Connecting a wiring trough to a panel without losing the rating

Join a wiring trough under an enclosure with a rated hub on the side that faces water. On the sheltered side, a plain locknut-and-nipple joint is enough. A threaded hub into the trough top, then a close nipple with locknuts into the panel bottom, keeps the rating where it matters.

NEMA4 Enclosure engineering team · Published October 29, 2026 · 5 min read

The short answer: put the rated fitting on the side that faces the weather. A plain threaded joint is enough on the side that does not. For a trough mounted under an enclosure, that usually means one gasketed screw-in hub, often called a Myers-type hub, in the top of the trough. The hub's threaded body passes through a close nipple into the bottom of the panel and is secured there with locknuts. One rated fitting does the sealing work. The second joint only has to be mechanically sound and tight.

Why one rated end is enough

Think about where water actually is. Rain hits the outside of the enclosure and the exposed top of the trough. Everything between the trough's top wall and the panel's bottom wall is sheltered: vertical surfaces in the shadow of both boxes, not exposed to hose-directed or wind-driven water. That is why the rain-exposed surface gets the gasketed, rated hub, and the sheltered surface gets locknuts on the same nipple.

Ratings are manufacturer ratings, not UL listed, and they describe the whole box after every opening is made. If you want a deeper look at what a rating survives once you modify the box, see what NEMA rating a panel keeps after you cut it and mount devices. The same logic applies here. Every penetration must be closed with a fitting that restores the level of protection the box was built for.

What you need

  • A gasketed screw-in hub (Myers-type) sized to the nipple, with the gasket intact and the right hole size for its threads.
  • A close nipple of the right length and thread type for the hub and the panel knockout.
  • Two locknuts and, where the joint needs it, a locknut with a bonding or sealing ring per the fitting instructions.
  • A hole saw or punch matched exactly to the hub's required hole size, plus a deburring tool.
  • A torque or firm-tightening reference: the fitting maker's instructions.

If the opening will feed sealed cable instead of a nipple into another box, the sealing rules differ. The guide on how to install a cable gland without losing the rating covers that case.

Steps

  1. Confirm the hole locations. Hold the trough against the panel bottom and mark the trough top so the nipple lands plumb and clear of internal hardware on both sides. Check that the trough top is solid or has a knockout matching the hub; a marked but unpunched footprint tells you where the maker intended a hub to sit.
  2. Cut the trough opening with the hole size the hub specifies, not the nipple size. Deburr both edges. A ragged or oversize hole can keep the gasket from seating and cost the rating.
  3. Insert the hub from inside the trough so the gasket sits flat against the inner wall. Tighten the hub nut evenly until the gasket compresses; do not crush it.
  4. Thread the close nipple into the hub body hand-tight, then wrench it a fraction past hand-tight per standard practice for tapered threads. Do not use pipe dope on the gasketed side unless the hub instructions allow it.
  5. Pass the nipple through the panel knockout and secure it with a locknut on each side of the panel wall. Tighten the locknuts firmly; this joint is mechanical, not weather-sealing, but a loose one lets the assembly work loose and stresses the hub gasket.
  6. Bond the joint as your installation requires. Where the trough and panel are metal and the raceway serves as an equipment grounding path, follow the bonding rules your installation is built to; the guide on enclosure grounding and bonding covers the details.
  7. Support the trough on its own mounting feet or brackets. The nipple and hub are not structural members. A hanging trough will eventually lever the hub and open the gasket.
  8. Close any unused knockouts in both boxes with listed plugs before you call the job done.

Checks when done

  • The hub gasket is evenly compressed, with no twist or pinch visible.
  • The nipple is plumb and the trough hangs square on its own supports.
  • No unused knockout or opening is left open on either box.
  • The trough drains or seals as its rating intends; a rain-rated trough is built to shed or drain the water it takes.

Then run water over the assembly from above with the power off and check inside the trough for drips at the hub gasket. This is a functional check, not a rating test, but it finds a pinched gasket before the first storm does.

Mistakes that cost the rating

  • Rated hubs on both ends but no gasket seating on either: two bad joints instead of one good one.
  • A hole cut oversize and shimmed with tape or sealant. Sealant is not a fitting; see why in the guide to cutouts, glands and HMI windows.
  • Using the nipple to hang or align the trough, which works the hub loose over time.
  • Leaving a knockout open in the trough, which defeats the rating even if the hub joint is perfect.
  • Sideways entry into the trough wall on a rain-rated box. Rain-rated boxes shed water down their sides; a horizontal penetration into a wall can admit it. Keep the entry on the protected top surface or follow the box maker's stated entry zones.

If the layout pushes you toward side entries, conduit bodies or flexible connectors, the article on wiring methods into a NEMA 4 enclosure: EMT, PVC or cable compares the options. The piece on bottom conduit entry into a NEMA 4 floor-mounted enclosure covers the same joint geometry from below.

When to order the opening instead of cutting it

If the trough top is solid, the hole is one clean hub size, and you have a punch or hole saw of that size, cutting it in the field is normal work. Once you need several openings, an oversize cutout for a bolted hub, or entries that must line up with the panel above, order the box with the cutouts factory-made. On a stainless trough or a custom body, a factory-cut opening comes from an approved drawing, the edges are finished, and the rating question is settled by the manufacturer rather than argued in the field. Our custom enclosures are built from one piece to your width, height, depth and cutout layout, delivered in 10 business days from your approval of the drawing.

For the drawing itself, send hole positions with dimensions from a datum, not just "match the panel". The cutout drawing checklist for an enclosure quote lists what a quote needs so the hub footprint lands where the nipple expects it.

What to put on the order

  • The gasketed hub, sized for the nipple and the wall thickness of the trough top.
  • The close nipple, correct length so it spans both walls without bottoming out.
  • Locknuts for the panel side, plus any bonding ring your installation requires.
  • Listed plugs for every unused knockout.
  • If the trough is custom: a drawing showing the hub hole size and position on the top wall, and the stated rating for the finished box.

Keep the rated side honest and the sheltered side tight. That is the whole joint.

Enclosures for this job

Catalog sizes that suit the job this article answers, picked from its subject; open one for its full specifications.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 14 × 8 in304 stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Do both ends of the nipple need a rated hub fitting?

No. Water and wind-driven rain only reach the outside of the enclosure and the top of the trough. A rated hub on the trough top keeps the rating there. The joint between the nipple and the enclosure bottom sits inside the protected envelope of both boxes, so locknuts on a plain nipple are normal practice, unless the manufacturer or the inspector specifies otherwise.

Why can a NEMA 3R trough feed a panel with a lower-rated entry?

NEMA 3R is built for rain, sleet and snow. Its openings face down or are shielded, and water that enters a 3R box is expected to drain. Once the boxes are stacked, the panel bottom and the trough top are both sheltered. The rain-exposed surface is the trough top, and that is the surface the rated hub protects.

Does drilling the trough top myself keep the rating?

Only if the fitting you install restores the rating. A correctly sized hole, deburred, sealed with a rated gasketed hub and tightened per the fitting maker's instructions, can hold it. A loose hole, an oversize punch or a fitting with no gasket will not. If the cut is beyond a simple hub hole, order the opening factory-cut so the drawing and the rating stay consistent.

What if the trough has knockouts instead of a solid top?

If a knockout matches the hub size, remove it cleanly and install the same rated hub. If the knockout size does not match the nipple, use a reducing washer only where the fitting maker allows it. Never leave an unused knockout open or covered only with tape; close unused openings with listed plugs to keep the rating.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides