Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Exhaust heat dissipation in an enclosure: from watts to fan airflow

Take h from published convection tables — 10 W/m²K for slow air, 100 W/m²K for a moderate stream — to bracket the exhaust's watts, then size the fan from V = Q/(ρ·cp·ΔT). A 500 W load on a permitted 10 K rise needs 0.0415 m³/s of air: 149 m³/h, or 88 CFM.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 7 min read

Short answer: bracket the coefficient, then move past it. Published tables of convective coefficients put forced convection in air at 10 W/m²K for slow flow over a surface and 100 W/m²K for a moderate stream, so treat those as the ends of your estimate. Then size the fan from the air-side balance, V = Q / (ρ × cp × ΔT): a 500 W load on a permitted 10 K rise needs 0.0415 m³/s of air — 149 m³/h, or 88 CFM. The coefficient only fixes the first number, and it can move your fan size fivefold; the airflow arithmetic is exact.

The only ballpark worth using for h

You want one number for h, and the tables give you a bracket instead: 10 W/m²K for low-speed forced air over a surface, 100 W/m²K at moderate speed, and still air sits near 10 W/m²K again. The coefficient belongs to the airflow, so choose your row from the air speed at the duct. In the usual regimes h grows with speed somewhere between its square root and its four-fifths power, so quadrupling the air speed roughly doubles to triples h.

Air movement at the duct h to use, W/m²K
Still air, natural convection about 10
Slow drift, about 1 m/s [200 ft/min] 10 to 25
Fan-blown, 2 to 5 m/s [400 to 1,000 ft/min] 50 to 100

Radiation rides along with the convection you set out to compute. A duct at 150 °C [302 °F] in 40 °C [104 °F] surroundings radiates about 3.5 W/m²K with bright stainless and about 10 W/m²K once it is oxidized or painted, from the Stefan–Boltzmann relation. At slow air speeds that radiant share is as large as the convection term, so either count it or keep the duct polished.

Two equations, two different questions

The surface equation estimates a load; the air balance turns a load into fan flow. Q = h × A × (T_surface − T_air) answers how many watts the duct dumps into enclosure air. V = Q / (ρ × cp × ΔT_air) answers how much air carries those watts out for the rise you allow. Use the first while a hot duct is all you know, and the second for every buying decision afterwards.

Equation Answers Inputs
Q = h × A × ΔT_surface watts leaving the duct h from the table, exposed area, surface-to-local-air difference
V = Q / (ρ × cp × ΔT_air) fan flow for the allowed rise load Q, ρ = 1.2 kg/m³, cp = 1,005 J/(kg·K), allowed rise

Those air properties hold at 20 °C [68 °F] near sea level; air at 50 °C [122 °F] is about 10 % lighter, so add a tenth to the flow on a hot site. Keep the boundary honest while you are at it. Count only the duct length whose heat lands inside the box, and measure the air next to the duct rather than the room, because after an hour of running it is warmer in there.

The sealed box also sheds a little through its walls, 3.7 W per square metre of stainless per kelvin of rise, which is the path the heat calculation guide works for sealed boxes. Once a fan moves the air, the airflow term dominates, and the fan airflow calculation near ambient temperature covers the same balance for boxes whose inlet and outlet sit close in temperature.

From a hot duct to a fan size in six steps

  1. Measure the exposed duct. Note the outside diameter and the length actually inside the enclosure, then A = π × d × L for a round duct. Lagged or shielded sections contribute nothing to enclosure air.
  2. Take two temperatures. Read the duct surface with a thermocouple or an IR gun with emissivity set correctly, and read the air within a hand-width of it; the difference is ΔT_surface.
  3. Pick h from the air speed using the table above, and add 3.5 to 10 W/m²K for radiation unless the surface is polished.
  4. Add the panel's own heat. Take each device's dissipated watts from its datasheet; when the datasheet is silent, the device heat-loss lookup shows how to get the number.
  5. Choose the allowed air rise. Ten kelvin is the usual allowance: with 30 °C [86 °F] inlet air it holds the outlet at 40 °C [104 °F], the ambient ceiling for drives and most electronics unless their datasheets allow more.
  6. Convert, then select the fan. Compute V = Q / (ρ × cp × ΔT_air) and buy against the delivered-flow curve with your grilles and filter fitted, because free-air ratings flatter a fan and the grille pressure-drop numbers show by how much.

Worked example: a 3 in exhaust duct in a 24 x 20 x 8 in box

A typical case; put your own measured numbers in the same slots.

Inputs.

  • Duct: 3 in [76 mm] outside diameter with 20 in [0.51 m] exposed inside the box, from the installation drawing.
  • Surface at 150 °C [302 °F], air next to it at 40 °C [104 °F] after an hour of running, so ΔT_surface = 110 K.
  • Air drifts slowly past it, so h = 25 W/m²K from the slow-drift row; the duct is bright stainless, and its 3.5 W/m²K radiant share stays in hand as margin.
  • Electronics on the plate dissipate 170 W, from the device datasheets.
  • Box: 24 × 20 × 8 in [0.61 × 0.51 × 0.20 m] stainless, 1.07 m² of wall.
  • Allowed air rise 10 K over a 30 °C [86 °F] inlet; air at 20 °C [68 °F], so ρ = 1.2 kg/m³ and cp = 1,005 J/(kg·K).

Rule in words. A cylinder's exposed area is π × diameter × length; duct heat is coefficient × area × temperature difference; fan flow is heat divided by density × specific heat × allowed rise.

Arithmetic.

  • A = π × 0.076 m × 0.51 m = 0.122 m², call it 0.12 m².
  • Duct heat: 25 W/m²K × 0.12 m² × 110 K = 330 W.
  • Load into enclosure air: 330 W + 170 W = 500 W.
  • Wall credit: 3.7 W/m²K × 1.07 m² × 10 K = 40 W, so size to the full 500 W and let the wall be margin.
  • Flow: V = 500 / (1.2 × 1,005 × 10) = 500 / 12,060 = 0.0415 m³/s, which is 149 m³/h or 88 CFM.
  • Imperial cross-check: 500 W is 1,706 Btu/h and 10 K is 18 °F, so with the standard sea-level factor of 1.08 Btu/(h·CFM·°F), CFM = 1,706 / (1.08 × 18) = 88.

Decision. The walls of this box alone hold a 10 K rise only up to about 40 W of load; at 500 W the decision is made, and you order a fan or a cooler that moves at least 88 CFM through this heat. The spread that h causes shows why the estimate deserves a label:

h, W/m²K Duct heat, W Total with 170 W of electronics Fan flow at 10 K rise
10 132 302 0.025 m³/s (53 CFM)
25 330 500 0.0415 m³/s (88 CFM)
50 660 830 0.069 m³/s (146 CFM)
100 1,320 1,490 0.124 m³/s (262 CFM)

Ten times the coefficient means five times the fan. So design on the row that matches your air speed, then replace the estimate with the measurement below at commissioning.

Checks that prove the fan is carrying the load

  • Run at maximum load until the readings stop moving, about an hour on a box this size, then measure inlet and outlet air. A rise of 10 K or less proves the flow.
  • Read 14 K instead? The fan is moving 10/14 of design, about 63 CFM of your 88, so clean or upsize the filter before touching the heat estimate.
  • Confirm delivered flow with an anemometer at the outlet: 88 CFM through a 4 in [100 mm] opening is about 5 m/s [1,000 ft/min] of face velocity.
  • Repeat after the first filter change; loading is what steals flow over the months.

What a fan opening does to a Type 4X rating

NEMA's enclosure FAQs state the weakest-link rule: an assembly's rating follows its lowest-rated part. A cooling opening with a fan and filter grille therefore re-rates a stainless Type 4X box down to the grille's level, which is acceptable indoors in dry, clean air and wrong for washdown. For a box that must hold its rating, keep it sealed and move the heat with a closed-loop unit; the fan versus air conditioner versus heat exchanger comparison picks the device on the same 500 W. Our boxes are rated NEMA 4X / IP66 by the manufacturer and not UL listed, and the fan or cooler cutout goes on the custom drawing, delivered in 10 business days from your approval of the drawing.

Keep the hot duct off the door seal: EPDM gasket material holds to 150 °C [302 °F] and silicone to 200 °C [392 °F], so a 150 °C duct riding an EPDM seal sits at its ceiling. And treat the duct as live heat: 150 °C burns bare skin in seconds, so the guard stays in place whenever the fan runs.

The decision by case

  • Up to about 40 W total in a box this size: the stainless walls hold the 10 K rise by themselves, so keep the box sealed and fanless. The small-enclosure heat dissipation article and the non-ventilated stainless sizing article carry that path, and the enclosure heat calculator checks your number.
  • Above the wall capacity, dry indoor air: fit the fan-and-grille set at the calculated flow, 88 CFM in the example, and accept the grille's lower assembly rating.
  • Above the wall capacity, washdown or outdoors: sealed box plus a closed-loop heat exchanger or air conditioner sized on the same watts. When the cooler or the heat forces a bigger box, the enclosure selector narrows it by inside height, width and DIN module count.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How much heat does the duct lose by radiation?

Radiation runs about 3.5 W/m²K off bright stainless and 10 W/m²K off an oxidized or painted surface at a 150 °C duct in 40 °C air. On the 0.12 m² example duct that converts to 46 W to 132 W on top of the 330 W of convection, up to 40 % more heat, so include it unless the duct is polished.

Can I measure the heat load instead of guessing h?

Yes. At steady maximum load, measure the airflow through the box and the outlet-to-inlet rise, then Q = 1.2 × 1,005 × V × ΔT. A fan delivering 60 CFM (0.028 m³/s) against a 12 K rise is carrying 1.2 × 1,005 × 0.028 × 12, about 405 W. That measured number replaces the whole h estimate at the next revision.

Why a 10 K rise, and what if I allow 5 K?

Ten kelvin holds the outlet air at 40 °C with a 30 °C inlet, the ambient ceiling for drives and most electronics. Flow scales inversely with the rise you allow: 5 K doubles the example to 176 CFM, and 15 K cuts it to 58 CFM but leaves hot-side devices sitting in 45 °C air. Pick the rise from the device ratings, then let the arithmetic set the fan.

Can I put a fan on a NEMA 4X stainless enclosure?

You can mount one, but the fan and grille set the assembly's rating, and a filter-fan pair is typically rated IP54, well under 4X. Indoors in dry air that trade can make sense; in washdown keep the box sealed and cool it with a closed-loop heat exchanger sized on the same watts. We cut the fan and cooler openings to your drawing, delivered in 10 business days from your approval.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 24 × 20 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job

Keep reading

More on outdoor, heat and moisture

All articles

Buying guides

The guides behind this answer

All guides