Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

ANSI device 69: permissive switch in breaker control panels

ANSI device 69 is a permissive control device: generally a two-position, manually operated switch; one position permits a breaker to close or equipment to run, the other blocks it. On a breaker with pull-to-trip, the 69 contact holds the close circuit open until you reset it by hand, so a no-close fault after a manual trip points at 69 first and at the close coil only after 69 checks out.

NEMA4 Enclosure engineering team · Published November 13, 2026 · 8 min read

Short answer: ANSI device 69 is a permissive control device, generally a two-position, manually operated switch. One position lets a circuit breaker close or equipment run; the other blocks it. On oil circuit breakers with a pull-to-trip lever, the 69 contact opens the close circuit the moment the lever trips the breaker. It stays open until you reset it by hand. When a breaker trips on the lever and then refuses a close command, the 69 contact is the first suspect and the close coil is the last. The rest of this page gives the C37.2 definition and the two jobs a 69 holds in practice. Then it works the meter check that finds the open contact in a 125 V DC close circuit, and ends with what to label and order for the panel.

What C37.2 gives device 69

IEEE C37.2 assigns function numbers to protection and control devices, so a drawing full of relays reads the same way in every plant. On that list, 52 is the circuit breaker and 69 is the permissive control device. The auxiliary contacts matter later: 52a is closed when the breaker is closed, 52b closed when it is open. The standard defines 69 as a generally two-position, manually operated device. In one position it permits a circuit breaker to close or equipment to be placed in operation; in the other it prevents operation. The 2022 edition of C37.2 added numbers for newer functions such as arc-flash detection and dynamic disturbance recording. Device 69 keeps its long-standing meaning.

The number names a job, not a part. Two panels can both show 69 with different hardware behind it, so the schematic and the device nameplate tell you what you are standing in front of. The job is worth naming precisely. An auto-reclose control puts its breaker back in by program after a fault; a 69 is the opposite instrument, a gate that holds the close path open until a person clears it.

The two jobs a 69 holds in practice

Two arrangements cover nearly every 69 you will meet.

Arrangement Where you meet it What it is How it clears
Pull-to-trip reset switch Oil and medium-voltage breakers with an emergency trip lever A switch actuated by the trip lever itself Reset the lever by hand
Local/Remote selector Panels taking close commands from SCADA or a remote desk A two-position selector in the close command leg Turn the selector to the wanted position
Both in one lineup Larger switchgear with a trip lever and remote close The selector and the trip-lever switch, wired in series Clear each in turn

The first is the classic oil-circuit-breaker case. The switch that opens the close circuit is the 69, actuated by the pull-to-trip or emergency trip lever, and it must be reset manually before the next close. The second is why the number is so often described as a Local/Remote selector. Both do the same work: the close path stays open until a person at the panel puts it back.

How pull-to-trip blocks the close

Operating the manual trip lever does two things at once. It trips the breaker mechanically through the trip latch, and it moves a linked contact that opens the closing circuit. From that moment, every close command arrives at an open series path and does nothing, whether it comes from a pushbutton, a control switch or a remote output. The breaker is not broken; it is held open on purpose until a person resets the lever. Reset by the method the maker marks on the breaker or its diagram, usually returning the lever to its set position. With the 69 contact back in its close-permitting state, the close path is complete again, the rest of the chain allowing.

Three symptoms account for most of the confusion:

  • Manual trip worked, close command dead. The 69 is still in its block position: reset it before anything else.
  • Close works only with the selector in one position. The 69 is wired as the Local/Remote permissive; that is by design, not a fault.
  • Reset done or selector in Remote, close still dead. Another contact in the chain is open: measure it, next section.

Finding the open contact in a 125 V DC close circuit

One meter walk settles a no-close trip. Here is the case with the numbers.

The inputs:

  • Control bus: 125 V DC, the standard utility control battery voltage. Buses at 48 V DC and 250 V DC also exist, and the method is identical.
  • Meter: a handheld DMM with a 10 MΩ input, the usual figure for this class of meter.
  • Close coil: 100 Ω assumed for the arithmetic, an illustrative value. Real close coils run from tens to a few hundred ohms, and the answer barely moves.
  • Breaker state: tripped on the pull-to-trip lever, so the breaker is open, the 52b contact is closed and the 69 contact is open, with every other contact healthy.
  • Command: close pushbutton held pressed. With the 69 open this puts no current anywhere in the chain, so holding it is safe; the meter is the only load.

The rule: with one contact open, no current flows anywhere in the chain, so every closed contact and the coil sit at about 0 V across themselves. The one open contact carries the full bus voltage, because the meter is the only path around it and its 10 MΩ dwarfs the coil's ohms.

The arithmetic:

  • Across the open 69 contact: 125 V × 10,000,000 Ω / (10,000,000 Ω + 100 Ω) = 124.999 V
  • The same reading with a 1,000 Ω coil: 125 V × 10,000,000 / 10,001,000 = 124.99 V
  • Both readings land within 0.02 V of the bus, a 0.01 % difference, so the coil value does not matter.

The threshold: a contact that should be closed and reads over 95 % of the bus is the open link. That is over 119 V on a 125 V bus, or over 46 V on a 48 V bus. A contact that should be closed and reads under 1 V is genuinely closed.

The result in this case: the meter across the 69 contact reads 124.999 V. The 69 is the open link, and it is holding the breaker out exactly as the lever left it.

The decisions from here:

  • Reset the lever by the marked method and re-measure. The 69 should read under 1 V, and a close command should then put about 125 V across the coil, which closes the breaker.
  • A reset 69 that still reads over 119 V is a stuck contact or a bent linkage. Repair it before another close attempt.
  • A 69 that reads under 1 V with the close still failing means the open link sits elsewhere. Keep the command held, keep your meter on the chain, and measure each remaining contact the same way.
  • If every contact reads about 0 V, two opens sit in the chain and the across-contact test finds neither. Chase nodes instead: measure each terminal to the negative control bus, and the open element lies between the last node reading over 95 % of the bus and the first reading under 5 %. On a 125 V bus that is over 119 V against under 6 V; on 48 V DC, over 46 V against under 3 V.

Walking the rest of the close chain

On a DC control scheme the close path runs in the usual order: the close command contact, the 69 permissive, the anti-pump and closing-relay contacts, the 52b auxiliary contact, and the close coil. Each contact carries only that circuit's current, and a close coil draws amps rather than milliamps. The command-side contacts and any interposing relay therefore need a rating for the coil current, not just for a signal. When the wiring and the drawing disagree, a wire landed where no drawing shows one, correct the paperwork first and then retest.

The chain hides which link opened. The meter method in the previous section answers it one contact at a time, the same way first-out fault indication in a series e-stop chain singles out the first open contact. If this chain is one you are wiring yourself for the first time, the first control panel build layout and wiring tips keep the drawing, the wire and the terminals in step. For the trip side and the close side together, a breaker trip and close circuit wiring guide walks the same chain contact by contact.

What to put on the panel for a 69

Specify the permissive the way you would any device an operator depends on.

  • Mark the number everywhere. The device tag, both wire ends and the terminal strip each carry 69, so the schematic and the cabinet read the same.
  • Give each 69 pole its own terminal pair, counted the way counting terminal blocks by points, not blocks works through the rest of the panel.
  • Keep the close-chain devices on one row of the backplate with the terminal strip below, the arrangement the backplate and DIN rail layout guide shows.
  • Adding a Local/Remote selector or a reset pushbutton to an existing outdoor cabinet means a door cutout and a bezel. The devices behind the cutout decide what the enclosure keeps; see what NEMA rating a panel keeps after you cut it and mount devices.
  • The hole, the seal and the device depth behind a selector are covered in the cutouts, glands and HMI windows guide.
  • Enclosures from us are rated NEMA 4X / IP66 by the manufacturer; they are not UL listed. On a UL 508A control panel, NEC 409.110 requires the enclosure type number on the panel marking, so state the type where the inspector looks.

The decision, case by case

Case First stop The answer
Tripped on the lever, close command dead Meter across the 69 contact A reading at the bus voltage means the permissive is set; reset the lever by the marked method, then close
69 reset, still a bus-voltage reading across it Linkage and switch Stuck contact or bent linkage; repair before another close
69 reads under 1 V, close still dead Next contact in the chain Walk command contact, anti-pump, closing relay, 52b and coil with the same meter method
Close works in one selector position only The drawing The 69 is the Local/Remote permissive; the panel works as drawn
Wiring and drawing disagree The paperwork Correct the drawing first, then retest the chain

Read 69 as a function, and let the trip lever's contact be your first stop after any manual trip. Let the meter, not a parts swap, point at the open link. That is the discipline of the permissive: the breaker stays held out until a person at the panel decides otherwise.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
12 × 10 × 6 in304 stainless12 x 10 x 6 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Does device 69 trip the breaker?

No. 69 is a permissive: it permits or blocks a close, it does not trip. On a pull-to-trip breaker the same lever does two jobs: it trips the breaker mechanically and, through its linked 69 contact, opens the close circuit until you reset it. The trip coil and the protective relays do the tripping in every other scheme.

Is a 69 always a Local/Remote selector?

Often, not always. C37.2 makes it a two-position permissive, and Local/Remote selection is the most common form in control panels. On older oil breakers the 69 is instead the switch actuated by the manual trip lever, reset by hand before the next close. The number names the job; the schematic names the hardware.

What voltage reads across an open 69 contact?

Essentially the full control bus. Hold the close command with one contact open: no current flows, so closed contacts and the coil read about 0 V and the single open contact reads the bus, about 125 V DC on the standard utility battery or about 48 V DC on a 48 V bus. A 10 MΩ meter barely loads the reading.

Can you jumper a 69 contact to get the breaker closed?

Electrically it would complete the close path, and you must not: the 69 contact is the inhibit that holds a manually tripped breaker out of service until someone resets it in person. Jumpering also hides a genuinely stuck contact or a bent linkage. Find why the contact is open and fix that instead.

What else sits in series in a breaker close circuit?

Besides the 69, the close path usually holds the close command contact, the anti-pump and closing-relay contacts, the 52b auxiliary contact and the close coil, each in series; any single open contact stops the close. Because a close coil draws amps rather than milliamps, the command-side contacts and any interposing relay need a rating for the coil current, not just the signal.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 12 × 10 × 6 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides