326 m²
- Total heat Q = 20 W + 2 W = 22 W
- Rise ΔT = Q / (k × A) = 22 / (3.7 × 0.326) = 18 K
- Inside air = 46 °C + 18 K = about 64 °C
Finish moves the absorptance, and with it the answer:
| Finish | Solar absorptance | Absorbed at 1000 W/m² on 0.10 m² | Inside air at 46 °C ambient |
|---|---|---|---|
| White paint | 0.25 | 25 W | ≈ 58 °C |
| Mill stainless | 0.40 | 40 W | ≈ 64 °C |
| Light grey paint | 0.50 | 50 W | ≈ 68 °C |
| Dark grey or black | 0.80 | 80 W | ≈ 81 °C |
All four rows carry the same 2 W board and the same arithmetic. A painted steel wall transfers at k = 5.5 W/m²K and plastic at 3.5 W/m²K, but a dark finish gives back far more than the better k gains.
Is shading enough, or do I need a fan?
Shade is enough when ambient plus about 4 K stays under the equipment rating: at 46 °C a fully shaded 2 W box holds near 50 °C, which suits gear rated 50 °C and leaves 40 °C-rated gear out of reach. A cover over the box removes the direct beam; sky-diffuse and ground-bounce typically leave 10-20% of clear-sky noon, so take 15%: 40 W × 0.15 = 6 W absorbed, 3 W inward, 5 W total, and ΔT = 5 / (3.7 × 0.326) = 4 K. How a sun shield cuts solar heat load gives the standoffs and gaps that stop the shield re-radiating onto the box.
| Your case | What holds the temperature |
|---|---|
| Ambient ≤ 35 °C, shaded, ≤ 5 W | Sealed box: rise ≈ 4 K, no fan |
| 46 °C ambient, shaded, gear rated 50 °C | Sealed box at ≈ 50 °C |
| 46 °C ambient, full sun, gear rated 50 °C+ | Filtered fan ≈ 5 CFM: air within 10 K of ambient |
| 46 °C ambient, gear limited to 40 °C | Re-rate the gear or fit an enclosure air conditioner |
For one hot board in a small sealed box, conduction cooling to the wall is the quiet alternative to any fan. Run your own numbers next in the enclosure heat calculator.
How many CFM does the fan need?
Size it from the heat it carries: CFM = 1.76 × W / ΔT(°C), the same law as CFM = 3.16 × W / ΔT(°F), both for air at 1.2 kg/m³ at sea level - our 22 W at a 10 K rise needs 3.9 CFM, or about 5 CFM with the filter loaded.
- Add the watts the air must carry: 2 W board + 20 W inward sun = 22 W unshaded; 5 W shaded.
- Pick the air rise you accept, 10 K typical. Airflow scales inversely with it: allow 5 K and you double the CFM, allow 20 K and you halve it.
- CFM = 1.76 × 22 / 10 = 3.9 CFM. In Fahrenheit: 3.16 × 22 / 18 = 3.9 CFM.
- Add 20-30% margin for the filter's pressure drop as it loads (adding a filter without choking the fan) and another 20% above 2000 m [6,600 ft], where thin air carries proportionally less heat: 3.9 × 1.3 ≈ 5 CFM.
- Read the fan's curve at that back-pressure, not its free-flow sticker.
- Prove the result with a logged day, as the next section describes.
For a sanity check, invert the law: W = 0.57 × CFM × ΔT(°C). A 10 CFM fan at an 8 K rise carries about 46 W, so one salvaged laptop fan covers twenty of these boxes - run it slow and quiet. Air has to go through the box, intake to exhaust; fan-cooled enclosure airflow shows the placement that stops the exhaust recirculating into the intake.
How do I cut the intake holes without wrecking the rating?
The fan-and-filter kit carries its own rating - IP54 is the common one for outdoor kits - and once it is on the door, the assembly is IP54, whatever the box alone says. The weakest part sets the assembly's rating. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and after a filtered fan goes on, the filter's code describes the box: first digit 5, dust-protected; second digit 4, splashing water. In a hose-down zone, keep the box sealed and move the heat with an enclosure heat exchanger or air conditioner, or mount the fan-cooled box outside the spray. NEC 110.28 keeps the systems separate in US installations: a spec that calls for an enclosure type is met by the type, and an IP code alone will not satisfy it.
Cut the intake low on the shaded side and the exhaust high on the opposite face, so stack effect works with the fan. Put a rain hood over any upward-facing opening, deburr the cutouts, and seat the kit's gasket flat. You can also order the box with the openings cut and finished at the factory - small stainless junction boxes go through checkout with your cutouts and are delivered in 10 business days from your approval of the drawing. To reverse the flow, physically flip the fan: these are brushless DC or EC fans, and swapping the leads achieves nothing useful. Lock out and prove the box de-energized before you drill or wire anything mains-powered.
How do I prove the cooling works?
Log one clear day and judge the worst hour: with the board's own sensor or a logger at its air inlet, the build passes when the peak sits at least 5 K under your equipment limit, and 2-4 pm is usually the peak. Where to measure ambient temperature inside an enclosure covers probe placement. Intake air should read within a kelvin of outside ambient. Exhaust should read ambient plus the rise you designed - 46 °C + 10 K = 56 °C in this example.
If the measured exhaust rise runs 2-3 K over design, the filter is loading or the fan is running slow; clean it and re-log. Repeat the check after the first summer, because a season of dust and bugs eats the margin you added in step 4.
What mistakes kill the board or the rating?
Four do the damage: a fan stirring sealed air, a filter the bugs have nested in, a dark finish in full sun, and a filtered fan where the hose hits. An internal-only fan removes 0 W from a sealed box - it couples a hot board to the walls (your 1.7 K at 2 W) while the sun load stays put. An unscreened intake nests in one season, so fit the kit's mesh and check it monthly in bug weather. Dark grey paint runs the worked box at 81 °C against 58 °C in white - a 23 K swing for a colour choice. And an IP54 kit in the wash zone loses to the hose; that box needs the sealed route.
One night-time trap remains: when the fan stops, a clear sky radiates the box surfaces below ambient and dew forms on your board. Run the fan continuously, or in a sealed box fit a small 5-10 W thermostat-controlled heater; the outdoor enclosures page covers heaters and condensation in detail.
Decision in one line each: ambient under 35 °C and shaded - sealed box, no fan. Desert sun with 50 °C-rated gear - shade and a light finish, sealed box. Sun on the box and you want the margin - filtered fan at 1.76 × W / ΔT(°C) plus the filter margin, about 5 CFM here. Gear limited to 40 °C at a 46 °C ambient - re-rate the gear or fit an enclosure air conditioner.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a fan inside a sealed box cool the electronics?
No. A recirculating fan only evens out hot spots; the heat still leaves through the walls at k x A, and 2 W through 0.326 m2 of stainless (k = 3.7 W/m2K) is a 1.7 K rise. Getting heat out of the box takes airflow through it, a conduction path to the wall, or refrigeration.
How much does white paint or full shade actually buy?
On the worked box at 46 C ambient: mill stainless (absorptance about 0.40) lands at 64 C inside, white paint (about 0.25) at 58 C, full shade at 50 C. Shade plus a light finish together are the cheapest 14 K you will ever take off an enclosure.
Can I keep a NEMA 4X rating after mounting a filtered fan?
No - the assembly takes the kit's rating, typically IP54: dust-protected and rated for splashing water. Keep a filtered-fan box out of the hose-down zone; where the hose hits, leave the box sealed and move the heat with an enclosure heat exchanger or air conditioner.
What if ambient alone is above my equipment's rating?
At 46 C ambient with gear limited to 40 C, no fan or shade reaches the target: a fan-cooled box bottoms out at ambient and a sealed one sits above it. Switch to equipment rated 50-60 C (common for single-board computers and PoE devices) or fit an enclosure air conditioner, the only box-side option that cools below ambient.





