Cable gland sealing ring or O-ring: which your box needs

Order the flat sealing ring by the gland's thread size, not by the cable. An M20 gland takes a ring of about 24 mm OD and 21 mm ID clamped between gland body and wall; that is the seal that carries the enclosure's rating. The dome-nut O-ring only seals nut to gland body.

NEMA4 Enclosure engineering team · Published November 23, 2026 · 6 min read

Short answer: a cable gland has two different seals, and only one keeps your enclosure's rating. The flat sealing ring clamps between the gland body and the enclosure wall, and you order it by the gland's thread size: about 24 mm outside diameter and 21 mm inside diameter for an M20x1.5 gland. The small O-ring under the dome nut seals the nut to the gland body and nothing else. A box can lose the nut O-ring and stay sealed at the wall; it cannot lose the face ring and stay sealed at all. This follows from how gland entries and cutouts are designed into an enclosure in the first place.

Two seals on one gland

A typical metric domed-nut gland has this stack, outside to inside:

Part What it seals What it needs to fit
Dome nut O-ring Nut to gland body Gland body diameter, per the gland datasheet
Flat sealing ring Gland body to enclosure wall Gland thread size (M20, M25, G1/2...)
Cord seal insert Cable to gland bore Cable outside diameter, per the clamping range

Three fits, three different ordering dimensions. The sealing ring is the one engineers most often miss. It ships loose, gets dropped at install time, and looks like packaging scrap. The cord insert is sized by the cable, the dome O-ring by the gland model, and the face ring by the thread: an M20 gland takes the same ring whether it grips a 6 mm or a 12 mm cable. Matching the cord insert to the cable is its own check, set out in cable gland clamping range: match the seal to the cable.

The flat sealing ring carries the enclosure rating

Under NEMA 250 and IEC 60529, the enclosure's water protection is tested as a complete assembly, and every penetration is part of that assembly. Our enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed. That rating assumes sealed entries built per the gland maker's instructions. A gland rated IP68 by its own maker buys you nothing at the wall if the gland body sits metal-on-metal against the enclosure face. Water wicks along the thread and straight through the hole. The flat ring, compressed by the gland body as it is tightened from inside against its locknut, is what stops that path.

So when the ring is missing, the question is never whether the gland itself is good enough. It is what sits between the gland's landing face and the wall. No engineered part there means no seal there.

Sizing the ring: an M20 worked example

Take the common case: an M20x1.5 brass or stainless gland into a 316L wall with a factory entry hole. A metric M20 gland is specified around a 20.1 to 20.3 mm hole, and the ring dimensions follow the thread:

  • Ring inside diameter: about 21 mm. The M20 thread has a 20 mm major diameter, so a 21 mm bore slips over the thread with 0.5 mm clearance per side.
  • Ring outside diameter: about 24 mm. With the hole at 20.3 mm, that leaves (24 − 20.3) / 2 = 1.85 mm of bearing land on the flat wall on each side of the hole. That land is the sealing face, so the hole must stay below the ring's outside diameter with margin; at 20.3 mm you have it.
  • Ring thickness: 1.5 to 2 mm of NBR or EPDM sheet. At that thickness the gland body compresses the ring evenly over its whole face when the locknut is tightened.

The ordering rule is simple: size the sealing ring by the gland thread, not by the cable. Each metric thread step up (M16, M20, M25, M32) raises the ring's outside diameter by roughly 4 to 6 mm. The ring's bore tracks the thread major diameter and its outside edge tracks that gland's landing face. For the M20 case above, 24 × 21 × 1.5 mm is the ring you order. If the datasheet names a specific ring article for the gland, use that number, because some gland families use a shaped or beveled ring rather than a plain washer. Thread selection itself is covered in M20 cable gland hole size for plastic and aluminum.

Hole diameter matters as much as the ring. The entry hole must sit between the thread's clearance size (about 20.3 mm for M20) and a diameter that leaves the ring bearing land, so keep it under roughly 22 mm. A hole cut to 24 mm or larger leaves the ring nothing to compress against at the center, and the wall seal is gone even with the ring installed. That check belongs on the cutout drawing before the hole is made; the cutout drawing checklist covers what to send.

The dome-nut O-ring: useful, but not the wall seal

The O-ring under the dome nut does a different job. It seals the nut to the gland body so the dome's clamp on the cord seal stays consistent. It also keeps water that has already passed the cable jacket from sitting in the nut threads. Losing it does not open a path from outside the enclosure to inside. The face ring and the cord seal are in that external path; the nut joint is not.

Two practical notes. First, the nut O-ring is sized to the gland body, not to the thread or cable, and gland makers sell it as a separate article; some ship glands without it and note that in the datasheet. Second, its absence shows up as an inconsistent clamp on the cable. The nut torques down hard on metal instead of seating on rubber, so check the cable is still gripped and the cord seal insert is compressed. If the cable is flat or an odd shape, that changes the cord seal story entirely; see sealing flat cable into a waterproof enclosure gland.

What to put on the order

  1. Flat sealing rings, one per gland, sized by thread. For M20: 24 mm OD × 21 mm ID × 1.5 to 2 mm, NBR (oil contact) or EPDM (hot water and steam); silicone spans -60 to 200 C where heat rules, per typical O-ring handbook limits.
  2. The gland maker's named ring article when the datasheet lists one; a shaped ring from the maker beats a generic washer.
  3. Dome-nut O-rings for glands whose datasheet lists them as separate; order by gland model, not thread.
  4. A hole check on the drawing: entry holes sized to the gland's specified clearance (20.1 to 20.3 mm for M20), small enough to leave the ring's bearing land.

The decision

  • Ring missing from the box at install time: the wall has no seal without it. Order the ring by gland thread (24 × 21 × 1.5 mm for M20), fit it, and re-tighten the gland from inside against the locknut before the panel goes into service.
  • O-ring missing from the dome nut: the enclosure keeps its rating at the wall. Replace the O-ring to keep the cable clamp consistent, but the urgent part is the face ring.
  • Unsure which part is which: the flat ring is a washer-shaped sheet that sits on the wall; the O-ring is a round cord that sits in the nut. A round O-ring cannot do the wall job on a flat gland landing. It needs a machined groove to control its squeeze, as set out in O-ring squeeze for a sealed enclosure face: how much compression.
  • Hole already cut too large: a ring cannot seal a hole it overhangs. Move the entry, use the next thread size up with the correct larger ring, or order a plate with the entry positioned correctly through our custom stainless cutouts.

Sealing a box is a chain: cord seal to cable, ring to wall, gasket to door. The weakest link sets the rating, and the cheapest link in the chain is the 24 mm rubber washer you almost threw away. For the entry side of outdoor boxes, see sealing SER cable entering an outdoor junction box.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 14 × 8 in304 stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

What size sealing ring does an M20 cable gland need?

Order by the gland thread, not the cable: about 24 mm outside diameter, 21 mm inside diameter and 1.5 to 2 mm thick for an M20x1.5 gland. The 21 mm bore slides over the 20 mm thread, and the 24 mm edge bears on the flat wall around the 20.3 mm entry hole. The cable range of the gland (say 6 to 12 mm) never changes the ring size.

Does a missing O-ring on the gland nut break the enclosure rating?

No. The dome nut O-ring seals the nut to the gland body, a joint inside the cable-entry stack that carries no water head from outside. The wall seal is the flat sealing ring under the gland body. Replace the nut O-ring for a consistent cable clamp, but the box keeps its rating without it as long as the face ring is in place and compressed.

Can I use an O-ring instead of the flat sealing ring on the wall?

Not on a flat wall. A flat sealing ring compresses over its whole face on a flat surface with a 20.3 mm hole. An O-ring needs a machined groove of the right depth and width to control its squeeze; see O-ring squeeze for a sealed enclosure face. On a flat gland landing, NBR or EPDM sheet 1.5 to 2 mm thick is the part that works.

Do the sealing ring material and the cable gland rating have to match?

Pick the ring elastomer for the environment and match the gland's rating: NBR for oil contact, EPDM for hot water and steam, silicone from -60 to 200 C where heat rules, per typical O-ring handbook limits. A gland rated IP68 by its maker still depends on the ring at the wall; an IP68 gland on a plain unsealed hole gives an unsealed hole.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece