Put every cable and antenna entry on the bottom wall of the enclosure and leave the top face solid. A top hole is the one placement mistake that leaks all by itself: rain ponds on that face for hours, the gland's elastomer seal slowly hardens in the sun, and gravity then walks the water onto your board. When the mount blocks the bottom, use the lower 2 in [50 mm] of a side wall and hang a drip loop below every entry. Antenna coax needs one extra rule, because the cable itself can carry water in. Ratings first: these enclosures are rated NEMA 4X / IP66 by the manufacturer and are not UL listed, and the assembly keeps that rating while every part fitted through a hole carries an equal one.
Which face gets the holes
Gravity decides placement, so put it on your side. Water stands on a top face until it evaporates, and a tired seal under standing water weeps inward; the same tired seal on a bottom face has to lift water before it can leak. Over the years an outdoor box serves, every elastomer hardens, so place the aging seal where gravity holds the water off it.
| Face | Verdict | Why |
|---|---|---|
| Top | leave it solid | rain ponds on it, and a weeping seal drips onto the electronics |
| Door | leave it solid | the cable flexes at the gland every time the door swings |
| Back | reserved | it carries the wall-mount feet or the pole bracket |
| Sides above the low strip | spare them | a weep lands on hardware mounted below the hole |
| Lower 2 in [50 mm] of a side | second choice | the hole sits below every terminal, so a weep lands on the bottom wall |
| Bottom | first choice | water must climb to reach the seal, and any weep falls clear |
For how the gland itself grips the cable — seal range, nut torque, locknut inside or out — read sealing an outdoor junction box with glands, drip loops and drains.
Why antenna coax needs its own rules
An antenna lead fails differently from a power cable. Water that reaches a badly sealed antenna end travels inside the coax, along the braid and the dielectric, and a cheap antenna becomes a small plumbing line feeding your modem. Three habits close that path:
- Mount both antennas above the box, run the coax down the pole, and form a loop whose lowest point sits below the gland before the cable turns up into it. Water on the jacket falls off the loop.
- Buy antennas with factory-molded, sealed cable ends, and wrap any field-made joint in two half-lapped layers of self-amalgamating tape.
- Terminate connectors inside the enclosure where they stay dry. A bulkhead RF connector through the wall is workable when its O-ring seats in a clean, flat hole; the antenna feedthrough seal for outdoor cable entries covers that route.
Respect the bend radius while you form the loops: braided coax holds to about 10 cable diameters, so 5 mm [0.2 in] RG-58-class cable turns no tighter than 2 in [50 mm]. Fit a coax surge arrestor at the entry and bond its body to the enclosure ground with a short strap; the enclosure grounding and bonding guide shows the terminal and the strap. For the wider problem of water travelling inside conductors, see stopping water wicking through cable strands.
What you need on the bench
- One gland per cable, sized so the cable OD sits inside the clamping range. Typical nylon glands clamp M12 over 3–6.5 mm [0.12–0.26 in], M16 over 4.5–10 mm [0.18–0.39 in] and M20 over 6–13 mm [0.24–0.51 in]; the gland's datasheet range wins. The cable gland clamping range guide walks the match.
- A blanking dome rated IP68 by its maker, for the spare position every row deserves.
- Self-amalgamating tape for outdoor coax joints.
- Clips or standoffs to hold each drip loop in shape, off the wall so water cannot track behind the cable.
- A coax arrestor and its ground strap.
Two cables through one gland works only in the narrow case the two-cables-one-gland article sets out, so plan one hole per cable unless your pair matches it.
Place the cutouts, step by step
- Fix the orientation first. Decide the mounting face, the hinge side and the door swing, then mark the top of the box as mounted. That face carries zero holes.
- List every entry with its cable OD, and choose each gland so the OD sits near the middle of its range. A seal working at its limit gives up first on a weathered jacket.
- Rule the bottom wall. Keep every hole edge at least 3/4 in [19 mm] from the enclosure edges and 1 in [25 mm] from the next hole, so each seal nut turns without fouling the corner radius or its neighbour.
- Take hole sizes from the gland data. Metric glands seat in the thread plus 0.5 mm: 12.5 mm [0.49 in] for M12, 16.5 mm [0.65 in] for M16, 20.5 mm [0.81 in] for M20. Trade-size conduit fittings follow the knockout diameter table UL 50 prints as Table 71-1A; the enclosure cutouts, glands and HMI windows guide carries the full set.
- Lay it out in the cutout designer. It places holes on any face, checks spacing and exports the drawing. A fully custom body starts from your own drawing; the custom stainless enclosures page lists what to send.
- Order the holes factory-cut. Punched holes keep the wall flat and the gland centred, and the box is delivered in 10 business days from your order; custom work counts from your approval of the drawing.
- Form the drip loops outside. The lowest point of each loop sits 4 in [100 mm] below its gland, and the clip holds it off the wall.
- Dress the inside for drips. Keep the lowest terminal 2 in [50 mm] above the bottom wall, land field wiring on spring or lever terminals (screw terminals walk loose with day-night cycling), and leave slack at every gland tail.
Worked example: a five-entry solar node
Picture a solar-powered irrigation node: a 4G antenna, a GPS antenna, a 20 W panel lead, three soil probes and one valve. Combine the three probes and the valve into one 6-conductor cable of 9 mm [0.35 in] OD, and the hole count drops to four plus a spare. Order both antennas on 5 mm [0.2 in] RG-58-class coax; the 2.8 mm [0.11 in] RG174 lead falls below a typical M12 gland's 3 mm [0.12 in] floor, so the seal never grips it.
| Entry | Cable | OD | Gland (range) | Hole |
|---|---|---|---|---|
| 4G antenna | RG-58-class coax | 5 mm [0.2 in] | M12 (3–6.5 mm) | 12.5 mm |
| GPS antenna | RG-58-class coax | 5 mm [0.2 in] | M12 (3–6.5 mm) | 12.5 mm |
| Solar panel | 2-core 16 AWG | 7 mm [0.28 in] | M16 (4.5–10 mm) | 16.5 mm |
| Probes + valve | 6-conductor | 9 mm [0.35 in] | M20 (6–13 mm) | 20.5 mm |
| Spare | blanked | — | M12, IP68 dome | 12.5 mm |
Now the arithmetic. Holes: 12.5 + 12.5 + 16.5 + 20.5 + 12.5 = 74.5 mm [2.93 in]. Gaps: four at 25 mm [1 in] = 100 mm [3.94 in]. Row total: 174.5 mm [6.87 in]. The 12 x 10 x 6 in 316L wall-mount enclosure gives a 10 x 6 in [254 x 152 mm] bottom face: 254 − 174.5 = 79.5 mm, so 39.75 mm [1.6 in] each end, well over the 19 mm [0.75 in] minimum. The same row on the 10 x 8 x 6 in 316L box leaves (203 − 174.5) / 2 = 14.25 mm [0.56 in] per end, under the minimum, so split that row in two or take the wider box. Decision: the 12 x 10 x 6, one row, spare blanked.
Inside, the mounting panel keeps its lowest terminal 2 in [50 mm] above the bottom wall, which leaves 252 mm [9.9 in] of the 11.91 in [302 mm] interior for rail. Material: 316L where fertilizer dust and wash spray reach the box; 304 holds on a plain field post. The stainless wall-mount range runs from 6 x 4 x 4 in [152 x 102 x 102 mm] up to 60 x 36 x 16 in, so a sixth entry fits a catalog size rather than a custom body. If lithium cells ride inside, keep the pack inside its own instructions' temperature window; 0–45 °C [32–113 °F] charging is the common datasheet limit for lithium-ion, and full sun on a sealed box passes it sooner than you expect. When that heat pushes you toward a vent, vent choices for an outdoor solar node is the rating decision to read first.
Checks when the box is up
- Before first power, hose the finished entries for 3 min from a handheld nozzle and dry-check with paper towel inside. The lab jet test behind IP66 is heavier — IEC 60529 sprays a 12.5 mm nozzle at 100 L/min [26 gal/min] from 2.5–3 m [8.2–9.8 ft] for at least 3 min — so your hose pass says the glands seat and nothing more.
- Pull each cable by hand: the seal grips the jacket with no movement, and a coax nut stops a quarter turn past grip so the braid keeps its round section.
- Sight along each coax: the loop's lowest point still sits below its gland where you clipped it, with bends no tighter than 2 in [50 mm].
- Photograph the as-built holes against the approved drawing and file it with the site paperwork.
Mistakes that cost the rating
- A top or door entry. Gravity and door swing load the seal, and the top face ponds after every rain.
- A field-drilled, oversize hole. An oval hole lets the seal walk; factory punching keeps the wall flat and the gland centred.
- An open spare hole. Fit the IP68 dome on day one — the assembly carries the lowest rating among its parts.
- A drilled weep hole. It opens a sealed box to air, dust and splash; condensation is a heat-and-venting question, and sealed box or vent: which stays dry outdoors works it through.
- An overtightened coax gland. A crushed braid detunes the antenna and shows up as lost signal margin before it ever drips.
Enclosures in this article
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 316L stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 10 × 8 × 6 in | 316L stainless | 10 x 8 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I put a gland in the side of the enclosure instead of the bottom?
Yes, when the hole sits in the lower 2 in [50 mm] of the side and the cable leaves in a drip loop whose lowest point hangs well below the hole. Water on the jacket then falls off the loop, and any weep at the gland runs down the inside wall below your terminals instead of across them.
Do I need a drip loop with a bottom entry too?
Only for cables that arrive from above: the solar panel lead and both antenna coax runs. Drop each loop so its lowest point sits the same 4 in [100 mm] below the gland that the layout step sets. A cable rising straight from the ground already makes water climb, so it can go straight in.
Should I drill a small weep hole in the box for condensation?
Skip it. NEC 314.15 allows 3 mm to 6 mm [1/8 to 1/4 in] drain openings only in boxes listed for damp or wet locations with drains. A drilled weep in a sealed 4X box just opens it to air, dust and splash; manage condensation with heat, a larger box, or a breather rated IP66 by its maker.
How close together can gland holes be?
Keep 1 in [25 mm] between hole edges and 3/4 in [19 mm] from any enclosure edge, so every seal nut turns without fouling its neighbour or the corner radius. Five holes including a spare fit one row on a 10 in [254 mm] bottom face with about 1.6 in [40 mm] to spare at each end.