Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

480 to 120 V, 1.5 kVA transformer in a NEMA 3R box

Build the box from parts: a 1.5 kVA dry transformer (3.1 A primary, 12.5 A secondary) gets two 4 A time-delay primary fuses, one 15 A secondary fuse and a padlockable 600 V, 30 A rotary disconnect in a 16 x 14 x 8 in stainless NEMA 3R enclosure with a sloped top and two 1/4 in drains. Its 15-45 W of losses lift the inside air about 20 K, so no fan is needed.

NEMA4 Enclosure engineering team · Published November 23, 2026 · 7 min read

Short answer: build this one from parts. Packaged outdoor transformer-disconnect combinations start at 5 kVA and switch with breakers, so a 1.5 kVA job means a dry transformer, three fuses and a padlockable rotary disconnect in a custom NEMA 3R box. Below: the fuse sizes with the arithmetic, the box size and layout, the heat check that shows why no fan is needed, and the openings that keep the rain rating. The last section is the spec to send for the quote. If the transformer lands on a pad or pedestal instead of a wall, the outdoor pedestal transformer article covers that version.

Is there an off-the-shelf 1.5 kVA NEMA 3R transformer enclosure?

Nothing packaged fits this size: the smallest outdoor transformer-disconnect combinations are built for 5 kVA and up, with a primary breaker and a load center instead of your three fuses, so the practical route is parts in one custom box. Indoor transformer-disconnect combinations do come in this size range. Their steel cabinets carry an indoor rating with no rain test, so they answer the layout question and skip the weather one. The outdoor parts list stays short:

  • 1.5 kVA dry transformer, 480 V to 120 V, single phase
  • two 4 A time-delay primary fuses in 10 x 38 mm holders
  • one 15 A time-delay secondary fuse
  • a padlockable 600 V, 30 A rotary disconnect
  • the NEMA 3R enclosure itself

We fold, cut and seal the box to your drawing; you buy the electrics from your panel distributor. Delivery runs 10 business days from your approval of the drawing.

What does NEMA 3R protect against outdoors?

NEMA 3R is the outdoor rain and sleet rating: the rain test in NEMA 250 sprays the assembled box through standard nozzles at 5 psi [34 kPa], and the scope is falling rain, sleet and ice — no hose washdown, windblown dust or submersion. Falling rain and ice formation are exactly what the type names.

Washdown changes the answer. Type 4 takes a hose stream of 65 gallons per minute from a 1 in nozzle, so a panel near wash spray is a Type 4 job. Salt air changes the material and the designation; the NEMA 3R vs NEMA 4 guide sorts those cases. The type on the label is a manufacturer rating for the built design — rated NEMA 3R by the manufacturer; not UL listed.

How do you size the three fuses?

The primary draws 1500 VA ÷ 480 V = 3.1 A and the secondary draws 1500 VA ÷ 120 V = 12.5 A, so the box carries two 4 A time-delay primary fuses and one 15 A time-delay secondary fuse. Size the primary pair under the NEC ceiling: the transformer table in the NEC allows primary protection at 150 % when primary current runs 2 to 9 A, which is 4.7 A here, and the chosen fuses load it to 128 % of rated current.

Energization pulls magnetizing inrush of 10 to 25 times full-load current for the first cycles. UL 248-8 requires a time-delay fuse to hold 5 times its rating for at least 10 s, so the time-delay curve rides the inrush where a fast-acting fuse blows on switch-on.

The secondary fuse protects the 120 V wiring: 125 % of the 12.5 A secondary is 15.6 A, so the chosen size fits under the ceiling. Fuse the ungrounded leg and bond X2 to the enclosure ground once, at the transformer. Both pairs sit in Class CC holders on DIN rail, labelled PRI and SEC. Grounds run green per NEC 250.119 and size from the fuses through NEC Table 250.122; 14 AWG is the table floor, so run 12 AWG. Bonding and bar layout live in the enclosure grounding and bonding guide. The same arithmetic scaled up is primary fuse-sizing walkthrough for a 45 kVA transformer. Padlock the disconnect off and prove the primary lugs dead with a meter before touching them.

What disconnect goes on the door?

A padlockable rotary disconnect does the lockout: a 600 V, 30 A frame dwarfs the 3.1 A primary load, its handle mounts through the door, and the handle locks in the off position with the operator's own padlock. A non-fusible switch fits this build because the fuses live on the DIN rail; a fused rotary switch is the single-device alternative.

Door-mounted rotary operators interlock the door closed while the handle is on, and the shaft cutout belongs on the drawing. Height: NEC 240.24(A) wants the center of the handle grip, at its highest position, no higher than 2.0 m (6 ft 7 in) above the floor or platform. Working space comes from NEC 110.26(A): the 120 V circuits fit the 3 ft (900 mm) Condition 1 depth, and the 480 V-to-ground side sits in a deeper band, so keep 4 ft [1.2 m] clear in front. The wall anchoring details are in the secure wall-mount article.

How big should the box be?

Order a 304 stainless NEMA 3R box at 16 x 14 x 8 in: the 8 in depth stacks the transformer on the floor, the disconnect mechanism and fuse holders on the panel, and 3 in [75 mm] of clear space in front of the terminals. Lay it out in three zones.

The transformer bolts to the back panel, low and left; a dry type this size weighs about 10 kg [22 lb] on most maker datasheets, so four M6 bolts carry it, and the control transformer floor-mounting article shows the detail. DIN rail runs across the middle for the fuse holders and terminal blocks. NEC 312.6 sets the wire bending space at terminals; 12 AWG needs a modest loop, and the 3 in of clear depth covers it with margin. Material: 304 stainless inland, 316L within reach of salt or brine. The fundamentals of fitting the box sit in the enclosure sizing guide.

How hot does the box run, and does it need a fan?

It needs no fan: the transformer's losses run 1-3 % of 1500 VA, so 15-45 W, and the worst-case 45 W lifts the inside air just 20 K above ambient in this stainless box. Worked example at the worst case: exterior surface = 2 x (16 x 14) + 2 x (16 x 8) + 2 x (14 x 8) = 928 in² = 0.60 m².

Wall transfer for stainless is 3.7 W/m²K, so the rise is 45 ÷ (3.7 x 0.60) = 20 K. At a 40 °C summer ambient the air inside sits near 60 °C. The transformer is built for that; its insulation class exists so it can run hot, and nothing else in the box objects. The same box in painted steel (5.5 W/m²K) rises 13.6 K instead.

Keep the box sealed and skip the fan. A fan needs a rated assembly and an opening in the roof or door, while the sealed design holds the 3R rain intent. If a 24 V supply or small PLC moves in later, add its nameplate loss to the 45 W; every 10 W adds about 4.5 K. Breathers, vents and ratings are the subject of the breather vent article.

What keeps the rain rating after the cutouts?

Every opening goes on the drawing: a solid top, one door cutout for the disconnect shaft, two bottom gland entries aimed down, and two 1/4 in drains at the bottom rear edge — factory-cut openings in the built design hold the NEMA 3R rating. The solid roof matters most; water lands there first.

Drains are part of the design. NEC 314.15 approves drainage openings of 1/8 to 1/4 in in boxes for damp and wet locations, and a 3R build counts on that weep path. Conduit and gland entries sit in the bottom wall facing down — the wall-mount orientation article explains why the top stays solid. Mounting feet bolt through the back wall from inside so the rain face stays unbroken; the weatherproof box mounting article shows the detail. Openings cut after the fact are the subject of the article on the rating a panel keeps after field cutouts. Ask for a sloped top in the drawing: a few degrees of roof pitch sheds rain before it finds the door seam.

What goes on the order?

Send one transformer, its three fuses, a lockable rotary disconnect and the enclosure spec in this table — every line matches the numbers above, and the quote comes back with a drawing to approve.

Item Order as
Transformer 1.5 kVA, 480 V to 120 V, single-phase dry type
Primary fuses 2 x 4 A time-delay, 600 V, 10 x 38 mm, Class CC holders
Secondary fuse 1 x 15 A time-delay, 10 x 38 mm
Disconnect Padlockable rotary, 600 V, 30 A, door-mounted
Enclosure 304 stainless NEMA 3R, 16 x 14 x 8 in, sloped top, solid roof
Openings 2 x bottom gland hubs, 2 x 1/4 in drains at the bottom rear
Grounds 12 AWG green to a bonded bar, NEC Table 250.122 minimum
Delivery 10 business days from approval of the drawing

Decide by site. Inland rain exposure takes the build above in 304 stainless. Coastal salt takes 316L with the Type 4X designation, whose test adds 200 hours of salt spray against an AISI 304 specimen. Washdown or hose spray around the panel moves the whole job to Type 4. If the load list grows or the transformer passes 5 kVA, weigh one transformer or two for the remote outdoor cabinet before ordering the bigger box.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
16 × 14 × 8 in304 stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can the primary fuses be 5 A instead of 4 A?

Yes. The NEC transformer table sets the primary ceiling at 150 % of the 3.1 A primary when that current runs 2 to 9 A — 4.7 A here — and its next-standard-size allowance takes the rating to a 5 A time-delay fuse. Both sizes ride the energization inrush on the time-delay curve; the smaller pair clears a fault tighter, which suits a pure control load.

Why does the secondary get only one fuse?

Because the secondary is 120 V with one leg bonded to the enclosure ground: only X1 is ungrounded, so one fuse covers the circuit and a fuse in the bonded leg adds nothing. Size it at or under 125 % of the 12.5 A full-load current — a 15 A time-delay fuse does that with margin. Fuse each added load branch separately when you split the outputs.

Will rain get in through the bottom drains?

Some will, and that is the design: a Type 3R box sheds falling rain and drains what gets past the door seam. The two 1/4 in openings sit at the bottom rear edge, inside the 1/8 to 1/4 in range NEC 314.15 approves for drainage in wet-location boxes. Mount the enclosure level so water reaches them instead of pooling in a low corner.

The site sits on the coast — what changes on the order?

Change the material to 316L and ask for the box as Type 4X. Near salt air, the molybdenum in 316L improves pitting and crevice resistance, and Type 4X is the designation whose test adds 200 hours of salt spray against an AISI 304 stainless specimen, so the spec matches the site. Fuses, disconnect and layout stay exactly as above.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

Check the heat load in the calculator · NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides