Braking resistor duty cycle not in the catalog: interpolate it

Keep the ohms the chopper threshold sets — R = 760²/7500 ≈ 77 Ω, so order 75 Ω for a 7.5 kW peak — and scale the watts with duty: at 50% the continuous rating must cover half the peak, 3750 W. Hand that average heat to a housing outside the sealed panel; a 20 × 16 × 8 in stainless box sheds only about 43 W for a 15 K rise.

NEMA4 Enclosure engineering team · Published November 15, 2026 · 8 min read

The table is not wrong; it stops short of your job. Keep the resistance the chopper threshold sets and scale the watts with the duty: for a 7.5 kW peak against a 760 V DC threshold, R = 760² / 7500 ≈ 77 Ω, so you order 75 Ω, and at 50% duty the continuous rating must cover half the peak — 3750 W in the worst case. That average heat leaves through a housing outside the sealed panel, because a 20 × 16 × 8 in stainless box sheds only about 43 W for a 15 K rise. Below is the arithmetic on a real table row, the commissioning checks, and the point where interpolation stops and a regenerative front end starts.

What the table gives you

A resistor table is arranged by supply voltage class and drive rating, and each row carries four numbers: resistance, continuous watts, short-time peak watts, and the duty the row was rated at, with a maximum pulse length in the footnote. Read the footnote before any interpolation, because duty is on-time, and the on-time is defined per window.

One published table rates its parts for five decelerations of 10 s each inside a 120 s window — 50 s of braking, about 42% on-time. Your 50% might be 10 s on in a 20 s cycle, or 30 s on in 60; write your own pair down before you touch the rows.

An illustrative pair of rows for one 400 V frame (take yours from the maker's instruction sheet):

Tabled duty Resistance Continuous rating Peak, 10 s pulses
5% 75 Ω 375 W 7.5 kW
10% 75 Ω 750 W 7.5 kW

Both rows sit on one straight line through the origin — continuous watts = 7500 × duty — and that line is the whole interpolation. The ohms column holds still while the duty moves; what an ohms-and-watts brake resistor spec means is covered on its own page.

The ohms come from the chopper threshold

The chopper is a switch across the DC link. Above its threshold it connects your resistor, which burns the regenerated energy and holds the link down; below it the resistor sits idle. One drive maker's support documentation puts that threshold at least 50-70 V above the highest DC-link voltage the drive will ever see. On a 400 V supply the link idles near 540-566 V, and choppers in that class switch in around 760 V — call that the number here, and read the exact figure from the brake parameter list of the drive in front of you.

Resistance then follows from the peak power the resistor must swallow:

R = V_threshold² / P_peak

At 760 V and 7.5 kW: R = 577,600 / 7500 = 77 Ω, so you order the standard value just below, 75 Ω. Two fences bound that choice. Stay at or above the drive's minimum resistance for its rating — say 50 Ω for this frame — which caps chopper current at 760 / 75 = 10.1 A. Stay low enough that the resistor can clamp the link at P_peak; too many ohms and the link keeps climbing until the drive trips on overvoltage. The minimum resistance rule for a small drive is worth a read before you reuse a resistor from a smaller unit.

The watts come from the duty

Duty is braking time over cycle time, t_brake / t_cycle, and two energies set the watts. A load that overhauls at constant speed — a downhill belt, an unwinder, a hoist lowering — feeds the resistor a rectangle: E = P_peak × t_brake. A ramp stop at constant braking torque feeds a triangle, because power falls from P_peak to zero with the speed: E = ½ × P_peak × t_brake.

Everything thermal comes from the average over the cycle:

P_avg = E / t_cycle

At 50% duty the rectangle gives 0.5 × P_peak and the ramp stop a quarter of it. The peak rating carries its own condition: it holds for pulses up to the length shown in the tabled column heading. Carrying a tabled part to a longer pulse works only while the pulse stays short against the resistor's thermal time constant, which lives in its datasheet. When the load regenerates through most of every cycle, sizing the brake from the load's duty and a hoist brake sized from energy, not motor kW both push you toward a regenerative front end before any resistor.

Worked example: 7.5 kW at 50% duty

Example inputs — replace every one with yours:

  • 400 V, 7.5 kW four-pole drive, 1450 rpm at rated speed
  • Load overhauls at rated speed, 100% braking torque, 10 s on in a 20 s cycle
  • Chopper threshold from the drive's brake parameters: 760 V
  • Minimum resistance for the drive rating: 50 Ω

Peak power. Rated torque is 9550 × 7.5 / 1450 = 49.4 N·m. At 1450 rpm the braking power is 49.4 × 2π × 1450 / 60 = 7.5 kW. That is P_peak.

Resistance. R = 760² / 7500 = 77 Ω, so order 75 Ω — above the 50 Ω minimum, chopper current 10.1 A.

Energy and average. The rectangle carries 7500 W × 10 s = 75 kJ per event, so P_avg = 75,000 J / 20 s = 3750 W. The same event as a plain ramp stop would carry half of that, 37.5 kJ and 1875 W; order for the profile the machine actually runs.

The interpolation. Continuous watts = 7500 × duty gives 375 W at 5%, 750 W at 10%, and 3750 W at 50%. Your duty needs five times the biggest continuous rating in the table, so this row set has no part for you at 75 Ω. The choice moves to the maker's higher-duty family, a bank of tabled parts at the same ohms, or a regenerative front end — while the ohms never moved.

