Short answer: use a gasketed conduit hub — the trade calls them Myers hubs — rated for Type 4X, drill the knockout size it lists (7/8 in [22.2 mm] for 1/2 in trade size) from the outside with a step bit, and bring the conduit in at the bottom. The hub's O-ring clamps the polycarbonate wall and closes the ring gap that a bare pipe or a locknut leaves open. Keep the drill slow, because polycarbonate softens near 150 C [300 F]. Leave EMT out of genuine 4X duty and run PVC or rigid instead. If you would rather never drill plastic at all, we cut every hole in a stainless box before it ships, delivered in 10 business days.
Which fitting seals conduit into a polycarbonate 4X enclosure?
A gasketed conduit hub — sold across the trade as a Myers-style hub — is the fitting: its flange and O-ring clamp the wall, its makers list it for Types 2, 3, 3R, 4, 4X and 12, and its bonding lug gives you the ground point a plastic box lacks. The hole you drill is deliberately bigger than the conduit — 7/8 in [22.2 mm] for a 1/2 in hub — and the O-ring under the flange closes that ring gap against rain and hose water.
A locknut with a sealing washer attempts the same job with clamp force alone, and on polycarbonate it loses. The plastic creeps under sustained nut pressure, the washer relaxes, and the joint weeps; vibration hurries it along. Washers belong on stiff steel walls, hubs seal on anything, which is why the hub vs sealing locknut comparison for outdoor entries lands on the hub side. Buy the hub with a bonding lug unless your raceway is all PVC.
What size hole do you drill for the hub?
Drill the knockout diameter the hub's listing calls for — 7/8 in [22.2 mm] for 1/2 in trade size, 1-1/8 in [28.6 mm] for 3/4 in and 1-3/8 in [34.9 mm] for 1 in — the standard knockout diameters that UL 50's fitting table (Table 71-1A) sets.
| Hub trade size | Hole to drill | Metric |
|---|---|---|
| 1/2 in | 7/8 in | 22.2 mm |
| 3/4 in | 1-1/8 in | 28.6 mm |
| 1 in | 1-3/8 in | 34.9 mm |
The O-ring buys you forgiveness: it closes an annular gap of about 1/16 in [1.6 mm] to 1/8 in [3.2 mm], so a small miss still seals.
Worked example. You drill for a 1/2 in hub, target 0.875 in, with a step bit that climbs in 1/16 in landings:
- 15/16 in: 0.9375 − 0.875 = 0.0625 in over — inside the O-ring's range, it seals.
- 1 in: 1.000 − 0.875 = 0.125 in over — the edge of the range; fit a fresh O-ring and move on.
- 1-1/8 in: 1.125 − 0.875 = 0.250 in over — twice the range. No 1/2 in hub seals that wall, and the rescue is the next size: a 3/4 in hub lists exactly 1-1/8 in.
Entries of 2 in trade size and up go to a hole saw at the same slow speed, started from the pilot hole.
How do you drill polycarbonate without chipping it?
Start from the outside with a sharp step bit at slow speed — under about 800 rpm — after a 1/4 in [6 mm] pilot: the outside face stays clean where the O-ring seals, and the blowout lands inside where the flange covers it. At speed a bit rubs more than it cuts, and polycarbonate softens near 150 C [300 F], leaving a ridged, half-melted bore that shreds O-rings. Under about 800 rpm — a plastics-shop rule of thumb — the cut comes off as clean curls.
The routine:
- Pilot 1/4 in [6 mm] first; a step bit without a pilot wanders on smooth plastic.
- Step up one landing at a time, lifting often to clear the chips.
- Clamp a wood block behind the wall where you can reach it; the block takes the exit blowout instead of the box.
- Deburr both faces with a countersink turned by hand, or a twist bit about twice the hole size, so no chip ring stands proud.
- Lock out and prove dead any box that is already wired before steel touches it.
Some bonding hubs seat their flange inside the enclosure. If yours is one of them, flip the rule and drill from the inside, so the O-ring's face gets the clean cut. For hole placement to the millimetre, drilling accurately placed holes in a plastic enclosure covers layout and jigs. The low-speed habit transfers to other plastic work too — if a repair ever needs a seal groove, cutting O-ring grooves in polycarbonate with a router shows the tooling.
How do you mount the hub and bring the conduit in?
Seat the flange and its O-ring against the clean drilled face, run the locknut down snug with one firm wrench pull, then thread the conduit in and seal its threads — and put the whole entry in the bottom wall.
- Open the door and, on a wired box, lock out and prove dead.
- Deburr both faces of the hole so no chip ring can cut the O-ring.
- Roll the O-ring into the flange groove and pass the hub through, flange against the face you drilled from.
- Run the locknut finger-tight, then give it one firm pull on a normal wrench. Stop when the O-ring shows an even squashed ring all the way round; heavy-handed wrenching cracks the wall.
- Thread the conduit in: a PVC male adapter with its seal ring seated, or rigid with thread sealant on clean, dry threads.
- Bring the entry in from the bottom. A weeping top hub drips straight onto your terminals; a bottom weep drips onto the floor. The same logic, with floor-standing boxes, runs through bottom conduit entry into a NEMA 4 floor-mounted enclosure.
- Land metallic raceways on the hub's bonding lug — the bonding section below names the conductor and its color.
- Come back after the first week of service and re-snug the locknut. Polycarbonate creeps a little under clamp, and a small catch-up on the wrench is normal, not a leak.
Does a field-drilled hole keep the 4X rating?
Yes — the drilled hole costs you nothing as long as the fitting that fills it carries the rating: a hub listed Type 4X in a box rated 4X keeps the assembly at 4X, because the O-ring does the sealing the removed plastic once did. The assembly now takes the rating of its weakest part, and the candidates are the hub and the thread you just sealed.
NEMA 250 defines Type 4X for indoor and outdoor use under hosedown. Its corrosion test, Table 5-1D, adds another 200 hours of salt spray alongside an AISI type 304 stainless specimen, and the enclosure is judged against that specimen. Ratings are manufacturer ratings: NEMA publishes the standard and does not test or certify enclosures, and our stainless boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. For the broader question, drilling and the enclosure rating covers what a hole changes and what it leaves alone.
What actually costs the rating:
- a hole drilled past the O-ring's 1/8 in [3.2 mm] range
- a top entry with anything less than a gasketed hub
- a dry, unsealed male thread — PVC threads wick water by capillary action
- a chipped or melted seat under the O-ring
- a vent or drain added later for condensation, which drops the assembly to that fitting's rating
The full set of rules for holes made after the box exists is in field-drilled conduit entries that keep a 4X rating. Or skip the drilling: our stainless boxes leave the shop with every hole cut and deburred from new. Lay it out in the cutout designer and it is delivered in 10 business days, counted from your approval of the drawing.
Which conduit material belongs on a 4X box?
For real 4X service run PVC or rigid — galvanized, aluminum or stainless — and keep EMT for indoor rooms, because thin-wall EMT rusts at its cut threads long before a plastic box shows anything. Type 4X has two halves, water and corrosion, and a 4X box fed by a rusting EMT riser satisfies the box's rating and nothing else. EMT with compression fittings is defensible outdoors — set-screw couplings are for dry interiors — but the corrosion half of 4X argues for PVC or rigid where weather or washdown is real. The full trade-off sits in wiring methods into a NEMA 4 enclosure: EMT, PVC or cable.
| Service | Conduit to run | Entry and seal |
|---|---|---|
| Food-plant washdown, daily hoses and sanitizer | Schedule 40/80 PVC or rigid aluminum | bottom hub, EPDM O-ring |
| Outdoor rain and sun | UV-resistant PVC or rigid galvanized | bottom hub, sealed threads |
| Vibration, final drop to a motor | liquid-tight flexible off a hub | sealing rings both ends |
| Indoor dry control room | EMT with compression fittings | any face, hub still easiest |
For the PVC route, connecting Schedule 40 PVC to an outdoor enclosure covers glue, expansion and support, and whether a Myers-style hub seals on PVC conduit answers the thread question directly. If the environment is still choosing the box for you, the enclosure selector sorts candidates by environment and rating.
How do you bond metal conduit to a plastic enclosure?
Bond the metal inside the box: NEC 314.3 allows a nonmetallic enclosure to take metal raceways only where their metal parts are bonded together inside it, and the hub's bonding lug is that point. Run your equipment grounding conductor to that lug or to a ground bus, sized from the rating of the overcurrent device ahead of it per NEC Table 250.122. Insulated grounding conductors of 6 AWG and smaller are green, or green with yellow stripes, under NEC 250.119. Keep neutrals on their own isolated bar — that is the point of NEC 250.6 — and the full treatment is in the grounding and bonding guide. An all-PVC raceway carries no metal to bond; land the grounding conductors on the bus all the same.
What checks prove the entry still seals?
Hose the finished entry the way the test does — about 100 L/min from a 12.5 mm nozzle at roughly 3 m [10 ft] for a few minutes — then open the door and hunt for water at the O-ring, the thread and the locknut side. Those jet figures are the IEC 60529 second-digit 6 test, so a garden hose fully open is a fair everyday stand-in. Work through:
- the O-ring shows an even compressed ring, with no daylight at the annulus
- the flange sits on flat, unchipped wall
- sealant or a seal ring is visible at the thread root
- the interior is dry after the hose test
- the locknut still feels snug a week later
If anything weeps, hunt in this order: an unsealed thread first, a chipped or melted O-ring seat second, an oversize hole third. Each fix is above — re-seal the thread, deburr and fit a fresh O-ring, or step up one hub size.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Will a locknut and sealing washer seal as well as a hub on plastic?
Not for 4X duty. A sealing washer needs an unyielding metal wall under it; polycarbonate creeps under sustained nut pressure, the washer relaxes, and the joint weeps within the first season. A hub's O-ring keeps its squeeze as the wall breathes. Save washers for steel walls and use a hub here.
Can you bring liquid-tight flexible conduit straight into the box?
Yes, through a wet-location-rated liquid-tight connector with its own gasket, or by threading the flexible conduit's male adapter into the hub body. Flexible drops absorb vibration instead of passing it into the box. Put sealing rings at the wall and at the conduit end so the entry stays at the hub's rating.
Which O-ring material handles washdown chemicals?
Nitrile, the standard hub O-ring, runs about -30 to 120 C and is fine with plain water and oils. For hot caustic cleaners and sanitizers, specify EPDM, about -50 to 150 C, the elastomer that tolerates steam and caustic. Silicone reaches about -60 to 200 C but weakens in hot caustic, so EPDM is the washdown pick.
How far from the enclosure edge can you drill?
Rule of thumb: give the hole edge one full hole diameter of flat wall from any edge or corner bend — a 1-1/8 in [28.6 mm] hole wants 1-1/8 in of flat wall all round. That keeps the flange and O-ring off the corner radius, where a curved seat cannot seal. On a small box this rule, not the hub, sets the layout.