Reserve 6 in [152 mm] of clear space above and below the drive, 2 in [50 mm] at each side, and keep the air around it at or below 40 C (104 F). Those are the working numbers for laying out a backplate. The drive's own manual is the figure that counts, and documented ones run from 3.9 in [100 mm] top and bottom to 7.9 in [200 mm] above a large frame. The vertical gaps matter most, because a VFD breathes through its heatsink fins: cool air in at the bottom, hot air out of the top. Above 40 C the drive derates, and one typical curve drops it to 80% of rated current. This page gives the clearance figures, the mounting steps and the heat arithmetic. The 25 hp worked example assumes 550 W of drive loss; swap in your datasheet's number before you size cooling.
What the manuals ask for above and below
Air through a drive runs vertically. The internal fan pulls enclosure air up through the heatsink fins and pushes it out of the top of the unit, so a choked top gap makes the drive drink its own exhaust. Every drive manual therefore names free space above and below, and one maker states that none is needed at the sides. Three documented sets of figures:
| Drive class | Free above | Free below | Free at the sides |
|---|---|---|---|
| Compact drives, one maker's mounting note | 3.9 in [100 mm] | 3.9 in [100 mm] | none needed |
| Mid-frame drives, one maker's FAQ | 4.7 in [120 mm] | 4.7 in [120 mm] | varies by model |
| Large frames, one maker's mounting instruction | 7.9 in [200 mm] | per the manual | per the manual |
The frame sets the number: the 4.7 in [120 mm] figure comes from a maker that says it varies by model. Until you have the datasheet, lay the plate out to 6 in [152 mm] above and below and 2 in [50 mm] at the sides, then move devices when the manual asks for more. The side gap is wiring room. It keeps the power duct and the shielded motor cable off the case, lets the drive's terminal cover open, and leaves the door room to close over deep connectors. If you are still choosing the box, start from sizing an enclosure for a drive and clearance around the panel's other devices.
Mounting the drive on the backplate
- Fix the drive model before you drill anything. Clearances and heat loss are per frame size, and even the 4.7 in [120 mm] figure shifts between models of one range.
- Mark the footprint with 6 in [152 mm] clear above and below. Measure from the drive's top to the roof, a duct or the device above it, and the same below to the next device.
- Hold 2 in [50 mm] at each side for the power duct, the control duct and the shielded motor cable. The full layout picture is in backplate and DIN rail layout.
- Keep both vertical gaps empty. A horizontal duct, rail or wire bundle crossing above or below the drive cuts the air column the heatsink needs.
- Give the drive the cool end of the plate. The air leaving a braking resistor or a control transformer becomes the drive's intake air.
- Cover the line-side taps off the main disconnect. A finger-safe power distribution block is the standard answer, and one maker documents its blocks as IP20 finger-safe protection under specified conditions. UL 508A calls for that protection on feeder-circuit connections that stay live.
- Put the ground bus within easy reach. Land every ground lug without holding a screwdriver between the incoming feeders. Neutrals go on their own bar; enclosure grounding and bonding lays out the bus work.
- Face the distribution block's taps toward the duct they serve, so each conductor drops straight in instead of looping over the block.
- Remote-mount the detachable keypad on the door or outside the box, with its cable through a gland. You can then program the drive with the cabinet closed and powered.
Worked example: a 25 hp drive 6 in under the roof of a 36 x 30 x 12 in box at 35 C ambient
Inputs, each with its source:
- Drive: 25 hp [18.5 kW], the example case. Its frame's manual figure: 4.7 in [120 mm] free above and below.
- Mounting: the drive's top sits 6 in [152 mm] under the enclosure roof, the gap many first builds end up with.
- Box: 36 x 30 x 12 in [914 x 762 x 305 mm] stainless. Wall heat transfer for stainless: k = 3.7 W/m²K.
- Ambient: 35 C. Drive electronics are rated for 40 C enclosure air unless the datasheet allows more.
- Heat: 550 W at full load, an assumption for this drive class. Replace it with the power-loss figure from your datasheet; finding the watts loss covers the datasheets that stay silent.
The clearance check comes first: 6 in available against 4.7 in required leaves 1.3 in [33 mm] spare. Pass. Had this been the large frame asking 7.9 in [200 mm], the drive would sit 1.9 in too high and move down the plate.
The rule in words: a sealed box sheds its heat through its walls, so the internal rise equals the heat divided by the wall coefficient times the wall area. The arithmetic:
- Wall area A = 2(0.914 × 0.762) + 2(0.914 × 0.305) + 2(0.762 × 0.305) = 1.39 + 0.56 + 0.46 = 2.4 m² [26 ft²].
- Heat path = k × A = 3.7 W/m²K × 2.4 m² = 8.9 W/K.
- Rise = 550 W ÷ 8.9 W/K = 62 K.
- Inside air = 35 C + 62 K = 97 C, against a 40 C drive limit.
Your allowed rise is 40 − 35 = 5 K, so the sealed box carries 8.9 W/K × 5 K = 45 W. The drive alone dissipates 550 W, twelve times over. Doing it passively would take 550 ÷ 5 = 110 W/K of wall, which at 3.7 W/m²K means 30 m² [320 ft²] of stainless. Sealed is out; move the heat with air.
Airflow = heat ÷ (air density × specific heat × allowed rise) = 550 W ÷ (1.2 kg/m³ × 1005 J/kg·K × 5 K) = 0.091 m³/s = 328 m³/h = 193 CFM.
Decision: the mounting passes on clearance and the sealed box fails on heat. Fit about 200 CFM of filtered airflow, switched on at 35 C. Put your own inputs through the enclosure heat calculator before you order hardware.
Cooling it: fan size, thermostat and the box rating
Set the intake low and the exhaust high, on the door or one side wall, so the stream sweeps up past the heatsink. The chimney does the cooling and the fan feeds it. Switch the fans with a thermostat closing at 35 C, the 5 K margin under the derate point. A fan that runs around the clock filters the shop's dust 8,760 h a year, and a thermostat-run fan does the same job for a fraction of that; thermostat control for an enclosure fan sets out the wiring.
Mind the weakest part. A filter-fan assembly carries its own code, commonly IP54, and the cabinet's rating drops to that of the fan. On a washdown enclosure rated NEMA 4X / IP66 by the manufacturer; not UL listed, hold the seal with an air-to-air heat exchanger or an enclosure air conditioner. Fan versus air conditioner versus heat exchanger picks between them.
Derating buys you little here. The 80% curve applies just above 40 C, and this sealed box reaches 97 C, so move the heat out instead of planning around the curve.
Checks once the panel runs
- Load the drive for an hour at full output, then read the heatsink temperature on its display and the enclosure air just above the unit. At your design ambient both stay under 40 C.
- Watch one heat cycle. The fan starts as the box passes 35 C and stops as it cools. A fan that never stops in a 25 C shop points to a wrong setpoint or to exhaust air short-circuiting back into the intake.
- With power off, confirm the finger-safe covers sit home on the line-side taps and the keypad cable seats in its gland. The line side of the main disconnect stays live with everything else off, as why the line side stays live explains, so lock out and prove de-energized before your hand goes in.
Mistakes that cook a drive quietly
- The phantom gap. The drive has 6 in [152 mm] to the roof, then a wire duct runs 2 in above the unit. The working gap is 2 in, and the drive recirculates its own exhaust.
- The missing bottom gap. A drive hard against the bottom rail starves its own intake, which needs the same free column as the outlet.
- Sizing the fan from the box. Airflow comes from the watts: 550 W at a 5 K rise is 193 CFM whatever the cabinet measures.
- Bare feeder taps. The finger-safe covers take minutes to fit and let you open the door on a live panel without exposing the taps.
- The always-on fan. It loads its filter with dust year-round and buys nothing when the box is cool.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 36 × 30 × 12 in | 304 stainless | 36 x 30 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much clearance does a VFD need above and below?
Plan 6 in [152 mm] and treat the drive's manual as the deciding figure: documented instructions ask for 3.9 in [100 mm], 4.7 in [120 mm] or 7.9 in [200 mm] depending on frame. When two drives share a cabinet, hold the same 6 in between them, because each one's intake sits in the other's exhaust path.
Do VFDs need clearance at the sides?
Often none for cooling: one drive maker states outright that no side clearance is needed because the airflow runs vertically through the heatsink. Keep about 2 in [50 mm] anyway, so the power duct and the shielded motor cable stay off the case and the drive's terminal cover opens without unclipping the duct.
What happens to a VFD above 40 C enclosure air?
It derates. One typical curve drops the drive to 80% of rated current once enclosure air passes 40 C (104 F), which turns a 25 hp [18.5 kW] drive into a 20 hp one. Run hotter still and the drive trips on heatsink temperature. Hold the air at or below 40 C, or accept the derate and buy the next frame up.
Should the cabinet fans run all the time?
Run them on a thermostat closing at 35 C, 5 K under the drive's 40 C derate point. A continuously running fan filters the shop's dust about 8,760 h a year; a thermostat-run fan in a two-shift plant runs roughly 4,000 h, so the filter lasts about twice as long.