Where the resistor lives: free air or the box

Resistor watt ratings are free-air ratings. Inside a sealed box, the box must shed every average watt, and stainless sheds about k = 3.7 W/m²K of surface. A 20 × 16 × 8 in box carries roughly 0.78 m², so it rejects 3.7 × 0.78 × 15 ≈ 43 W for a 15 K rise. Your 3750 W would ask for 3750 / (3.7 × 15) = 68 m² — a sealed cube 3.4 m on a side. The decision makes itself: the resistor goes outside in its own housing, and only the drive's own losses stay in the panel — about 3% of rating, near 225 W here, wanting about 4 m² of stainless for the same 15 K rise. Hand the panel number to the enclosure heat calculator and it sizes the box or the cooler in one pass.

The housing around the resistor is a design problem of its own — weather outside, 3750 W inside — and outdoor brake resistor enclosures and a box on top of the machine cabinet cover both layouts. A sealed stainless housing rated NEMA 4X / IP66 by the manufacturer, not UL listed, keeps the rain off while the heat leaves through a path built for it; custom enclosures cut to your layout run from one piece and are delivered in 10 business days, counted from your approval of the drawing. Inside the panel, how to size an electrical enclosure and mounting a braking resistor in a drive enclosure carry the fundamentals, and braking resistor overload from a hot panel shows how a cooked install reads.

One safety note: braking resistor surfaces are built to run hot, with datasheet maxima commonly in the 200-350 °C class. Guard the housing, keep cable ducts and combustibles clear of it, and lock out and prove dead before you touch the wiring.

The interpolation, step by step

  1. Write the profile: t_brake, t_cycle, stops per hour, and the worst event — overhauling at speed or a ramp stop.
  2. Compute P_peak at the worst instant from torque and speed, or from inertia; sizing a brake resistor for duty walks that calculation.
  3. Read the chopper threshold from the drive's brake parameters and set R = V² / P_peak, rounding down to a standard value that clears the drive minimum.
  4. Compute E for the worst event, then P_avg = E / t_cycle.
  5. Open the maker's table row for your drive rating and voltage: resistance, continuous watts, peak watts, and the duty footnote with its pulse length.
  6. Test each candidate part on two numbers: continuous rating at or above P_avg, and peak plus pulse length at or above your event. Between tabled duties, read continuous watts off the line watts = P_peak × duty, same ohms, and take the next size up.
  7. When your duty sits above the highest tabled row — 50% usually does — stop interpolating: move to the higher-duty family, a series-parallel bank at the same ohms, or a regenerative front end.
  8. Enable the brake function in the drive parameters at the duty that matches the part, land the wires on the brake terminals, and wire the resistor's thermal switch into the protection input when it has one.

Checks once the brake runs

  • Trace the DC link through the worst stop: it should plateau at the threshold — about 760 V in this example — and stay under the overvoltage trip.
  • Run the full profile until temperatures stop rising, then read the housing: below the datasheet maximum, thermal switch untripped.
  • Measure the resistor cold, before and after: within tolerance of the nameplate, commonly ±10%.
  • After several hours of the real cycle, check the drive for heatsink and chopper overtemperature messages; there should be none.

Mistakes that cook a 50% brake

  • Sizing on peak watts alone: the 5%-duty part holds the link at the full 7.5 kW peak and cooks at one tenth of the continuous watts you need.
  • Applying the tabled peak to a longer pulse than the footnote allows.
  • Leaving the brake function disabled in the drive parameters: the chopper never fires, and the drive trips on overvoltage with the resistor wired perfectly.
  • Mounting the average watts inside the sealed box — 43 W per 15 K against 3750 W.
  • Stretching the ramp to save watts: the same energy leaves the motor every stop, so P_avg = E / t_cycle holds, and only the peak and the ohms change.
  • Running continuous regeneration through a resistor: an unwinder or a lowering hoist that regenerates most of every cycle belongs on a regenerative front end.

When interpolation stops

Your situation What to order
Duty between tabled rows Same ohms; continuous watts from the duty line; next size up
Duty above the table, 50% typical Higher-duty family or a bank at the same ohms; a regenerative front end as the average climbs toward the drive rating
Regeneration through most of the cycle Regenerative front end; the resistor only trims the stops
Duty at or below the tabled rows The tabled part whose continuous rating covers P_avg

At 50% duty the ohms are an ordinary lookup and the watts are a kilowatt-class purchase: half the peak in the worst case, a quarter for a pure ramp stop. Interpolate the table to that number, keep the pulse inside the tabled length, and put the average heat in a housing built to shed it. Where the maker's table ends, the next duty family or a bank answers; where the average watts climb toward the drive's rating, the answer is a regenerative front end instead of a bigger resistor.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can I run the 5% duty resistor at 50% duty when the ohms match?

The ohms are fine and the watts are the problem. Continuous watts scale with duty, so 50% duty needs ten times the continuous rating of the 5% part — 3750 W against 375 W in the worked example. A resistor short on watts still holds the DC link down perfectly and cooks itself within hours.

How do resistor makers define duty in their tables?

By on-time, with the numbers in the footnote. One published table uses five decelerations of equal length inside a 120 s window: 50 s of braking, about 42% on-time. Interpolate against that definition rather than the bare percentage, and keep your braking pulse inside the stated length.

Does a longer deceleration ramp reduce the resistor heat?

It lowers the peak, not the average. The same energy leaves the motor every stop, so P_avg = E / t_cycle is unchanged: 75 kJ per stop at one stop per 20 s is 3750 W whether the brake pulse is short or spreads across the cycle. The ramp changes the peak and therefore the ohms, not the watts the housing must shed.

Can I parallel two catalog resistors to reach the continuous watts?

Yes, when the combined resistance clears the drive minimum. Two identical 150 Ω parts in parallel give 75 Ω and share the heat; two 75 Ω parts give 37.5 Ω, which sits under a 50 Ω minimum and overloads the chopper. In series the resistance doubles and may climb too high to clamp the link at your peak power.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 20 × 16 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job

Keep reading

More on outdoor, heat and moisture

All articles

Buying guides

The guides behind this answer

All guides