Enclosure depth for servo drives that project 190 mm

Add the drive projection, wiring space and door clearance: a drive that projects 190 mm from the mounting plate needs about 380 mm of internal depth, so a 300 mm deep box will not close with the drives wired. Move the duct to the sides or step up to a deeper cabinet.

NEMA4 Enclosure engineering team · Published November 25, 2026 · 5 min read

Short answer: size the internal depth as drive projection plus about 100 mm of wiring space plus 50 mm of door clearance. A servo drive that projects 190 mm from the mounting plate therefore needs roughly 380 mm of internal depth, and a 300 mm deep cabinet will not close over it once the drives are wired. The fix is a deeper box, or a layout that takes the duct off the drive face.

How the depth adds up

The usable depth of an enclosure is the distance from the back wall to the inside of the door, not the outside dimension. Wall and door thickness on a stainless cabinet typically take 15 to 25 mm per side, so a box marked 300 mm deep carries about 270 mm of internal depth. NEMA 250 sets no minimum depth; each manufacturer picks its own dimensions, which is why you size the inside yourself from what goes in it.

Four things stack up between the back wall and the door:

  • Mounting plate standoff, 10 to 20 mm for the plate fixings.
  • Component projection, the datasheet depth of the deepest device, measured from its mounting face.
  • Wiring space, about 100 mm: a 40 x 60 mm wiring duct is 60 mm deep, and you want 40 to 60 mm more for connector plugs and the bend radius of the cables. Shielded motor cable wants a bend radius around 6 to 10 times its diameter, which on a 10 mm OD cable is 60 to 100 mm; a gentle S-bend inside the duct keeps it lower.
  • Door clearance, a free gap in front of the tallest item so connectors can be unplugged and the door seats without pressing on anything.

Worked example: two drives at 190 mm projection

Say you mount two pulse-and-direction servo drives and a small controller on one plate, inside a 500 x 500 x 300 mm cabinet:

Item Depth used
Mounting plate standoff 20 mm
Drive projection 190 mm
Wiring duct on the drive face, 40 x 60 mm 60 mm
Connector plugs and cable bends 40 mm
Door clearance 50 mm
Total needed 360 mm

The box gives you about 270 mm of internal depth, so you are 90 mm short before the door closes, and the straight plug-in control connectors are the first thing the door would crush. Two ways out:

  1. Go deeper. An internal depth near 380 mm, outside roughly 420 to 450 mm, closes the layout with room to spare. Our stainless wall-mount enclosures run up to 16 in (406 mm) deep, and the enclosure size chart lists inside and outside dimensions so you can check the plate area and depth together.
  2. Move the wiring off the drive face. Put the ducts on the sides of the box at the drive level, route the control cables sideways out of the connectors, and use right-angle connectors where the drive allows them. That drops the full wiring stack in front of the drives to maybe 20 mm of plug projection, and 270 mm of internal depth then carries 20 mm standoff plus 190 mm drive plus 30 mm of plugs plus 30 mm of clearance. It fits, but only just: any drive with a deeper front face, a fan shroud or a braking resistor inside the box breaks it.

Option 1 is the one to take unless the cabinet has to reuse an existing cutout or mounting footprint. Extra depth on a new box is cheap; crushed connectors are not.

Steps to size the depth

  1. Read the projection of every device from its datasheet: mounting face to the front of the tallest connector, with the connector plugged. Pick the deepest device; that is your projection number.
  2. Add the plate standoff you plan to use, typically 10 to 20 mm on M4 or M5 fixings.
  3. Add 100 mm for wiring: 60 mm for a 40 x 60 mm duct plus 40 mm for plugs and bends. Take it down to about 60 mm only with right-angle connectors and side routing.
  4. Add the door clearance.
  5. Add 30 to 50 mm for wall and door thickness to get the outside depth, then pick the next catalog size up from that number.
  6. Lay the components out on the plate at the same spacing you plan in the box, and measure the true stack with a straight edge across the front of the connectors. The drawing numbers and the delivered parts differ more often than you expect.

The same stack logic drives width and height, not just depth. The guide to sizing an electrical enclosure works the full box from component list, wire bending space and fill, and the VFD clearance guide gives the top and bottom air space drives want for convection, which a depth-only calculation leaves out.

Mistakes that cost the depth

  • Measuring the drive body and forgetting the connectors. On many compact drives the plug-in control connector adds 25 to 40 mm over the molded case; that alone turns a fitting layout into a fouling one.
  • Standing the drives off the plate to gain depth. Standoffs move the drive forward, so the projection grows by the standoff height and you lose the same millimetres twice. If you need space behind a drive for through-plate wiring, it comes out of the wiring budget in front, not out of nothing.
  • Putting the duct across the drive faces in a shallow box. Route power and signal ducts along the sides instead; the multi-drive layout article shows the arrangement that keeps connector fronts clear.
  • Ignoring plug removal. A connector that needs a straight pull longer than the door gap does not come out with the door closed. Leave the full wiring budget in front of any connector you service regularly, and keep plugs and wiring clearance in mind the way the DIN rail controller clearance article does for rail-mounted devices.

What to put on the order

State the internal depth you calculated, not just the outside size. For the worked layout above, that is 380 mm internal, which you can get from a stock deep wall-mount size or by setting depth yourself in the enclosure builder, where you also place the cutouts so the gland entries land below the drive connectors. Orders go out as manufacturer-rated NEMA 4X / IP66; not UL listed, and are delivered in 10 business days, counted from your approval of the drawing for custom sizes.

Before you cut anything in the field, sit the drives on the plate, plug every connector, and close the door over a straight edge laid across the fronts. If the straight edge clears by 50 mm or more, the depth is right; if it fouls, add the difference to the depth and re-order before the panel is wired.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How much depth do I add behind the drive projection for wiring?

Plan about 100 mm between the tallest component and the door side of the box: a 40 x 60 mm wiring duct plus 40 to 60 mm for connector plugs and cable bends. If the connectors on the drives are right-angle instead of straight, you can take 40 to 60 mm off that figure, down to roughly 60 mm.

Will a 300 mm deep enclosure close over drives that project 190 mm?

No, not with the drives wired. The drives alone reach about 210 mm from the back wall with the mounting plate standoff, and a duct on the drive face adds its full depth, so the door needs at least 270 mm of clear depth before any door clearance. At 300 mm you have about 30 mm left, which is not enough for connectors and cable bends.

Does the door gasket count as door clearance?

No. Allow 50 mm of free space in front of the tallest component before anything touches the door or its gasket. The gasket compresses a few millimetres, and a hinged gasketed door needs that gap to seat evenly along its full length; that 50 mm also gives you room to lift a connector out of its plug without fighting the door.

What depth cabinet should I order for two drives and a controller?

With 190 mm drive projection, expect an internal depth near 380 mm and an outside depth of 420 to 450 mm once you add wall and door thickness, which is typically 15 to 25 mm per side on a stainless cabinet. Our catalog wall-mount line goes to 16 in (406 mm) deep; for any other size, set the depth you need in the enclosure builder.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides